| 1 | Construction of Panel & meter room, Rejuvenation of Sump well, Screen chamber and inlet chamber, Repair of existing LT Panel room, boundary wall and site development work. |
| 2 | (1001)Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. |
| 3 | (1011) Concrete with 40 mm gauge brick ballast, local sand and cement in proportion in 8:4:1 in foundation including supply of all material,labour T & P etc. required for proper completion of work. |
| 4 | (1029) Ist. Class brick work in 1:6 cementand local sand mortar in foundation and plinth including supply of all material, labour T & P etc. required for proper completion of work. |
| 5 | (1054) 20 mm thick D.P.C.with cement and approved coarse sand 1:2 including 5% water proofing material or in proportion as specied by the manufactures including supply of all material, labour T & P etc. required for proper completion of work. |
| 6 | Ist. Class brick work in 1:6 cement and local sand mortar in super structure including supply of all material,labour T & P etc.required for proper completion of work as per direction of Engineer incharge. |
| 7 | Ist. Class brick work in 1:4 cement and local mortar in super structure including supply of all material,labour T & P etc.required for proper completion of work as per direction of Engineer incharge. |
| 8 | Ist. Class brick work for half brick work in 1:4 cement and local mortar in super structure including supply of all material,labour T & P etc.required for proper completion of work as per direction of Engineer incharge. |
| 9 | (1149) Supply and fixing of M.S. angle iron chaukhats of 50 mm x50 mmx6 mm with M.S. sheet door shutter including simple moulding straightg work as in chaukhats and also supply of all material,labour T & P etc.required for proper completion of work as per direction of Engineer incharge. |
| 10 | Fixing of hold fast of doors and windows chaukhats already moulded on chaukhats in P.C.C. 1:2:4 etc.required in all respect to complete the work. |
| 11 | (1025) R.C.C. work with cement,coarse sand and 20 mm gauge approved stone ballast in proportion of 1:1.50:3 in sun shed and lintel on doors and windows excluding supply of reinforcement and its bending but including its fixing and binding the same with 0.50 mm thick binding wire and the cost of binding wire and including necessary centering and shuttering supply of all material,labour T&P etc. required for proper completion of work as per direction of Engineer incharge. |
| 12 | R.C.C. Work cement,coarse sand and 20 mm gauge approved stone ballast in proper ratio of 1:1.5:3 excluding supply of reinforcement and it bending but including its fixing and binding the same with 0.5 mm thick binding wire (to be supply by the contractor) centering nd shuttering supply of all materials, Iabour,T&P etc required for proper compltion of work.(SOR:1021) |
| 13 | (1151) M. S. or iron work in plain work such as R.C.C.or R.B. work (when not included in over all rates) brought to required shape as necessary including bending for proper completion of the work including supply of steel and its wastage. |
| 14 | (1190) 12 mm thick plaster with cement and local sand mortar I:6 over brick work minimum thickness not to be less than 10 mm including supply of all material,labour T&P etc. required for proper completion of work. |
| 15 | (1188) 12 mm thick plaster with cement and local sand mortar 1:6 over brick work minimum thickness not to be less than 10 mm including supply of all material,labour T&P etc. required for proper completion of work. |
| 16 | (1190 & 1200) 12 mm thick plaster with cement and local sand mortar 1:4 over brick work minimum thickness not to be less than 10 mm including supply of all material,labour T&P etc. required for proper completion of work. (On Raf face of 1 brick wall) |
| 17 | 6 mm thick plaster in 1:4 ratio with cement and local sand mortar over ceiling including supply of all material,labour T&P etc. required for proper completion of work as per direction of Engineer incharge. |
| 18 | (1202) 25 mm thick 1:2:4 plain cement concrete floor with cement coarse sand and 20 mm gauge stone ballast laid in pannels finished with 3 mm floating coat of neat cement including 75 mm thick base concrete consisting of cement local sand and Ist. Class brick ballast 40 mm gauge in proportion of 1:4:8 including supply of all material,labour T & P etc. required for proper completion of work. |
