| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : Garrison Engineer Kapurthala Name of Work : Repair/ replacement/ maintenance of external LT distribution, equipments and allied works at Mil Stn Kapurthala under GE Kapurthala. Contract No : GE KPT- /2026-27 Bidder Name : SCHEDULE OF WORKS(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # S.No Description of work Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Taking down existing LT panel by disconnecting all incoming and outgoing cables, earthing connection, dismantling PCC and making good the disturbed surface all as directed |
| 3 | Supply, install, testing and commissioning of LT Distribution Panel (CPRI) cubicle type IP-65 , Outdoor type confirming to IS-61439 factory fabricated prewired made out of 3.15 mm thick CRCA sheet outer & 2 mm thick CRCA sheet inner of suitable size to accommodate all accessories/ fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB ad TPN bus bars and outgoing feeders. The TPN bus bars shall be insulated with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision of termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of platform. The plateform of LT Panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class 'B') work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-Charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY structure after seven tank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter with min 3 hinges on each door and shall have louvers and air vent gasket for natural flow of air Neoprene Adhesive type gasket shall be used to make panel vermin proof and comprising of the following |
| 4 | Incoming : (i) MCCB 4P 400 Amps, 36 KA 415 Volts (Thermal and magnatic release adjustable range from 70% to 100% ) - 01 No (ii) TPN Aluminium bus bar of capacity min 1.5 times of IC MCCB -01 No'sOutgoing : (i) MCCB FP 160 Amps 16 KA 415 Volts (Thermal and magnatic release, adjustable range 70% to 100%) - 03 N(ii) MCB TPN, 63 Amps, 16 KA 415 Volts.- 02 No's(iii) Digital type Digital Timer switch suitable for 3 phase, 415 volts AC supply for street light feeder programmable 1 min, with backup for 6 years, 28 memory locations, current capacity 10 Amps weekly program with 1 changeover |
| 5 | Incoming : (i) MCCB 4P 250 Amps, 36 KA 415 Volts (Thermal and magnatic release adjustable range from 70% to 100% ) - 01 No (ii) TPN Aluminium bus bar of capacity min 1.5 times of IC MCCB -01 No'sOutgoing : (i) MCCB FP 100 Amps 16 KA 415 Volts (Thermal and magnatic release, adjustable range 70% to 100%) - 02 N(ii) MCB TPN, 63 Amps, 16 KA 415 Volts.- 02 No's(iii) Digital type Digital Timer switch suitable for 3 phase, 415 volts AC supply for street light feeder programmable 1 min, with backup for 6 years, 28 memory locations, current capacity 10 Amps weekly program with 1 changeover |
| 6 | Incoming : (i) MCCB TPN 160 Amps, 36 KA 415 Volts (Thermal and magnatic release, adjustable range 70% to 100%) - 01 No's (ii) TPN Aluminium bus bar of capacity min 1.5 times of IC MCCB -01 No'sOutgoing : (i) MCCB 4 pole 100 Amps 25 KA 415 Volts - 03 No'(ii) MCCB 4 pole 63 Amps 25 KA, 415 Volts - 02 No's (b) Combined Voltmeter & Ammeter 0 to 500 Amps digital type with built in selector switch CTS of suitable ratio (Set of Three) |
| 7 | M&L for earthing complete with galvanized iron or steel or steel earth plate electrode of size 60cmx60cmx6.3mm thick buried directly in ground, vertically to a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at depth of not less than 1.5 mtr below ground level surrounded from all sides with alternate layers of charcoal and common salt and connected to GI Strip of size 32x6 mm by means of GI bolts, nuts washers & check nuts electrode connected to main switch board or main control board or on poles or on transformer and GI pipe light grade 20 mm bore for watering including providing funnel and wire mesh GI frame and 10 cm thick suitably reinforced RCC pit cover PCC chamber pit with PCC 1:3:6 type C2 using 40mm graded stone aggregates complete including excavation and earth work, disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown in plate No 5 of SRR-1991 Part-1 . |
