| 1 | Taking down copper/aluminium point wiring (light, fan , socket or power) including fixtures and fittings such as switches, ceiling rose, pendant ,regulators,sockets,light fittings etc.removing materials and making good disturbed surfaces of wall, floor complete all as specified. |
| 2 | Taking down old/unserviceable sub main wiring any size/type complete all specified and directed. |
| 3 | Taking down old/unserviceable LT cable of any size/type complete all specified and directed. |
| 4 | Taking down unsv MCB Distribution board/Metal clad socket of any size/capacity/make complete all specified and directed. |
| 5 | Disconnecting & taking down flame proof tube light fitting of any capacity or description and refixing & reconnecting the same on same or new location complete all as specified. |
| 6 | Disconnecting & taking down flame proof flood light fitting of any capacity or description and refixing & reconnecting to same or new location complete all as specified. |
| 7 | Disconnecting & taking up flood light fitting of any capacity or description and refixing & reconnecting to same or new location complete all as specified. |
| 8 | M&L for flame proof point wiring with FRLSH PVC insulated PVC un-sheathed electric cable confirming to IS:694, 1100V grade AC single core having multi stranded FRLSH copper conductor of size 1.5 Sqmm nominal cross sectional area for phase & neutral drawn in & including 1.6mm thick concealed surface ERW stove enamelled rigid mild steel conduit conforming to IS: 9537 of size not less than 20 mm dia including fitting such as mild steel junction box, mild steel couplings unions, bends, reducers, inspection elbow, sealing conduits, plugs etc conduit ISI marked in surface wiring system with and including 1.5 Sqmm green PVC insulated unsheathed FRLSH copper conductor cable as earth wire connected to earth dolly by providing lugs complete Flame proof lumiiares and draw in the same concealed conduit complete all as specified and directed. |
| 9 | All as per Item No-8 Above but for One 3 pin/5 pin socket out let 16 Amp on independent board with independent circuit from DB box with 2.5 sqmm PVC insulated, unsheathed single core multistranded copper conductor cable 1100 volts grade including 2.5 sqmm PVC insulated unsheathed solid copper conductor cable as earth continuity conductor complete all as specified & directed. |
| 10 | M&L for flame proof sub main wiring drawn in and including concealed ERW stove enamelled rigid mild steel conduit conforming to IS: 9537 of size not less than 25 mm dia medium grade with FRLSH PVC cable 04 Sqmm nominal area 4 run single core PVC insulated unsheathed cable with stranded copper conductor incl 01 run of 04 Sqmm size FRLSH PVC cable stranded copper conducter as earth continuity wire and connected to earth dolly with proper crimping of thimbles bottle type complete all as specified and directed. |
| 11 | M&L for flame proof sub main wiring drawn in and including concealed ERW stove enamelled rigid mild steel conduit conforming to IS: 9537 of size not less than 20 mm dia medium grade with FRLSH PVC cable 2.5 Sqmm nominal area 2 run single core PVC insulated unsheathed cable with stranded copper conductor incl 01 run of 2.5 Sqmm size FRLSH PVC cable stranded copper conducter as earth continuity wire and connected to earth dolly with proper crimping of thimbles bottle type complete all as specified and directed. |
| 12 | Supply & fix Switch flame proof rotary type with termination box in LM6 ,16 Amp single pole 250V complete all as specified and directed. |
| 13 | Supply & fix Flame proof switch socket and plug combined in LM6 cable termination box ,16 Amp 250V, 2P+Earth complete all as specified and directed. |
| 14 | Supply and fix Flame proof - weather proof switch socket & plug combined 16A, 500 V(3P+Earth) complete all as specified and directed. |
| 15 | M&L for flame proof sub main wiring drawn in and including concealed ERW stove enamelled rigid mild steel conduit conforming to IS: 9537 of size not less than 32 mm dia medium grade with FRLSH PVC cable 10 Sqmm nominal area 4 run single core PVC insulated unsheathed cable with stranded copper conductor incl 01 run of 10 Sqmm size FRLSH PVC cable stranded copper conducter as earth continuity wire and connected to earth dolly with proper crimping of thimbles bottle type complete all as specified and directed. |
| 16 | M&L for flame proof sub main drawn in and including concealed ERW stove enamelled rigid mild steel conduit conforming to IS: 9537 of size not less than 32 mm dia medium grade with FRLSH PVC cable 6 Sqmm nominal area 4 run single core PVC insulated unsheathed cable with stranded copper conductor incl 01 run of 6 Sqmm size FRLSH PVC cable stranded copper conducter as earth continuity wire and connected to earth dolly with proper crimping of thimbles bottle type complete all as specified and directed. |
| 17 | Supply, laying (in replacement), jointing, testing and commissioning Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 10 Sqmm 2.0 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: Excavation & earthork, sand cushioning and bricks for protection of cable shall be measured and paid separately. |
