| 1 | Material and labour for structural steel work as in base plate for pumpsets with nut bolts washers welding and necessary fabrication work in any situation valve chamber covers and similar items etc as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including taking down the existing unserviceable items complete all as specified and directed. |
| 2 | Supply and spread / fill high strength calcium based granular chlorination chemical(Grade I)(Packing in 45 KG)of following specifictons:- (a) Description- Whitish granules (b) Garnular Size(Mesh passing through-100BSS): 1.1(+0.1)%(c) Other insoluble calcium salts: 1.1(+0.1)% (d) Requirement must be 140-200gms per one lac liter of water to achive 1PPM at injection point all as specified and as directed. |
| 3 | Supply and spread bleaching powder suitable grade conforming to IS specification No 1065/1989 with minimum available chlorine percentage of mass 33.5% and slab percentage Nil all as specified and as directed. |
| 4 | Supply and spread sodium hypochloride solution with active chlorine content 6gm / ltr conforming to IS 11673 in 35 ltrs capacity container all as specified and as directed. |
| 5 | Supply and repalce FRP chemical dosing pump with storage tanks 150 litres capacity pressure upto 10Kg/sqcm suitable for existing STP FRP chemical dosing pump all as directed. |
| 6 | Cleaning of Bar screen chamber 4.275 Cum capacity having one compartment by specialized water tank clean process as under and writing the details like 'Cleaned ON ',\\"sump capacity\\" with white enameled paint over black painted surface on sump (02 Nos,) all as specified and as directed. (a) Dewatering using submerssible pump/bailing out of water to dispose the minimum level of dirty water from the tank (b) Cleaning the tank bottom, walls and ceiling using high pressure water jet to dislodge the algae calcinations, dirt etc.(c) Disposing the dirt water sludge etc., using specially desinged sludge removal pump.(d) Cleaning the tank inside thoroughly by using industrial grade vacuum pump to make the tank inside free from dirt, algea and sludge etc.(e) Treating the inside walls, bottom, ceiling of tank including all nooks and corners by using and spraying anti bacterial agent such as Hydrogen peroxide (bio degradable) for disinfection of tank inside(f) Total disinfection and sterilisation of tank hygienically cleaned and bacteria free and safe for storage of water |
| 7 | All as per item No.06 here in before but SBR tank 137.5 Cum capacity(01 No) and 20 Cu m (01 Nos) |
| 8 | All as per item No.06 here in before but chlorine contact tank 84 Cum capacity (01 Nos) and 12 Cu m (01 Nos) |
| 9 | All as per item No.06 here in before but treated water contact tank 84 Cum capacity (01 Nos) and 12 Cu m (01 Nos) |
| 10 | Taking down the sewage treated water at collection point in sample bottle of 2 ltrs from STP 250 KLD capacity and Sending the sample to authorized Government certified testing plant. The report shall be incorporated with following points (a) PH (b) COD (c ) BOD (d) TDS (e ) Total Nitrogen (f) Total Phosphorus (g) Fecal Coliform (h) Odour |
| 11 | All as per Item No. 10 above 50 KLD |
| 12 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for laying/taking out of cables, CI/GI/DI/HDPE pipe lines and getting out in sooft/loose soil all as specified and directed. |
| 13 | Returning, filling in trenches including spreading, levelling watering and well ramming in layers not exceeding 25 cms in soil all as specified and directed. |
| 14 | Removal of surplus excavated material and deposited where directed at a distance not more than 50 RM from strating point and not more than 1.5m level above ground level all as specified and as directed. |
| 15 | Taking down the unserviceable and broken bricks from the cable network system. Supply and fix DWC pipe of size 50mm dia for protection of LT cables all as specified and directed Make : Rex/ Tirupati |
| 16 | All as per Item No. 14 above but of size 30mm dia |
| 17 | Supply & Lay underground XLPE insulated armoured LT UG electric cable with heavy duty aluminium conductor 1100V grade in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of size 25 sqmm 3.5 core complete all as specified and directed by Engr-in Charge . |
| 18 | All as per item No 15 above but size 50 sqmm 3.5 core |
