| 1 | (PUBLIC ADDRESS SYSTEM)Supplying, installation, testing & commissioning of 10 zone, voice alarm controller with USB, MP3 player (including10 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required. |
| 2 | Supplying, installation, testing & commissioning of Call station complete as required. |
| 3 | Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
| 4 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. |
| 5 | Supplying, installation, testing & commissioning of digital audio amplifier240 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
| 6 | Supplying, installation, testing & commissioning of Voice command keypad10 zone, with microphone assembly complete as required. |
| 7 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. |
| 8 | Speaker cable Two pair, 2-core, 1.5 sqmm |
| 9 | Supply hdpe pipe for external cable laying |
| 10 | (FIRE ALARM SYSTEMS ) |
| 11 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 12 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 13 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 14 | Two Loop Panel |
| 15 | Supply & fixing of Addressable type smoke detector with base complete in all respects |
| 16 | Supply testing & commissioning of fault isolator module for isolation of short circuit, |
| 17 | Supply, installation, integrating with the existing main FACP, testing & Commissioning of Auto dialer with addressable control module connected to main control panel including connected cabling/wiring complete in all respects, as per technical specification. |
| 18 | Supply, installation, integrating testing & Commissioning of addressable control module |
| 19 | Supplying and fixing of 2.0 mm thick signboards as per fire norms and directions of EIC etc complete as required. |
| 20 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 21 | (DOWN COMER SYSTEM) |
| 22 | Pvc water tank with complete(5000X2) |
| 23 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) |
| 24 | (a) Horizontal type, multistage, centrifugal,Monobloc pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 |
| 25 | b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class- 'F' insulation, conforming to IS-325. |
| 26 | (c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. |
| 27 | (d) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 28 | i)450 lpm at 35 m Head |
| 29 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 30 | i)100 mm dia |
| 31 | ii)80 mm dia |
| 32 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe below gound level with wrapping and coating complete as required : |
| 33 | i)100 mm dia |
| 34 | SITC of the internal landing valves shall be single-headed made of s.s and conforming to IS:5290. It shall be complete with hand -wheel, quick coupling connection spring loaded type and blank cap |
| 35 | Ss hydrant valve 63 mm |
| 36 | SITC of 63mm dia Hose pipe Reinforced Rubber lined as per IS:636 type-A respectively with 15 M standard length including SS metal male and female Coupling duely bound with GI wire,etc. including all required accessories for fixing hoses in the fire shaft Complete As directed by engineer in charge. |
| 37 | SITC of SS branch pipe with 63mm dia female inlet and male threaded outlet with hexagonal based nozzle as per IS 903 |
| 38 | 63 mm branch pipe |
| 39 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 40 | i)30 m |
| 41 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 42 | i)100 mm dia |
| 43 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
| 44 | i)100mm dia |
| 45 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. |
| 46 | i)100mm dia |
| 47 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 48 | i)2 way-100 mm dia M.S. Pipe |
| 49 | Providing & fixing of pressure switch inM.S. pipe line including connection etc. as required. |
| 50 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 51 | Supplying of following size PVC insulated and PVC sheathed / XLPE aluminium conductor armoured power cable of 1.1 kV grade etc. as required. |
| 52 | i) 3.5X 6 sqmm |
| 53 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 54 | i)Upto 6 sq. mm |
| 55 | Fabrication, supplying, installation, testing & commissioning of compartmentlised floor mounted cubical out door type Fire fighting Auto panel fabricated out of 2 mm, thick CRCA sheet,3mm thick gland plates complete with 4 strips 100 A Al bus bar with hinged lockable doors, outdoor type, powder coated of approved shade after 7 tank treatment process, earthing with 2 nos earth strips of GI of size 25 mmx3mm , internal wiring, earth terminals, numbering etc, complete in all respect, suitable for operation on 415 V, 3 phase, 50 Hz, AC supply and pdg & fixing following switch gears. |
| 56 | Incoming |
| 57 | i. 100 A, MCCB FP 16 KA (Incoming) 1 No. |
| 58 | ii. Multi functional meter- 1 No |
| 59 | iii. 32amps, MCB - 2 Nos. |
| 60 | iv. single phase preventer-2 nos |
| 61 | v. add on auxillairy contact 40A 4 NO-2 nos |
| 62 | vi.LED type indicating lamps with 2 amps SP MCB's for protection -3 Nos |
| 63 | vii.100/5 amp,15 VA CT |
| 64 | viii.Rotary handle for MCCB |
| 65 | (FIRE EXTINGUISHERS) |
| 66 | Supplying, installing, testing and commissioning of 4.5 kG capacity stored pressure type carbon dioxide type fire extinuishers made from brand new seamless drawn steel cylinder as per IS 7285 with ISI mark, fitted with wheel valve as per IS 3224 with ISI mark, with discharge bend and horn and complete with initial charge as per IS 15683 with ISI mark and wall bracket complete as required. |
| 67 | Supplying, installation, testing and commissioning of ABC stored pressure type Fire extinguishers of 4 KG capacity fitted with discharge control valve and pressure gauge, filled with mono ammonium phosphate powder as per EN 3615 approved and supplied complete with initial charge as per IS: 15683 with ISI mark and wall bracket complete as required. |
| 68 | (CIVIL WORKS) |
| 69 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : |
| 70 | 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 71 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. |
| 72 | All kinds of soil |
| 73 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. |
| 74 | All kinds of soil. |
| 75 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 76 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) Please Enable Macros to View BoQ information |