| 19 | Supply and fix 22*3mm glass strips in position including supply of all material,labour T&P etc. required for proper completion of work. |
| 20 | (1232 & 1233) Painting or varnishing new work or new wood work in small areas with one priming coat and two coat of approved quality paint or varnish including supply of all material,labour T & P etc. required for proper completion of work. |
| 21 | (1261) ONE PRIMING COAT & ONE COAT OF DRY DISTEMPER ON NEW WORK. including supply of all material,labour T&P etc. required for proper completion of work. |
| 22 | (1262) SAME AS ITEM 1261 BUT FOR EACH COAT OF DISTEMPER AFTER FIRST COAT. |
| 23 | White washing with white cement in three coats including supply of all materials, labor, T&P, etc required proper completion of work.(SOR:1253) |
| 24 | Finishing walls with water proof cement paint of approved make and quality on new work with two coats to give an even shade including supply of all materia, Labour T&P etc. required for proper completion of work. |
| 25 | Finishing walls with water proof cement paint (Apex) of approved make and quality on new work with two coats to give an even shade including supply of all material,labour T&P etc. required for proper completion of work. |
| 26 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete(DSR-13.80) |
| 27 | (1201) 20 mm thick plaster in dado or skirting in 1:2 cement and sand mortar including supply of all material ,labour T & P etc. required for proper completion of work. |
| 28 | (1004) Sand filling in plinth in including supply of all material,labour T & P etc. required for proper completion of work. |
| 29 | (1286)Supply & Fix 100 mm dia P.V.C. down pipes complete with rose & bend and gratings with M.S. clamps 25 X 3 mm fixed on walls & supply of 150 mm long, 6 mm dia nails complete. |
| 30 | Provision for internal electrification work including supply of all material, labour,T&P etc. complete as per direction of Engineer incharge. |
| 31 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.10.6.1 80x1.25 mm M.S. laths with 1.25 mm thick top cove 10.6.1 80x1.25 mm M.S. laths with 1.25 mm thick top coveRolling shutter made of 80x1.25 mm machine rolled laths |
| 32 | (1167)Supply and lay 4 cm thick insulation layer of sand and clay over R.C.C. roof including supply of all material,labour T & P etc. required for proper completion of work. |
| 33 | Mud Faska on R. B. or R.C.C. Roof with 100 mm thick clay layer on roof and laying of tiles and jointing them with cement and sand mortar including supply of all material,labour T&P etc. complete. |
| 34 | (1015) Concrete with stone ballast,local sand and cement in proportion in 4:2:1 in foundation including supply of all material,labour T & P etc. required for proper completion of work. |
| 35 | Cleaning of Sump well campus including cutting and removal of bushes, shrubs, wild vegetation, grass, and unwanted growth, leveling of uneven ground, dressing of earth and neat appearance, removal and disposal of rubbish, debris as directed by the Engineer-in-Charge. |
| 36 | Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 metre openable length, having 50 nos rounds per 6 metre length, with angle iron ‘Y’ shaped placed 3.00 m apart and with 9 horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain horizontal, including necessary bolts or G.I. barbed wire tied to angle iron, all complete as per direction of Engineer-in- charge. |
| 37 | Supply & Laying of 80 mm thick CC pre rubber moulded interlocking paver tiles over 1:6:12 base concrete including earth work in excavation in proper slope & camber including all labour, T&P etc. required for proper completion of work as per directed by the Engineer-in-Charge. |
| 38 | Supply and filling of earth in campus including supply of necessary quantity of earth from a distance not exceeding 8km from the site of work and including watering, ramming, dressing etc. |
| 39 | Construction of U- Type Drain of size 300mm x 300mm as per unit estimate including supply of all materia, Labour T&P etc. required for proper completion of work. |
| 40 | Bailing out or Pumping out water for diversion by dewatering pumps including all consumables, diesel, oil, petrol, lubricants etc. and disposal of water all complete as per direction of Engineer-in-Charge. |
| 41 | Cleaning and desilting of Sump well, including removal of rubbish mixed with earth etc. and disposal of same, all as per the direction of Engineer-in-charge. |