| 18 | Supply and fix flame proof, zone I & II, Gas group IIA/IIB, weather proof DB TPN 415 volts 8 way with busbar in cast aluminium LM-6 enclosure operated externally spring type knob complete with suitable incoming and outgoing cable entries with cable glands suitable for hazardous area and confirmiing to IS-2147/62 neoprene gasket degree of protection IP65 suitable for MCCB TPN 63 Amps - 01 Nos (Incoming) and MCB SP 6-32 Amps - 24 Nos including connecting up with three core flexible copper conductor cable with suitable and taking down old unserviceable DBs, |
| 19 | Supply and fix flame proof, zone I & II, Gas group IIA/IIB, weather proof DB TPN 415 volts 4 way with busbar in cast aluminium LM-6 enclosure operated externally spring type knob complete with suitable incoming and outgoing cable entries with cable glands suitable for hazardous area and confirmiing to IS-2147/62 neoprene gasket degree of protection IP65 suitable for MCCB TPN 63 Amps - 01 Nos (Incoming) and MCB SP 6-32 Amps - 12 Nos including connecting up with three core flexible copper conductor cable with suitable and taking down old unserviceable DBs, |
| 20 | Supply and fix flame proof, zone I & II, Gas group IIA/IIB, weather proof DB SPN 415 volts 4 way with busbar in cast aluminium LM-6 enclosure operated externally spring type knob complete with suitable incoming and outgoing cable entries with cable glands suitable for hazardous area and confirmiing to IS-2147/62 neoprene gasket degree of protection IP65 suitable for MCB SPN 16 Amps - 01 Nos (Incoming) and MCB SP 6-32 Amps - 02 Nos including connecting up with three core flexible copper conductor cable with suitable and taking down old unserviceable DBs, Make Shyam/Sudhir/Flexpro |
| 21 | Supply and fixing LED light fiting 2x16 watt flame proof, CMRI cerified recommended for gas/vapor group of IIA/IIB, Zone 1&2 and IP 65 protection with die cast aluminium housing with heat resistant toughened glass with LED tube light flame proof fixtures driver, holders, connector etc. complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size fixed in repair/replacement complete all as specified and direct.Make Shyam/Sudhir/Flexpro |
| 22 | Supply and fixing LED light fiting 1x16 watt flame proof, CMRI cerified recommended for gas/vapor group of IIA/IIB Zone 1&2 and IP 65 protection with die cast aluminium hosing with heat resistant toughened glass with LED tube light flame proof fixtures driver, holders, connector etc. complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size fixed in repair/replacement complete all as specified and direct.Make Shyam/Sudhir/Flexpro |
| 23 | Supply and fixing LED down light fitting 70 watt flame proof, CMRI cerified recommended for gas/vapor group of IIA/IIB, Zoen 1&2 IP 65 protection with die cast aluminium housing with heat resistant toughened glass, with LED flame proof fixtures, drivers complete, prewired including connecting up with three core flexible copper conductor cable with suitable size fixed in repair/replacement complete all as specified and direct. Cat No WG/1240, of Sudhir or equivalent model.Make Shyam/Sudhir/Flexpro |
| 24 | Supply and Fixing LED down light fitting 200 watt flame proof, CMRI cerified recommended for gas/vapor group of IIA/IIB, Zoen 1&2 IP 65 protection with die cast aluminium housing with heat resistant toughened glass, with LED flame proof fixtures, drivers complete with all respect, prewired and including connecting up with three core flexible copper conductor cable with suitable size fixed in repair/replacement complete all as specified and direct. Cat No WG/1240, of Sudhir or equivalent model.Make Shyam/Flexpro |
| 25 | Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out cables and foundation of poles etc. and getting out in soft/loose soil, complete all as specified and as directed. |
| 26 | Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick each layer complete all as specified and as directed. |
| 27 | Removal of surplus excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5metre above the starting point complete all as specified and as directed. |
| 28 | Material and labour for sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts complete all as specified and as directed. Note : Punned down thickness (overall 18cm) shall be considered for measurement and payment. |
| 29 | Supply and laying well burnt sub class 'B' bricks for cable protection laid flat ,length wise, perpendicular to the axis of cable, complete all as specified. |
| 30 | Supply and laying/fixing GI pipe light grade 40mm bore for cable protection fixed to pole/wall or laid under floor/road/pavement with nuts, bolts, clamps etc as required including taking out old pipe complete all as specified and as directed. |
| 31 | Note: The Total amount shall subject to adjustment of credit of Rs. 164545.00 for old Materials as per Schedule of Credit. Please Enable Macros to View BoQ information |