| 1 | (Supply Part) - 2 Nos. 400 KVA 11/0.4KV Sub-Station |
| 2 | Distribution Transformer (Ordinary), 11/0.4 kV, 400 KVA |
| 3 | Steel Tubular Poles (10m, Working Load > 200 kgf/m²) |
| 4 | Muffs with concerete filling |
| 5 | X-Arm: [Channel Iron (100x50x6 mm), Length : 2800 mm X 2 Nos] for incommer line |
| 6 | MS Angle Iron (50X50x6 mm), Length: (2800 mm) x1 Nos for LA's |
| 7 | X-Arm: [Channel Iron (75x40x6 mm), Length : (2800mm) X 4 Nos] for supporting DO fuse unit & GO switch |
| 8 | Transformer Bed, Belting & Knee Bracing X-Arm: [Channel Iron (100x50x6 mm), Length : 2800 mm X 2 Nos] for Transformer Bed |
| 9 | X-Arm [Channel Iron (100x50x6 mm), Length : 460 mm x 2 Nos for supporting Main Channel of Transformer] |
| 10 | MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos |
| 11 | d MS Angle Iron (35X35x5 mm), Length : (460 ) x 2 Nos |
| 12 | MS Angle Iron (50X50x6 mm), Length : (950 mm) x 2 Nos for Bed Knee Bracing |
| 13 | Transformer LT Distribution Box and GO Switch fixing Assembly MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos |
| 14 | MS Angle Iron (50X50x6 mm), Length : (450 mm) x 1 Nos |
| 15 | GO Switch Handle Supporting: [Channel Iron (75x40x5 mm), Length : 460 mm |
| 16 | GO AB Switch Unit (11kV, 400A, 25 KA ) Tripple pole O/D type |
| 17 | D.O Fuse Unit |
| 18 | Surge Arrester, 9 kV Station Class (Porcelain Type) |
| 19 | Discs insulator sets (comprising 1 No. Disc: ^^(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps etc.) including dead clamp etc |
| 20 | Stay set complete |
| 21 | Stay Wire (7/3.15 mm) (6.0 kg Per Stay Set) |
| 22 | Pipe Earthing Set |
| 23 | LT Distribution Panel for Trasnformer Fitted with Bakelite sheet ,1000 Amp copper thimble ACB 1000 amp 3P 50kA -1 No., Make L&T,Schneider,Havells,ABB or equivalent, MCCB 400 Amp 50 kA 3P of L&T Schneider, ABB,Havalle or equivalent make -3 Nos |
| 24 | Half Clamp (M.S. Flat 50X6 mm) |
| 25 | Full Clamps (M.S. Flat 50X6 mm) |
| 26 | Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)] |
| 27 | Aluminium Thimble |
| 28 | Copper Thimble |
| 29 | Danger Plate |
| 30 | Barbed Wire |
| 31 | LT 3.5X500 mm² 1.1 kV XLPE Cable Unarmoured x 2 Nos. incommer |
| 32 | LT 3.5 X 400 mm² 1.1 kV XLPE Cable Unarmoured x 6 Nos. Outgoing |
| 33 | Energy Meter, HT 3-ɸ, 4 wire CT-PT operated Static Tri-Vector meter , PT ratio -/110V, CT ratio -5 Amp. |
| 34 | 11kV CT/PT combined unit 15 KV /110V 200/5 A |
| 35 | Red Oxide |
| 36 | Aluminium Paint |
| 37 | X-Arm: [Channel Iron (100x50x6 mm), Length : 2800 mm X 4 Nos] for CT-PT Unit |
| 38 | MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos for CT-PT Unit |
| 39 | MS Angle Iron (50X50x6 mm), Length : (450 mm) x 1 Nos for CT-PT Unit |
| 40 | Transportation Charges |
| 41 | (Supply Part) of 11 KV H.T. Line to proposed 2x400 KVA DTR |
| 42 | ACSR 6/1/4.72 (100 mm²) {Includes 3 conductor lengths for 3Φ and Additional 1% (Sag, Jumpering and wastage} |
| 43 | Steel Tubular Poles (13 m, Working Load > 227 kgf/m²) (with Ruling Span 90 m, 8 No. Run thro' and 3 No. Double Pole Dead End Structures) |
| 44 | Muffs with concerete filling (2000 mm) |
| 45 | Cross Arm: Horizontal [MS Channel Iron (100x50x6 mm), Length: 2340 mm i/c tolerance of 100 mm either side) x 2Nos. |
| 46 | Cross Arm: Horizontal [MS Channel Iron (100x50x6 mm), Length: 2600 mm ) x 1 Nos. |
| 47 | 11 kV Pin Insulators with GI pin (Porcelain, 12 kV, 10 KN): 6 No per structure |
| 48 | Cross Arm: Horizontal [MS Channel Iron (100x50x6 mm), Length: 2340 mm i/c tolerance of 100 mm either side) x 4 Nos. |
| 49 | Cross Arm: Horizontal [MS Channel Iron (100x50x6 mm), Length: 2600 mm ) x 2 Nos. |
| 50 | Discs insulator sets on Dead End structures (comprising 1 No. Disc: ^^(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps etc.) x (6 No. conductors) x (2 No. sides) |
| 51 | X- bracing set, MS Angle Iron: 50x50x6, Length: 2125 mm x 2 Nos. |
| 52 | Belt Set - MS Angle Iron: 50x50x6, Length (1800 x 2 Nos.) |
| 53 | Half Clamps |
| 54 | Full Clamps |
| 55 | Stay set complete in all respect (i/c Stay clamp / 4 No. for Dead structure and 2 No. for Run thro.) Double Pole Structures) |
| 56 | Stay Wire (7/3.15 mm) (10.0 kg Per Stay Set) |
| 57 | HT Earthing set complete |
| 58 | Single Continous Earth wire (GI, 8 SWG) {alongwith 2 wire lengths for avg. one road crossing @ 20 m and Additional 3% (Sag and wastage)} @ 0.102 kg/m |
