| 1 | SH :- I DG SetSupply, installation, Testing & Commissioning of 'Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo-Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings:(A) Diesel Engine:Turbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528. The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications.(B) Engine mounted Instrument Panel fitted with and having digital displayfor following:(i) Start-stop switch with key(ii) Water temperature indication |
| 2 | (iii) Lubrication oil pressure indication(iv) Lubrication oil temperature indication(v) Battery charging indication and Voltage indication(vi) RPM indication(vii) Over speed indication(viii) Low lubrication Oil trip indication(ix) Engine Running Hours indication(x) Fuel Level(C) Alternator:Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation.(D) Base Frame & Foundation:Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.(E) FUEL TANK:Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, |
| 3 | level indications & accessories as required as per specifications.(F) Exhaust System:Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor.(G) Starting System:12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set. (H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications.(I) AMF Panel:Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminum) and control (copper ) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software, the panel shall be of DG Set OEM make etc. as per approved by Engineering in charge and including the following:1. Suitable numbers and appropriate capacity 4 pole motorized electrically operated draw out with cradle type 3 position ACB/ MCCB with electronic release for O/C & E/F and shunt trip.2. Auto/Manual/Test/Off selector switch3. Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay).Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering 5. Energy analyser unit to indicate current, Voltage( L-N & L-L), kW, kVA (Phase & Total), Frequency, KWH, PF.6. LED Indicating lamps for load on mains and load on set.7. Fuse/ MCB for instruments.8. Battery charger, complete with transformer/ rectifier, D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.9. Main supply failure monitor.10. Supply failure timer.11. Restoration timer12. Control unit with three impulse automatic engine start/stop and failure to start lockout.13. Impulse counter with locking and reset facility. |
| 4 | 14. ON/OFF/Control circuit switch with indicator15. Audio/Video annunciation for(i) High water temperature(ii) Low lubricating oil pressure(iii) Engine over speed(iv) Engine fails to start(v) Full load/maximum load warning16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories17. Maintenance notification based on Engine Run Hour & due date.18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel, interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring. a)125KVA |
| 5 | SH :- II EI WorkProviding and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required |
| 6 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
| 7 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 meter below ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50 mm) |
| 8 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 9 | Supplying, laying and fixing of following sizes XLPE insulated PVC sheathed aluminum conductor armoured cable of 1.1 KV grade on Wall/surface etc complete as required.a) 3.5X 35 Sq.mm |
| 10 | b) 3.5 X 50 Sq.mm |
| 11 | c) 3.5X 95 Sq.mm |
| 12 | Supplying and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required.a) 3.5X 35 Sq.mm (32mm) |
| 13 | b) 3.5 X 50 Sq.mm (35mm) |
| 14 | c) 3.5X 95 Sq.mm (45mm) |
| 15 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.a) 3.5X 35 Sq.mm |
| 16 | b) 3.5 X 50 Sq.mm |
| 17 | c) 3.5X 95 Sq.mm |
| 18 | Supplying and fixing of cubical type indoor panel board pump starter panel suitable for 3 Phase, 4 wire, 415 volt, 50 Hz, dust and vermin proof made out of 2 mm thick CRCA sheet duly powder coated with siemens gray paint after prepaint treatment fully compartmentalized and with suitable capacity aluminium bus bar of with colour coated PVC sleeve, cable alley i/c. Manual ON-OFF Bypass push button assembly brought out at rain protected door slot so as to operate pumps manually without opening of doors of the panel , earthing studs & detachable gland plates i/c providing and fixing following switchgears and accessories therein complete with connection, interconnection earthing stud and neutral bus bar suitable base frame, concrete foundation i/c. testing and commissioning etc. complete as required. (Depth of panel minimum 300mm) (I) MAIN INCOMER 1 SET.125A, FP 36KA MCCB THERMAL MAGNETIC BASEDRELEASE WITH EXTENDED ROTARY HANDLE 1 NOS. (II) METERING(a)- DIGITAL MULTIFUNCTION METER 1 NOS. (b)-R, Y, B PHASE INDICATION LAMP 3 NOS. (c)- CT150/5 15 VA 1.0 CL 3 NOS. (d)- 06A SP MCB 3 NOS. (III) BUSBARS(a)-150A FP BUSBAR ALUMINUM 1 SET. (IV) OUTGOING (4SET)10 HP DOL STARTER 1nos.(a)-22A TP CONTACTOR 1 NOS(b)-9-15A OVERLOAD RELAY 1 NOS. (c)- ON,OFF INDICATION LAMP 2 NOS.(d)- PUSH BUTTON START,STOP 2 NOS. (e)- 32A DP MCB 10KA 1 NOS. (f)- AUX BLOCK 1NO+1NC 1 NOS. (g)-SINGLE PHASING PREVENTOR 1 NOS. (V) OUTGOING (1 SET)(a)63A, FP 25KA MCCB THERMAL MAGNETIC BASED RELEASE WITH EXTENDED ROTARY HANDLE 1 NOS. (b)ON INDICATION LAMP 1 NOS. |
| 19 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 20 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm |
| 21 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 22 | Supplying and fixing of 3 mm thickness Electric insulation rubber mat for High Voltage Resistance with ISI 15652-2006 for switch room etc as required. |
| 23 | Dismantling and Credit/buy back to contractor of old cable/termination/lugs/scrap material/other electrical items which is pertain to this work. |
| 24 | Dismantling and Credit/buy back to contractor of old 125 KVA DG set with AMF Panel. |
| 25 | Dismantling and Credit/buy back to contractor of PUMP ROOM Electrical Panel Please Enable Macros to View BoQ information |