| 42 | 6.00-7.50 M BGL (In Screen Chamber & Inlet chamber) |
| 43 | 7.50-9.0 M BGL (In Sump Well) |
| 44 | Repairs to plaster of thickness 12 mm to 20 mm in patches of area 2.5 sq.meters and under, including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete including disposal of rubbish to the dumping ground, all complete as per direction of Engineer-in-Charge. (In Sumpwell, Screen chamber, Inlet chamber, LT pemel room). |
| 45 | With cement mortar 1:4 (1 cement : 4 fine sand) |
| 46 | With cement mortar 1:4 (1cement: 4 coarse sand) |
| 47 | (1150) Supply & fixing of MS jaal over half portion of Sump well including fixing of girder, cutting, hoisting fixing in position and applying a primary coat of red lead paints as per direction of Engineer-in-Charge. |
| 48 | Repairing, Supply & fixing of Hand Railing of walk way of Sump well including supply of all material,labour T&P etc. required for proper completion of work as per direction of Engineer-in- Charge. (SOR 1149) |
| 49 | In Screen Chamber & Inlet chamber |
| 50 | In Sump Well |
| 51 | M. S. or iron work in plain work such as R.C.C.or R.B. work (when not included in over all rates) brought to required shape as necessary including bending for proper completion of the work including supply of steel and its wastage. |
| 52 | 6.00-7.50 M BGL (In Screen Chamber) |
| 53 | 7.50-9.0 M BGL (In Sump Well) |
| 54 | R.C.C. work with cement,coarse sand and 20 mm gauge approved stone ballast in proportion of 1:1.50:3 in sun shed and lintel on doors and windows excluding supply of reinforcement and its bending but including its fixing and binding the same with 0.50 mm thick binding wire and the cost of binding wire and including necessary centering and shuttering supply of all material,labour T&P etc. required for proper completion of work. |
| 55 | 6.00-7.50 M BGL (In Screen Chamber) |
| 56 | 7.50-9.0 M BGL (In Sump Well) |
| 57 | Repair of Gate Valve of inlet chamber including supply of all material, labour T&P etc. required for proper completion of work. |
| 58 | Regrading terracing of mud phaska over roof of LT Panel covered with tiles or brick, in cement mortar by dismantling tiles or bricks, removing mud plaster, preparing the surface of mud phaska to proper slope, relaying mud plaster gobri leaping and tiles or bricks, grouted in cement mortar 1:3 (1 cement : 3 fine sand), including replacing unserviceable tiles or bricks with new ones and disposal of unserviceable material to the dumping ground (the cost of the new tiles or brick excluded), all complete as per direction of Engineer-in- Charge. |
| 59 | H.T.Panel( Comprising with 1 -I/C and 2 -O/G. |
| 60 | SITC of Indoor Type Floor mounted HT Panel with 11 KV, 630 Amps 3 phase, 50 Hz Vacuum Circuit Breaker (VCB) Panel Fabricated by System Integrator of VCB Manufacturer as per IEC 62271-1,100,200 Standard made from Powder painted pre-fabricated, CRCA sheet steel /High quality Aluminium-Zinc (Aluzinc) coated sheet steel. Fabrication shall be done through CNC turret press and CNC bending machine having a rupturing capacity of 500 MVA, 26.3 KA breaking capacity for 3 sec, Internal arc type tested for 26.3KA for 1 sec with AFLR clasification with suitable capacity of bus bar connected with the incoming and outgoing panels as per given details- |
| 61 | Supply installation testing and commissioning of Incoming Panel comprising of following: - VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCBoperationg mechanism should be of M2 duty for minimum 10000 mechanicaloperation. - Closing & tripping coil of VCB should be of continious rating to achive minimal failure. - Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2: 0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)- VT Ratio: 11KV/1.732/110V/1.732/110V/1.732, -Core 1: 0.5, 20VA should be floor mounted and to be connected from the back side of the panel.- Numerical relay (should be VCB manufacturer's own make) having protections of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input , programable 6 Digital Output and programable 4 nos. LED at HMI.- Ammeter with Selectorswitch and Volt meter with Selector switch- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,KVAR, PF, KWH, KVARH, KVAH, A,V etc.- Trip circuit supervision relay (feature of numerical relay)- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS healthy etc., Space heaters - Power Pack (230V AC- 110V DC) and 8/12 window Annunciator. (Rate as per rajasthan pwd electric BSR-2022 SOR7, item no 23.7.2) |