| 59 | Cross Lacings (GI, 8 SWG) [ 2.2 m x 9 Nos @ 2 m spacing] {0.102 kg/m} |
| 60 | Eye Hook for earth wire |
| 61 | MS Angle Iron: 50x50x6, Length : 2800 mm for Gaurding |
| 62 | Danger Plate (250X200X1.6 mm) |
| 63 | Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)] |
| 64 | Barbered Wire |
| 65 | Red Oxide |
| 66 | Aluminium Paint |
| 67 | Transportation Charges |
| 68 | (Supply Part) CT PT metering Unit |
| 69 | 11 kV Outgoing Feeder: Control and Relay (CR) Panel with indoor VCB (12 kV, 1250 A, 25KA) including CT 400-200/5 |
| 70 | 11 kV Cable (11 kV, 185 mm², XLPE, Three Core, Armoured) {Busbar VCB to Isolator} {50m+ Spare- 50m} |
| 71 | 11 kV Cable Termination Kit (185 mm², Outdoor) |
| 72 | 11 kV Cable Termination Kit (185 mm², Indoor) |
| 73 | 11kV CT 400-200/1-1-1-1 A for Incomer -I &II and Buc Coupler |
| 74 | Transportation charges |
| 75 | (Erection Part ) of 2 Nos. 400KVA 11/0.4KV Sub-Station |
| 76 | Erection of 400 Kva,11/0.4KV Transformer, LT Box, MCCB Switch, Cable , service Cableand Energy Meter completed in all respect. |
| 77 | Un-loading and placing of 4oo KVA DTR on DTR Bed with Hydra complete in all respect |
| 78 | (Erection Part) ) of 11 KV H.T. Line |
| 79 | Erection of S/T pole 13 mtr long,(Double pole structure) with RCC muff Including Concreating digging of pit of size 1.10x0.75x1.50, drilling of holes in poles, X-bracing set, X-arms, Fixing of insulators, X-arms, X- bracing set, fixing of barbed wire, Danger plate, filling of pit & ramming and painting of pole complete in all respects(C.C. 1:3:6 for muffing will be provided by the contractor). |
| 80 | Erection of HT earthing set comprising digging of pit, fixing of GI wire to the earth system,and filling of pit complete in all respects. |
| 81 | Erection of stay set HT line, comprising digging of pit, fixing of stay rod, filling of pit, Nozzeling and tightining complete in all respects. |
| 82 | Sagging of conductor 1 KM single GI wire, AAAC cond., comprising laying of Conductor, stringing & sagging, binding with insulator complete in all respects. |
| 83 | Erection of H T line with AAAC/ACSR Conductor 6/1/4.72 mm2 (100mm2) such as stringing, tensioning and sagging,jointing and fastening . |
| 84 | Erection Part) of CT/PT Metering Unit |
| 85 | Erection of 11 kV Outgoing Feeder: Control and Relay (CR) Panel with indoor VCB (12 kV, 1250 A, 25KA) including CT 400-200/5, {Busbar VCB to Isolator} {50m+ Spare- 50m}, 11 kV Cable Termination Kit (185 mm², Outdoor & Indoor) & |
| 86 | Erection of 11 kV Cable (11 kV, 185 mm², XLPE, Three Core, Armoured) Coupler complete in all |
| 87 | Erection /Connection of 11 kV Cable Termination Kit (185 mm², Outdoor & Indoor) Coupler complete in all |
| 88 | erection of 11kV CT 400-200/1-1-1-1 A for Incomer -I &II and Buc Coupler complete in all respect |
| 89 | CIVIL PART (DTR foundation & chain link fencing of 2 No. 11/0.4 kV, 400 KVA distribution transformer |
| 90 | C/O RCC Foundation for 400 KVA Transformer:- Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. ordernary rock. |
| 91 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:3:6 (1 Cement : 3 coarse sand): 6 graded stone aggregate 40 mm nominal size) |
| 92 | Centering and shuttering including strutting, propping etc. and removal of form for:-Foundations, footings, bases of columns, etc. for mass concrete. |
| 93 | Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 94 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level 1:1.5:3 (1 cement : 1.5 coarse sand): 3 graded stone aggregate 20 mm nominal size) |
| 95 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 96 | Chain link fencing (For 400KVA Transformer):- Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 97 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand) : 8 graded stone aggregate 40 mm nominal size) |
| 98 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:1½:3 (1 Cement: 1½ coarse sand) : 3 graded stone aggregate 20 mm nominal size) |
| 99 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 100 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia 4 mm |
| 101 | Providing and fixing ISI marked M.S. pressed butt hinges bright finished with necessary screws etc. complete :100x58x1.90 mm |
| 102 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete :250x16 mm Please Enable Macros to View BoQ information |