| 1 | Part A: Construction of 33KV Tap Line for newly proposed Industrial Estate Banderpora, Budgam. |
| 2 | Supply and Erection of 11 Mtr. Long ST Poles ( ST-410 SP 56) with welded steel base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any). |
| 3 | Providing and fixing of fabricated GI V cross-arm/GI Channel X-arm including belting/clamps and braces with top angle iron Bracket including clamp as per site requirement |
| 4 | Providing, Laying,stringing ,tensioning and binding of 100 mm² ACSR Conductor. |
| 5 | Providing and fixing of PG Clamps for 100 mm² ACSR Conductor as per site requirement |
| 6 | Supply,installation,testing, and commissioning of 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 7 | Supply,installation,testing, and commissioning of 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm With fitting. |
| 8 | Providing and fixing of Galvinized Nuts and Bolts with washers as per site requirements. |
| 9 | Providing and fixing of Danger Plates with Clamps of reputed make |
| 10 | Providing and fixing of Anti-Climbing Device with Clamps of reputed make |
| 11 | Providing and fixing of Earthing of ST poles Complete by GI Pipe 40 mm 3 mtr long throughGI Strip 25x3mm as per REC standards. |
| 12 | Providing and painting of ST Poles with One coat of Red Oxide and two coates of Aluminium Paint to give even shade (reputed brand) |
| 13 | Providing and laying of Cement bottoming 1:2:4 mix using 20mm crushed stone aggregate including shuttering, form work etc as per REC standards 0.66 cum/pole |
| 14 | Providing and fixing of Aluminium Jointing sleeves |
| 15 | Providing and fixing Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2No.), anchor plate (300x300 x 8 mm), nut-bolts, 2 No. turn-buckles, 1.8mlong,20 mm diameter solid GS stay rod & 7/4 mm dia GI stranded wire complete (33kV) |
| 16 | Providing and fixing of Guard netting as per REC standard. |
| 17 | Part B: Thickening of existing 33KV Tap line towards 33/11 KV Receiving station Kanir |
| 18 | Supply and Erection of 11 Mtr. Long ST Poles ( ST-410 SP 56) with welded steel base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any). |
| 19 | Providing, Laying, stringing, tensioning and binding of 200 mm² ACSR Conductor (panther). |
| 20 | Providing and fixing of PG Clamps for 200 mm² ACSR Conductor as per site requirement. |
| 21 | Providing and fixing of Fabricated GI V cross arm with top bracket including clamp |
| 22 | Supply,installation,testing, and commissioning of 33 kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm. |
| 23 | Supply,installation,testing, and commissioning of 33 kV Polymeric composite Disc Insulator 36KV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting. |
| 24 | Providing and fixing of Galvinized Nuts and Bolts with washers as per site requirements. |
| 25 | Providing and fixing of Earthing of ST poles Complete by GI Pipe 40 mm 3 mtr long throughGI Strip 25x3mm as per REC standards. |
| 26 | Providing and fixing of Danger Plates with Clamps of reputed make |
| 27 | Providing and fixing of Anti-Climbing Device with Clamps of reputed make |
| 28 | Providing and fixing of Aluminium jointing sleeves |
| 29 | Providing and painting of ST Poles with One coat of Red Oxide and two coates of Aluminium Paint to give even shade (reputed brand) |
| 30 | Providing and laying of Cement bottoming 1:2:4 mix using 20mm crushed stone aggregate including shuttering, form work etc as per REC standards 0.66cum/pole |
| 31 | Providing and fixing Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2No..), anchor plate (300x300 x 8 mm), nut-bolts, 2 No. turn-buckles, 1.8mlong,20 mm diameter solid GS stay rod & 7/4 mm dia GI stranded wire complete (33kV) |
| 32 | Dismantling of old conductor 100 sqmm ACSR and subsequent return of same to the divisional stores |
| 33 | Providing and fixing of Guard netting as per REC standard. |
| 34 | Note: The material utilized/works executed shall be stritctly as per REC Standards with Latest amendments there off. Please Enable Macros to View BoQ information |