| 19 | Supply , install, testing and commissioning LT motor control panel for PGOE STP made out of 2mm thick CRCA sheet Indoor Cubicle type floor mounting free standing finished with epoxy powder coated siemens grey texture finish of suitable size to accommodate and including the following accessories. (a) 200 amps rated aluminium busbar mounted on suitable SMC - 04 Nos(b) 100 amps 4pole 25 KA on load change over switch -01 (c) 100 amps 4 pole 25 KA MCCB - 01 No for incoming, (d) 5 HP star delta starter with 32 amps 3 pole MCB - 06 No for outgoing, (e) 3 HP DOL Starter with 32 amps 3 pole MCB - 04 No for outgoing,(f) Timer switch with MCB 16amps 2 pole for street lights-01(g) MCB SPN 40A for duty rooms - 02 Nos (f) Digital MFM meter with suitable CTS & Indicator lamp - 01 Set, (g) Ammeter with suitable CTS for all outgoing starters. Including pcc complete all as specified and directed by Engr-in Charge . |
| 20 | Supply , install, testing and commissioning LT motor control panel for GOLF STP made out of 2mm thick CRCA sheet Indoor Cubicle type floor mounting free standing finished with epoxy powder coated siemens grey texture finish of suitable size to accommodate and including the following accessories. (a) 300 amps rated aluminium busbar mounted on suitable SMC - 04 Nos(b) 160 amps 4pole 25 KA on load change over switch -01 (c) 160 amps 4 pole 25 KA MCCB - 01 No for incoming, (d) 10 HP Star & Delta Starter with 63 Amps 3 pole MCB - 04 Nos for outgoing, (e) 15 HP Star & Delta Starter with 63 Amps 3 pole MCB - 02 Nos for outgoing(f) 5 HP star delta starter with 32 amps 3 pole MCB - 02 No for outgoing,(g) 1 HP DOL Starter with 32 amps 3 pole MCB - 04 No for outgoing, (h) Timer switch with MCB 16amps 2 pole for street lights-01(j) MCB SPN 40A for duty rooms - 02 Nos (k) Digital MFM meter with suitable CTS & Indicator lamp - 01 Set, (l) Ammeter with suitable CTS for all outgoing starters. Including pcc complete all as specified and directed by Engr-in Charge . |
| 21 | Earthing complete with copper plate electrode of size 60cm x 60cm x 3.15 mm thick burried directly in ground( earth pit not less than 2.25 m deep below the normal groungnd level) with top edgee of the plate not less than 1.5m below normal GL connected to copper strip of size 20 x 3 mm by means of bolts, nuts, check nuts washers of GI or steel all as shown in electrical plate No-5 of SSR Part I connected to machanery/equipments installed power house/sub station all as specified including testing on completion.Note No-1 the unit rate shall also include for excavation earth work in any type of soil PCC (1:3:6) type C1 pit RCC 1:2:4 type B-1 cover reinforced with 8 mm dia CTD bars @ 150mm C/C both ways funnel with 15mm bore GI watering pipe 20mm dia bore GI protection pipe wire mesh and copper lugs complete in addition to item No 1(a) to (e) of preamble ( Notes) Under sub heading earthing specified on SI page NO-389 of SSR Part-II 2004. |
| 22 | Taking down the unserviceable GI strip, supply and fix copper strip 20 x3 mm all as specified and directed |
| 23 | S/F in repairs street light Junction box PVC weather proof suitable for accommodating and including heavy duty PVC connector block of 30 amps capacity three phase with one number single pole MCB 06 Amps complete including fixing to pole with suitable brackets, bolts/nuts for connecting cable and testing complete |
| 24 | S&F for 45 W new generation energy saving environmental friendly long life versalile pressure die cast aluminium IP-66 street light with high power LED as light source complete all as specified and as directed by the Engineer-in-Charge Make Havells (Cat No. ENDURASUNDOWNNXTSL45WLEDCWPASYBOPC) or equivalent for Havells /Philips /Crompton |
| 25 | S&F for new generation energy garden light 8 W saving environmental friendly long life aesthetically desiged aluminium landscape luminaire for diffused lighting with high power LED as light source complete all as specified and as directed by the Engineer-in-Charge. Make Havells cat No BAMBOOBL8WLED830SSYMTOPCM(1.0m) OR equivalent for CG/Philips /Bajaj |
| 26 | Material and Labour for PCC (1:3:6) type C1 (Using 20mm graded aggregate) to making good the disturbed hard standing area/road and match with the existing surroundings complete all as specified and as directed. |
| 27 | Supply, fix, test and commissioning LED Post top lantern luminairs outdoor type 45 Watts new generation energy saving & environmental friendly long life versatile pressure die-cast aluminium IP66 roadway luminaire with high power LEDs as light source and electronic driver suitable for operation on AC single phase 220-240 Volts, 50 HZ supply, including provision of two single core 1.5 sqmm copper conductor PVC insulated, 1100 Volts, cable not less than 8 meter length etc, connectiing from junction boxes to poles complete all as directed by Engr-in-Charge. Make:Havells (Cat No. RUBYGENXPT45WLED757PSYMTOPC) or equivalent to Bajaj, Philips |