| 62 | Supply Installation Testing and Commissioning Outgoing Panel comprising of following: - VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCBoperationg mechanism should be of M2 duty for minimum 10000 mechanicaloperation. - Closing & tripping coil of VCB should be of continious rating to achive minimalfailure. - Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2: 0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)- Numerical relay (should be VCB manufacturer's own make) having protectionsof 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input ,programable 6 Digital Output and programable 4 nos. LED at HMI.- Ammeter with Selectorswitch and Volt meter with Selector switch- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,KVAR, PF, KWH, KVARH, KVAH, A,V etc.- Trip circuit supervision relay (feature of numerical relay)- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS healthy etc., Space heaters - Power Pack (230V AC- 110V DC) (Rate as per rajasthan pwd electric BSR-2022 SOR7, item no 23.7.3) |
| 63 | Providing & Laying XLPE insulated as per IS:7098/II/85 H.T.cable as per PWD specification for electrical Works for working voltage 11 K.V.(E) in existing RCC / Hume /Stoneware / PVC pipe/ open duct/cable trench, on existing cable trays or on surface etc. including making necessary connection, testing etc. |
| 64 | 3 core X 120sq.mm. armored HT Cable (From HT Panel to Transformers) Ref.13.1.2 (PRE BSR 2022) |
| 65 | SITC of 11 KV End Termination Kit Indoor type (3 core, 120sq.mm) Ref.13.12.2.3 (PRE BSR 2022) |
| 66 | 11 KV, 2.5 mm thick with proof voltage 22 KV / 3 min. and Break DownVoltage 45 KV Ref.8.10.2 (PRE BSR 2022) |
| 67 | Transformer: 160 KVA with Off -LTC (+5% to - 10% @ 2.5%) : Supply of star rated Copper wound distribution Transformer of 160 KVA rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & losses as defined as per IS 1180 part I 2014. including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C , ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint, including carrying of pre-commission Testing & Charging of Transformer complete in all respect. |
| 68 | Installation testing and commissioning of transformers @ 10% |
| 69 | L.T. Panel |
| 70 | SITC of 0.415 kV L.T. control panel for pumping plant-L.T. control panel suitable to operated on 415 ± 6 % volt , 3 Phase , 50 Hz, AC supply as per details given below-(A) 2 Nos incoming MCCB panels, each consisting of following items -(i) 4 pole MCCB ,250 A Rating ,35 kA- 1 No.(ii) C.Ts of suitable ratio- 1 No.(iii) Ammeter with selector switch - 1 No.(iv) Voltmeter with selector switch- 1 No. (v) Power factor meter(0.5 Lag&0.5Lead) - 1 No.(vi) Frequency meter-1 No.(vii) KWH meter - 1 No. (viii) 2 Pole over current relay & one pole earth fault relay - 1 No.(B)Bus bar chamber having 3 Nos. bus bars for phase and 1 No. bus bar for neutral of suitable size – 1 No. (C) 3 Nos. composite panels for pumping plants, each consisting of following items –(i) 4 pole MCCB 160 A current rating, 25 KA short circuit breaking capacity With Microprocessor based release with adjustable adjustable O/L & S/C setting with Inbuilt Instantaneous and Ground fault Protection -1 No.(ii)C.Ts. of suitable ratio- 1 No.(iii)Ammeter with selector switch - 1 No.(iv) Automatic start / stop device according to level in the sump- 1 No.(v)Indicating lamps(Auto/manual/low level/ reverse rotation) - 1 Set (D) 2 Nos. composite panels for pumping plants, each consisting of following items –(i) 4 pole MCCB 63 A current rating, 25 KA short circuit breaking capacity With Microprocessor based release with adjustable adjustable O/L & S/C setting with Inbuilt Instantaneous and Ground fault Protection -1 No.(ii)C.Ts. of suitable ratio- 1 No.(iii)Ammeter with selector switch - 1 No.(iv) Automatic start / stop device according to level in the sump- 1 No.(v)Indicating lamps(Auto/manual/low level/ reverse rotation) - 1 Set (E) 3 Nos. outgoing panels for miscellaneous works, each consisting of following items – (i) MCB of 40 A capacity- 1 No.(ii) C.Ts. of suitable ratio- 1 No. (iii) Ammeter with selector switch - 1 No.(iv) Indicating lamps- 1 Set (F)APFC Panel for total load.(G) 4 pole 400 A Rating ,35 kA Panel for DG sets incoming - 1 NO (G) Bus coupler arrangement in panels |
| 71 | LT Cable laying and jointing |
