| 1 | Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 75 to 90 Watt. Confirming to IP 66 and above Protection complete in all respect. E/I. UPPWD-2018 PS No. 1423 Catt-AAA Make:-Bajaj/Philips/Crompton/Surya/LT Light/Havells |
| 2 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. DSR-2018 12.34 |
| 3 | Supply & fixing of 6 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness with Single arm bracket 1 Mtr length in 1:2:4 RCC foundation bolt including the cost of foundation, excavation & back filling and Required T&Pcomplete in all respect as per direction of E/I. UPPWD-2018, PS-647 Make:- Bajaj/ GE/Philips/Valmont/Transrail |
| 4 | Supply and burying of 600 mm x 600 mm x 6.0 mm GI plate, vertically for eathing with its top at least 3 meters below ground level complete with 20 mm dia. GI Pipe and funnel for watering and one earthing lead of one no. 8 to 10 SWG GI wire in 12 mm. dia. GI Pipe up to switch board (from appron to switch board the cost of GI pipe and GI wire will be extra) 30 cm. square GI Frame with hinged cover, masonry housing, alternate layers of charcoal/coke and salt at least 150 mm. thick alround etc. as per direction of Engineer-in-charge complete in all respects (This will apply for earthing of poles also). UPPWD-2018, PS-702 |
| 5 | S/L of 25x3 mm. G.I. Strip from earth electrode directly in the ground as required complete in all respects (P.S. No. 716) |
| 6 | S/L of Al. armoured cable PVC insulated Ar. served & sheathed cable 1100 V grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I.Complete in all respects . The armouring of the cable shall be properly connected with the earth conductor by clamps etc. (PS No. 501) UPSR -2018 Make : Gloster/Universal/ Polycab/ Havells/ Diacab/Grandley/KEI-a)- 16 sq. mm 4 core |
| 7 | c) 50 Sq.mm. 3.5 Core |
| 8 | S/F of Plain or Pin type copper tin plated cable socket (Lug) to the cable lead, insulating with tape and making connector etc. Complete in all respects as per Direction of E/I (PS No. 504) UPSR-2018a)-16 sq. mm |
| 9 | b) 50 Sqmm |
| 10 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. DSR-18 (Elect.) Item No-14.16 Make-creator poly extrusion/duraline/rex/times/ narander plast/pioneer-a)-63 mm dia (OD-63 mm & ID-51 mm nominal) DSR-18 (Elect.) Item No-14.16.1 |
| 11 | Demolishing R.C.C. Work Manually by mechnical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of E/I. (AOR) |
| 12 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. 15.2.1 Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) 15.2.1 DSR(Civil)-2018 P-258 |
| 13 | Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate, moorum screening, red bajri and labour required.bituminous portion (DSR-2018 Item No-16.13.1 ,P-272) |
| 14 | Supply and fixing Following automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN,UPPWD-2018, PS-8071. 40 AMP SPN Please Enable Macros to View BoQ information |