| 1 | S/F of Double Pole Structure of 410 SP/55 11 M. long Pole STP in 1:3:6 CC foundation wioth 3 with 3 No. M long 100 mm x 50 mm x 5 mm and 2 No. 2 M. long 75 mm x 40 mm x 5 mm MS Channel, 2 No. 2.5 M. long 50 mm x 50 mm x 5 mm Angle Iron Braching and 14 No. 38 mm x 6mm D Clamp with necessary Packing Pieces complete with 250 KVA 11/0.433 KV, Level-2 BIS Standard, as per present UPPCL's Specifications & approved make including Pole mounted Transformer 11 KV TPMO & Fuse Set, earthing etc, Rate excluding deducting Plinth & LT MsCB Box. |
| 2 | S/F of TPN/ Telex Feeder Pillar Cubical Box made of 45mm x 45mm x 5mm Angle Iron frame and 14 SWG MS Sbheet with Both side Lockignarrangement. Dust and Vermin Proof consisting with Copper Bus Bar on Henry type Fuse unit on 2 No. 500 Amp and 3 No. 300 Amp. Tailless unit Completethe Box shall be Painted with approvedaluminium Paint over Red Oxide Primer in 1:3:6 CC foundation as directed by E/I. |
| 3 | S/F of 200 Amp Busbar Box made of 16 SWG CRCA Sheet including TPN Aluminium Busbar complete with locking arrangement with required Clamps nuts & bolts and grouting / .Fixed |
| 4 | S/L of Aluminiuum conductor PVC Insulated armoured served sheathed 400Sq mm x 3.5 Core LT cable 1100 volts grade at a deopth of 750mm below groundlevel over a cushion of 756 mm. Thick sand all around and protectedwith burnt bricks on sides and on top. |
| 5 | Same as Above but size 240 Sq mm x 3.5 Core. |
| 6 | S/L of 3 Core standard aluminium conductor XLPE (Cross linked Polyethylene) insualted PVC bedded, Galvanied flat steel strip armored 185 Sqmm 3 Core 11 KV grade cable confirming to I.S. 7098 ( Part-II with latest amendement) at a depoth of 900 mm below ground level ovdr a cushion of 100 mmthick fine rriver. sand al around and protected with well burnt bricks in sides and on top purt across. |
| 7 | S/F of 185 Sq mm 11 KV Joint Kit complete. |
| 8 | S/F of 400 Sq mm cable Lugs . |
| 9 | S/F of 240 Sq mm cable Lugs . |
| 10 | S/E of overhead line 3x95 S + 1x70 Sqmm + 1x16 Sqmm Arial Bunched conductor on poles I |
| 11 | T/L with HDPE 150 mm in 33 KV/100 mm in 11 KV & LT dia HDD for carring of Cable on Road Crosing complete with Repairing of all internal water connection/Sever Connection |
| 12 | Dismantling & Store /Street light Poles /PCC/Rail as per direction of UPPCL with Loading unloading cartage of Pole embedded in brick ballast & CC foundation etc. as required. |
| 13 | Dismantling of over head lines Wires/ ABC comprising of copper/aluminium overhead conductor, G.I, wire, cross arms, insulators etc, as Required & Deposite as per direction of UPPCL with Loading unloading cartage of all material with proper listing. |
| 14 | S/F of Steel tubualr Pole 9 M. Long designated 410 SP-32 in 1:3:6 cement concrete foundation including excavation back filling etc. complete |
| 15 | S/F of Steel bubular Pole 11 M. long designated 410 SP/55 in 1:3:6 cement concrete foundation including excavation back fillingetc. Complete |
| 16 | S/F of MS Channel, V shape, Bracing, Angel, Clamps and other required MS Iron Items etc. |
| 17 | S/F of 100 mm x 110 mm shackle insulator or 100 mm x 80 mm Pin insulator including G.I. Bolts/spindle nuts etc. |
| 18 | S/f of 11 KV Pin insulator complete with Pin, Nuts, & Bolts complete with Gun fiting complete. |
| 19 | S/f of 11 KV Disc insulator complete with Fittings , Nuts. & Bolts complete with Gun |
| 20 | S/E of overhead line with ACSR conductor on Poles/service brfackwet including binding etc. |
| 21 | S/E of overhead line with GI Wire 8 to 4 SWG on poles/service bracket including binding etc. |
| 22 | S/E of Stay set at least 3.5 M. away from the Pole complete with galvanised 19 mm diax 1.80. M. long Sary clamps, stay insulator 19 mm x 600 double screw tightener, 7/4.00 mm G.I. stary wire etc. in 1:3:6; cemtn concrete complete . |
| 23 | Painting of the electric pole with 2 coats of aluminium paint over red primncer complete |
| 24 | Earthing of pole by MS earthing rod of 20x2500mm and 6 SWG earthing wire etc |
| 25 | S/F of 100 mm dia GI Pipe Clas B Make Jindal Complete with required clamping . |
| 26 | S/F of Dead End Insulated Clamps complete on Poles as direction of E/I. |
| 27 | S/E of Suspension Insulated Clamps complete on Poles as direction of E/I. |
| 28 | S/Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. |
| 29 | Deduction of Cable Rate during errection in Pipe/Duct |
| 30 | Supply and fixing of 90 Watt LED street light Fitting having die cast aluminium body and diffuser with driver set suitable for 90 Watt. Confirming to IP 66 Protection complete in all respect. |
| 31 | S/F of followign capacity of Automatic street light cubicle control Panel painted with anti corrosive alkeli and acie proof paint considting of tme switch TSO 100 serive/Digital type with Contactors, HRC fuses, 100 Amp MCCB isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complte |
| 32 | S/L of 6 Sq mm Twin Flate unarmoured cable complete with proper connection. |
| 33 | S/L of 110 mm Dia HDPE pipe having pressure rating…….1 Extra Item Please Enable Macros to View BoQ information |