| 28 | Preparation of old painted surface and cleaning the surface throughly and applying two coats of synthetic metalic grey enamel paints with spray gun and writing the SM/MES No complete all as specified and directed, for electric driven centrifgual pump and motor set of capacities upto 15 HP of any make and including suction and delivery pipes all as specified and as directed. |
| 29 | Taking down the unservicible Butterfly valve's of various size supply and fix new cast iron butterfly valve as per BS-5155 standard wafer and lug type can be easliy fixed between two flanges with studs,bolts bolts,nuts,washers etc all as specified and as directed for the following sizes:-All as per Item No. 27 above 100mm dia |
| 30 | All as per Item No. 27 above 80mm dia |
| 31 | All as per Item No. 27 above 65mm dia |
| 32 | All as per Item No. 27 above 50mm dia |
| 33 | Taking down the unservicible CI Non Return valve supply and fix new size of 100 mm in repairs conforming to IS-5312 Part - I ,PN 1.6 ,having flanged end joints suitable size of 100 mm dia with brass seating including jointing materials such as 3mm rubber gasket 01 No, 10mm dia nut & bolts and washers complete all as directed. |
| 34 | Taking down the unservicible Gun metal globe / gate valve's of various size supply and fix new Gun metal globe / gate valve conforming to IS 778-1984 with iron wheel head, screwed both ends for GI pipe including all fittings / fixtures like nipple, union etc complete for following sizes all as specified and as directed by the Engineer-in-Charge.All as per Item No. 29 above 50mm |
| 35 | All as per Item No. 29 above 40mm |
| 36 | All as per Item No. 29 above 25mm |
| 37 | All as per Item No. 29 above 20mm |
| 38 | Taking down the unservicible Foot valve cast iron body of various size supply and fix new Foot valve cast iron body with fianged and leather diaphram including replacement of bolts, nuts gaskets etc all as directed for following sizes :- All as per Item No. 30 above 100mm dia |
| 39 | All as per Item No. 30 above 80mm dia |
| 40 | All as per Item No. 30 above 50mm dia |
| 41 | Dis connecting inlet&outlet pipe and electrical connection,taking out complete elecric driven centrifugal/monoblock pump set of any make of capacity up to 15 HP ,3phase,415volts,50Hz with suction and delivery lins of any size,shifting to civil workshop for carrying out repair/overhauling including replacement of wornout spares and briging back after repair,refixing testing commissioning etc., complete all as specified and as directed. |
| 42 | Dismantling of motor of capacity upto 3.0 HP, cutting and taking out burnt / unserviceable winding coils, cleaning of slots and rewinding with correct size / gauge super enamelled insulated copper wire including providing proper insulation, varnishing, drying, reassembling etc., complete. |
| 43 | Supply only following spares for upto 3.0 HP capacity electric driven pump set:-(a) Ball bearings (drive /non drive ) |
| 44 | (b) Cooling fan blade |
| 45 | (c) Terminal Box. |
| 46 | (d) Terminal connectors 3 phase. |
| 47 | (e) Electro dynamically balanced bronze impellor |
| 48 | (f) Shaft (mild steel) |
| 49 | (g) Gun metal bush |
| 50 | (h) Gland cup with bolts and nuts. |
| 51 | (i) Water seal |
| 52 | (j) Flange drilled suitable size with bolts, nuts and rubber gasket. |
| 53 | (k) Air lock nozzle brass |
| 54 | (l) Shaft coupling |
| 55 | (m) Rotor |
| 56 | Dismantling of motor of capacity 5.0/7.5 HP, cutting and taking out burnt / unserviceable winding coils, cleaning of slots and rewinding with correct size / gauge super enamelled insulated copper wire including providing proper insulation, varnishing, drying, reassembling etc., complete. |
| 57 | Supply only following spares for 5.0/ 7.5 HP capacity electric driven pump set:-(a) Ball bearings (drive /non drive ) |
| 58 | (b) Cooling fan blade |
| 59 | (c) Terminal Box. |
| 60 | (d) Terminal connectors 3 phase. |
| 61 | (e) Electro dynamically balanced bronze impellor |
| 62 | (f) Shaft (mild steel) |
| 63 | (g) Gun metal bush |
| 64 | (h) Gland cup/sleeve with bolts and nuts. |
| 65 | (i) Water seal |
| 66 | (j) Flange drilled suitable size with bolts, nuts and rubber gasket. |
| 67 | (k) Air lock nozzle brass |
| 68 | (l) Shaft coupling |
| 69 | (m) Rotor |