| 72 | Power and control cable-Supply of Armored 120 sq. mm 3.5 core cable - 2 Run required for power from each Transformer to each L.T. panel , Unarmored 120 sq. mm X3 core-1 run cable for power from starters to 40 HP Motors & Unarmored 10 sq. mm X3 core-1 run cable for power from starters to 15 HP Motors including lugging and jointing, laying, trench excavation and compaction as well as complete cabling of automation system etc. complete in all respect. |
| 73 | Earthing |
| 74 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% ofsize 600mm x 600mm x 3.0mm by embodying 3 mtr. below the groundlevel with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessorieslike nut, bolts, reducer, nipple, wire meshed funnel, and Heavy dutyweather proof poly-propylene earth pit chamber with lockable Jam freelid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. andembodying the pipe complete with alternate layers salt and coke/charcoal, testing of earth resistance for value of 5 ohms or less asrequired & must record by engineer in charge during site visit and ensureto enter in measurment book. All as per pre approved by Engineer incharge. Ref.14.3 (PRE BSR 2022) |
| 75 | Supply & Laying of 50mmX6mm size GI earth strip in horizontal or vertical run in ground/surface/recess including riveting,soldering, saddles, Jointing shall be done by overlapping and with 2 set of GI nut bolt & spring washer spaced at 50cm making connection etc.(20meter for each earthing) Ref.E140611 (PRE BSR 2021) |
| 76 | STARTER PANEL |
| 77 | SITC of Compraising of Soft Starter, suitable to meet the basic requirement of motor protections and suitable to run 40 HP motor (To be fixed in composite panel of LT Panel) |
| 78 | SITC of Compraising of Soft Starter, suitable to meet the basic requirement of motor protections and suitable to run 15 HP motor (To be fixed in composite panel of LT Panel) |
| 79 | Lighting system: |
| 80 | Supply & erection of M.S. Tubular Poles SP-36, 9.5 M height. |
| 81 | S/F of 72 watt LED with lumen reflector. |
| 82 | Feeder pillar for lighting |
| 83 | Supply and laying of 4x16mm2 Al. armoured cable. |
| 84 | Internal electrification with fixtures. |
| 85 | S/F 1200 mm ceiling Fan for LT Room |
| 86 | S/F of exhaust Fan for LT Room, |
| 87 | Earthing of street light pole (SOR-41) |
| 88 | Painting of street light (P5-634) |
| 89 | Supply and installation of DCP type of 5 Kg. Fire existinguisher (PS-1132) |
| 90 | 12 mm thick rubber mating for safe working on. (1mx2m) |
| 91 | Charges of Electrical safety Clearance |
| 92 | Expenditure on B&L Form, Challan etc. |
| 93 | Proper fencing of substation portion as per I.E. rules. (Ref. Ongoing AMRUT Work Aligarh Sewarage) |
| 94 | D.G. SET AND ACCESSORIES |
| 95 | SITC of Radiator Cooled and Turbo charged Silent type DG set , engine ,alternator capable of developing 125 kVA at 415+6%, 50 Hz AC at 0.85 P.F. lagging and self exciting coupled with suitable BHP diesel engine through flexible coupling and mounted on common base plate complete with fuel tank inside the acousting system and inbuilt control panel, Governor, Manual & electric Start , Batteries with battry charger, Engine instruments panel,AVM pads, All controls for operationof DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessiblefrom outside. T , 3 Met exhaust pipe, D.G. set shall be mounted under open sky resting on the foundation as per design, should comply CPCB-4. |
| 96 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 97 | Supply & Laying 50 mm X 6mm size GI earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 98 | Providing and Laying cable for DG Set to Panel 120 sq mm X 3.5 core x 2 run( armored aluminium ). |
| 99 | Supplying and making one end termination with heavy duty brass compression gland (as per IS 12943- 1990) SIBG type, heavy duty aluminium lugs (as per IS 8309 - 1993 & IS 8337-1976 ) duly crimped with crimping tool, PVC tape as per PWD specification for electrical Works etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade for 3.5 core X 240 sq mm. |
| 100 | SITC of Suitable capacity changeover switch |
| 101 | Three month Expenditure on Trial and Run Period |
| 102 | Mechanical Works |