| 8 | M&L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as directed. |
| 9 | Preparation to steel surface of existing LT panels, LT feeder pillars boxes of any size and description internally and externally after scraping and scratching the old paint with emery paper etc, and painting with two coat of gray painting with spray gun and writing feeder names and numbers with suitable capital letters in English with white paint on and a black paint strip of size 20 cm x 25 cm all as directed. |
| 10 | M&L for repair to LT panels feeder pillar box by dismantling old rusted and perished doors shutter and bus bar covers etc and providing new doors shutters, bus bar cover etc by cutting, welding, fabricating and made to existing shape with 3.15 mm plain black sheet and angle iron of required size including providing hinges and locking arrangement all as directed including material and labour for two coat of painting with synthetic enameled Grey paint over a coat of red oxide primer. |
| 11 | S&F in replacement MCCB, 4 pole, 3 phase, 415 volts, 400 Amps, repturing capacity 35 KA with overload and thermal tripping features. |
| 12 | All as per item No 8 here-in-before but 315 Amps repuring capacity 36 KA. |
| 13 | All as per item No 8 here-in-before but 250 Amps repuring capacity 36 KA. |
| 14 | All as per item No 8 here-in-before but 200 Amps repuring capacity 25 KA. |
| 15 | All as per item No 8 here-in-before but TPN 160 Amps repuring capacity 25 KA. |
| 16 | All as per item No 8 here-in-before but TPN 125 Amps repuring capacity 16 KA. |
| 17 | All as per item No 8 here-in-before but TPN 25 to 100 Amps repuring capacity 16 KA. |
| 18 | S&F in repair on load change over switch 4 pole 400 Amps in sheet metal enclosure |
| 19 | S&F in repair on load change over switch 4 pole 200 Amps in sheet metal enclosure |
| 20 | S&F in repair aluminum thimbles/Lugs crimping type of size 16 to 25 Sq mm |
| 21 | S&F in repair aluminum thimbles/Lugs crimping type of size 50 to 120 Sq mm |
| 22 | S&F in repair aluminum thimbles crimping type of size 150 Sq mm to 240 Sq mm all as specified. |
| 23 | M&L for straight through joint (epoxy) for LT 1100 Volts grade, aluminum conductor including jointing kits, aluminium ferrules and labour complete for making joints and testing size 185 to 240 Sqmm, 3.5 core |
| 24 | All as per item No 20 here-in-before but cable size 120 to 150 Sqmm, 3.5 core |
| 25 | All as per item No 20 here-in-before but cable size 70 to 95 Sqmm, 3.5 core |
| 26 | All as per item No 20 here-in-before but cable size 25 to 50 Sqmm, 3.5 core |
| 27 | All as per item No 20 here-in-before but cable size 10 to 16 Sqmm, 4.0/2.0 core |
| 28 | Dismantling & taking down existing ACSR conductor of any size by opening the binding wire from HT/LT electric poles complete all as specified. Note ACSR conductors wil be replaced with LT UG cable item no 27 to 35 where applicable or as directed by Engr-in-Charge. |
| 29 | Supply, stringing and fixing on existing poles, ACSR conductor of any type/ size including fixing to insulators with binding wire complete all as directed by Engr-in- Charge |
| 30 | Taking out old defective underground cable from trenches/ floors/road/wall /pipe/ pole LT cable of any size/ description including segregating the serviceable cable by cutting down defective portion after testing by meggar and relaying (Note : Excavation and earth work will be measured separately under respective item) |
| 31 | Taking out old defective underground cable/ACSR from trenches/ floors/road/wall /pipe/ pole LT cable of any size/ description including segregating the serviceable cable by cutting down defective portion after testing by meggar. (Approx 2000 LT cable is reduced for old ACSR where required or if place at new places during emergency. |
| 32 | Supply, Laying, jointing and testing XLPE PVC insulated & PVC sheathed LT cable, 1100 volts grade (heavy duty )with stranded aluminium conductor, cross sectional area 10 Sqmm 2 core fixed along the poles or passing through pipes or laid under floors or through walls complete all as specified. Note (i) Earthwork, sand cushioning, brick protection and GI pipe to be measured and paid for separately under respective items. |