| 70 | Dismantling of motor of capacity 10.0 HP, cutting and taking out burnt / unserviceable winding coils, cleaning of slots and rewinding with correct size / gauge super enamelled insulated copper wire including providing proper insulation, varnishing, drying, reassembling etc., complete |
| 71 | Supply only following spares for 10 HP capacity electric driven pump set:- (a) Ball bearings (drive /non drive ) |
| 72 | (b) Cooling fan blade |
| 73 | (c) Terminal Box. |
| 74 | (d) Terminal connectors 3 phase. |
| 75 | (e) Electro dynamically balanced bronze impellor |
| 76 | (f) Shaft( mild steel) |
| 77 | (g) Gland sleeve |
| 78 | (h) Water seal |
| 79 | (i) Air lock nozzle brass |
| 80 | (j) Shaft coupling |
| 81 | Dismantling of motor of capacity 15.0 HP, cutting and taking out burnt / unserviceable winding coils, cleaning of slots and rewinding with correct size / gauge super enamelled insulated copper wire including providing proper insulation, varnishing, drying, reassembling etc., complete |
| 82 | Supply only following spares for 15 HP capacity electric driven pump set:-(a) Ball bearings (drive /non drive ) |
| 83 | (b) Cooling fan blade |
| 84 | (c) Terminal Box. |
| 85 | (d) Terminal connectors 3 phase. |
| 86 | (e) Electro dynamically balanced bronze impellor |
| 87 | (f) Shaft( mild steel) |
| 88 | (g) Gland sleeve |
| 89 | (h) Water seal |
| 90 | (i) Air lock nozzle brass |
| 91 | (j) Shaft coupling |
| 92 | Taking up unserviceable centrifugal non clog submerciable sewage pump set 5.0 HP from sewage sump by bail out the water, disconnectin ,declamping , transport to authorised work shop and re-installation in the sump,testing complete including replacement of Gasket,cable protector kit,terminal block with terminal plate,'O' rings,seal monitors,safety rings,cable end cap,Painting as required and service charges complete all as directed. (Make:- KSB ) .Note: Replacement of Winding,insulating oil, bearings,Seal, Sensor,Shaft etc., shall be measured and paid separately under relevant items of this schedule.. |
| 93 | Supply only the following spares of centrifugal non clog submerciable sewage pump set 5.0 HP capacity (a) Winding with new copper wire of appropriate size including removing old burnt copper wire |
| 94 | (b) Replacement of bearing (Top,bottom & RR) |
| 95 | (c) Replacement of mechanical seal lower and upper |
| 96 | (d) Temperature Sensor |
| 97 | (e) Moisture sensor |
| 98 | (f) Rotor Shaft |
| 99 | (g) Repalcement Insulating oil as per manufacturer recommended grade |
| 100 | Repairing centrifugal non clog sewage pump set by replacing of the relevant spares taken including packing, refixing and testing of motor of capacity 1.0/2.0 HP complete etc., all as specified and directed.Note: Spare parts/ accessories like shaft, rubber flap, bearings, gland packing, rubber packing and sleeve etc., shall be measured and paid separately under relevant items of this schedule. |
| 101 | Supply only the following spares of 1.0/2.0 HP capacity centrifugal non clog sewage pump set (a) Winding with new copper wire of appropriate size including removing old burnt copper wire |
| 102 | (b) Shaft |
| 103 | (c) Rubber flap |
| 104 | (d) Ball bearing |
| 105 | (e) Gland packing |
| 106 | (f) Rubber packing |
| 107 | (g) Sleeve |
| 108 | (h) Electro dynamically balanced bronze impellor |
| 109 | Taking down the offload / unserviceable Sludge Feed Pump monoblock type from the 250 KLD sewage treatment plant. Supply and fix the Sewage Transfer pump of following parameters Set of two ( Make : Kirloskar or equivalent ) Technical Spec(a) 2 m3/hr @ 60 Capcity (b) 1500 RPM (c) 01 HP Including Suction valve and discharge valve |
| 110 | Taking out unserviceable following DI pipeline from trenches including supply and laying in trenches Ductile Iron spigot and socket pipes as per IS:8329/2000 Class K7 including EPDM rubber gasket suitable for and including push on rubber gasket joint with inside cement mortar lining and outside Zinc bitumen coating complete all as specified and directed for following sizes:- Make :- Electrosteel/Tata /Jindal (a) 100 mm bore DI tubing |
| 111 | (b) 150 mm bore DI tubing |
| 112 | (b) 200 mm bore DI tubing |
| 113 | M & L DI/CI fittings upto 150mm dia, ISI marked, such as bends (any type, radius any angle) tapers any type (straight or bend), increasing, decreasing or double socket etc) Tee pieces single branch, double branch,cross(all sockets and socket and spigot) collars, caps and plugs tail piece confirming to IS 1538/1993 complete all as specified and directed. Please Enable Macros to View BoQ information |