| 103 | Large Pumps The submersible non clog pumpset should be single stage having two vanes enclosed impeller coupled with submersible motor of 40 HP Rating 400 Volt ±10%,3 phase 50 Hz, solid handling capacity 125mm, suitable to pump raw sewage with an specific gravity 1.03 having following construction of material with 10 Met. cable as offered. (2W+1S). Casing-2% Ni Cl. IS.210 grade F.G.220 with hardness 275 BHN. Impeller-Stainless steel CF-8M. shaft-stainless steel AISI-410. Discharge of pump= 4410 lpm. Total Head= 23 M. Speed=980. Quantity of pumps. |
| 104 | Guid Rail System Guide rail system (Automatic coupling system) for 40 HP submersible pump sets complete for above pump set. 03 Set |
| 105 | Lifting Chain , MOC- alloy steel, lifting chain with oval ring @ 1m & with D/Bow shackle |
| 106 | Small Pumps The submersible non clog pumpset should be single stage having two vanes enclosed impeller coupled with submersible motor of 15 HP Rating 400 Volt ±10%,3 phase 50 Hz, solid handling capacity 125mm, suitable to pump raw sewage with an specific gravity 1.03 having following construction of material with 10 Met. cable as offered. (1W+1S). Casing-2% Ni Cl. IS.210 grade F.G.220 with hardness 275 BHN. Impeller-Stainless steel CF-8M. shaft-stainless steel AISI-410. Discharge of pump=1910 lpm. Total Head= 17 M. Speed=980. Quantity of pumps.Guid Rail SystemGuide rail system (Automatic coupling system) for 15 HP submersible pump sets complete for above pump set. 03 SetLifting Chain , MOC- alloy steel, lifting chain with oval ring @ 1m & with D/Bow shackle |
| 107 | Main piping and Valves. 150 mm dia delivery for small pumps and 200 mm dia delivery for large pumps, 300 mm dia common header line.Valves.Confirming to IS 780/2906 or as applicable, PN rating- 1.0, Type of liquid to be handled-potable water.Material of construction Body-CI,IS-210 grade FG 200, Wedge-CI IS210 Grade FG200, Spindle-Stainless steel AISI304, Sheet and face Ring-SS ASTMA 743 Grade C.F.8 M, Channel& Shoe-S.S.AISI,.304, Drain& Air plug-S.S.AISI.304, Bushing arrangement-Halprene on bronze, Rivets-AISI:304, Fasteners-MS.Sluice Valves |
| 108 | Sluice Valve 150 mm dia |
| 109 | Sluice Valve 200 mm dia |
| 110 | Sluice Valve 400 mm dia |
| 111 | Reflux Valve |
| 112 | Reflux valve 150 mm dia N.B.(Ref. Attached SOR of IVC with CE (E/M), UP Jal Nigam Letter) |
| 113 | Reflux valve 200 mm dia N.B.(Ref. Attached SOR of IVC with CE (E/M), UP Jal Nigam Letter) |
| 114 | Pipings Note : Regarding the size of pipes, Tee, Bend etc, contrctor is required to designed them self and may got it approved by the department before execution of works along with layout drawing .(Ref.UPJN SOR, 2022) |
| 115 | 150 mm, K9 delivery pipes for small pumping plants |
| 116 | 200 mm, K9 delivery pipes for large pumping plants |
| 117 | 400 mm, K9 common header pipes |
| 118 | Specials like bend, tee, D Joint etc.@ of 5% |
| 119 | Nut Bolt, Washer Rubber packing etc @ of 5% |
| 120 | INSTALLATION, TESTING & COMMISSIONING |
| 121 | Installation & Commissioning of all Pump set,Piping & Valves as mentioned in above @10% of supplied items. |
| 122 | Level Transmitter (For Hi-Lo cut-off & alarms) |
| 123 | SITC of Radar type level transmitter shall be provided in the pump house for measuring the sewage level in wet sump. The indicator shall be digital type showing depth in meters and shall be capable for input to PLC or HMI touch sceen for display. |
| 124 | Electro magnetic flow meter |
| 125 | SITC of CE/UL certified Electro magnetic flow metersuitable to measure 0 to 30 MLD flow to be fitted in 300 mm dia main header line.(Ref. upjn SOR) |
| 126 | H.O.T. Crane |
| 127 | SITC of 3 Tonn Chain Pully Block, Travelling Trolly with single girder rectangular over head travelling crane with suitable hight lift complete with wire rope, etc complete in all respect (Ref. MJP SOR, 2022) |
| 128 | Chequerred plate and guards |
| 129 | SITC of 3mm thick M.S chequerred plate over all the run of cables trenches to cover properly and M.S. grill and M.S. guard over all pipes ducts and other point where required as per site condition (Ref. UP Jal Nigam, GM Gzb Rate) (3X0.75+3X0.9+7X0.6+1X0.9)X1=10.05sqmm. |
| 130 | PAINTING |
| 131 | Painting of all pumps piping and valves with two coat enamel paint. (Ref.UP Jal Nigam E&M SOR, 2019) |
| 132 | SCREENS AND GATES: |
| 133 | Rising type thimble mounted CI Sluice Gates of reputed make at IPS |
| 134 | Stainless steel Manual Screen (20 mm gaping) having bar size 50mmx10mm with 20 mm spacing at peak load |
| 135 | Packing and Frieght |
| 136 | Installation, Testing and Commissioning Please Enable Macros to View BoQ information |