| 33 | All as per item no. 29 here in before but cross sectional area 16 Sqmm 2 core |
| 34 | All as per item no. 29 here in before but cross sectional area 16 Sqmm 4 core |
| 35 | All as per item no. 29 here in before but cross sectional area 25 Sqmm 3½ core |
| 36 | All as per item no. 29 here in before but cross sectional area 35 Sqmm 3½ core |
| 37 | All as per item no. 29 here in before but cross sectional area 50 Sqmm 3½ core |
| 38 | All as per item no. 29 here in before but cross sectional area 70 Sqmm 3½ core |
| 39 | All as per item no. 29 here in before but cross sectional area 95 Sqmm 3½ core |
| 40 | All as per item no. 29 here in before but cross sectional area 120 Sqmm 3½ core |
| 41 | All as per item no. 29 here in before but cross sectional area 240 Sqmm 3½ core |
| 42 | M&L for excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for laying of cables and getting out including trimming of sides complete all as specified and directed by Engineer-in-Charge. |
| 43 | Returing, filling in, including spreading, leveling watering and well ramming inlayers not exceeding 25 cms thick each layer compete all as specified and directed. |
| 44 | Removal of surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-charge. |
| 45 | M&L for sand cushioning with a layer of sand 8cm thick before laying of cable and 15 cm thick after laying of cable in trenches complete all as specified. |
| 46 | Supply & laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/abutting each other complete all as specified and directed by Engineer-in-charge. (for LT Cable ) |
| 47 | M&L for road cutting for laying of LT UG cable /Galvanised Iron Pipe/Rex Pipe complete all as specified |
| 48 | M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate for fdn of poles, stay etc. |
| 49 | M&L for PCC 1:3:6 type C1 using 20mm graded for padestal coping incl necessary formwork finished fair using extra cement. |
| 50 | S&F in replacement for GI protection pipe light grade for cable protection incl all fittings laid in trenches or fixed on pole all as specified for 50mm dia |
| 51 | S&F in replacement for GI protection pipe light grade for cable protection incl all fittings laid in trenches or fixed on pole all as specified for 80mm dia |
| 52 | Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting at side for re-use with in 50m |
| 53 | M&L for mild steel cross arms,bracing,supports,clamps and back plates fabricated from structural steel section including nuts,bolts washers,welding,bending cold or hot, drilling holes for bolts in any shape/size as directed including painting with two coats of approved colour over a coat red oxide primer all as specified and directed by Engr-in-Charge |
| 54 | Dismantling stay assembly complete. (demolition of concrete, etc. and excavationmeasured separately) |
| 55 | M&L for stay assembly with accessories in replacement as shown in electrical plate No.1 complete with diameter of rod 20 mm. Note:- loop type insulator, stay clamps, excavation and concrete will be measured and paid separately. |
| 56 | M&L galvanised stay strand size 7/4 mm complete all as specified and directed by Engr-in-Charge. |
| 57 | Taking down insulators off size & type. |
| 58 | S&F in repair pin type, porcelain,vitreous,white brown or green insulator including one galvnised mild steel spindle, two nos galvanised iron washer and one galvnised iron nut, 100mm height,65mm dia for 1100v grade |
| 59 | S&F in repair shackle, porcelain,vitreous,white brown or green insulator including galvnised mild steel straps, washers,insulator, bolts, washers and nuts for size 100mm height and 115mm dia for working pressure 1100 Volts |
| 60 | M&L for dismantling of the existing old rusted Steel/RCC poles of any type |
| 61 | S&F in replacement of steel tubular swaged poles type 410 SP-31 (9 mtr long) complete with CI base plate and finial taper plug,bolts, nuts and screws as specified all as directed by Engr-in-Charge. Note :- Excavation, earth & PCC work only will be measured separetely all other accessories and work deemed to be included in quoted rates. |
| 62 | S&F in replacement of prestressed concrete pole, 9.0 metres long, 102mm x 172mm at top and l2mm x 279mm at bottom, class 10 |
| 63 | M&L painting to steel tublar poles 9 m long with one coat of Synthetic enamel paint black & radium yellow paint combination Zebra marking up to 1 m from ground level /copping remaining Job portion painting with two coat of aluminium paint over a coat of red oxide including preparation of old painted surfaces complete all as specified and as directed. |
| 64 | M&L for marking/ numbering of steel poles / RCC poles with round background of balck paint colour of dia 20/ 25 cm alpha numeric number with each font length of 4/ 5 cm on yellow strip by black colour all as specified and directed by Engineer-in-Charge. (Note : Minimum 10 Nos alpha / numeric digit to be marked will be deemed to be included in each job) \\" |
| 65 | S&F in repair Volt meter 0-15KV with PT, digital type, suitable for LT panel 415V, as in replacement, complete all as specfied and directed. |
| 66 | S&F in repair ammeter, digital type, 200/5Amps & 100/5Amps, suitable for for LT panel 415V, as in replacement, complete all as specified and directed. |
| 67 | S&F in repair analog time switch 3 module of capacity 32A, suitable for LT panel 415V, complete all as specfied and directed. |
| 68 | S&F in repair modular contactor 3 module of capacity 16-40A alongwith add on block suitable for LT panel 415V, complete all as specfied and directed. |
| 69 | Supply, install, testing and commissioning of LT Distribution Panel (CPRI) cubicle type IP-65 , Outdoor type confirming to IS-61439 factory fabricated prewired made out of 3.15 mm thick CRCA sheet outer & 2 mm thick CRCA sheet inner of suitable size to accommodate all accessories/ fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB ad TPN bus bars and outgoing feeders. The TPN bus bars shall be insulated with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision of termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of platform. The plateform of LT Panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class 'B') work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-Charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY structure after seven tank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene Adhesive type gasket shall be used to make panel vermin proof and comprising of following :- (Bus Bar Panel). INCOMING : MCCB 4 Pole, 250 Amps ,415 Volt of breaking capacity 36 KA with Adjustable Thermal Magnetic - 01 Nos.Digital Multi function meter connected with suitable CTs and selector switch-1 No, Phase indicator RYB LED type - 1 Set |
| 70 | S&F in repair junction box factory made weather proof size 300mmx250mmx 150mm made of PVC inculded 25mmx6mm aluminium TPN bus bars & 01 MCB 6 Amps for controlled one No's of LED Lights complete all as specifed & directred |
| 71 | S&F in repair MCB SPN 240 volts 0- 32 Amps, 10KA, B-series. |
| 72 | M&L fo service wire and supply and fixing Service wire Al Conductor Weather Proof 6 Sqmm 2 core complete all as specified and directed. |
| 73 | M&L fo service wire and supply and fixing Service wire Al Conductor Weather Proof 10 Sqmm 2 core complete all as specified and directed. |
| 74 | Cutting the tree branches which touches the LT OH lines and 2.5 m away from centre line of LT OH line span not exceeding 60mts distance between poles by using necessory T&P items and depositing the tree branches/leaves at 30m distance away from the site. Note:- Any number of tree branches cut in one span will be measured as one length for payment pupose |
| 75 | M&L restreching, tightning and fixing of ACSR conductor of any size and capacity on LT electric poles including necessary aluminium bindingswires, connector, PVC sleeves for jumpers etc. complete all as specified and as directed. Note : The works includes one length will be measured for complete span of 4/5/6 ACSR conductor & GI wire. Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |