| 1 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc for laying of cables, erection of poles, struts/ stays etc not exceeding 10 sqm on plan and getting out in soft loose soil complete all as speicifed and directed. |
| 2 | Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil complete all as speicifed and directed. |
| 3 | Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point in soils complete all as speicifed and directed. |
| 4 | M & L for sand filling in trenches for cushioning of LT cables punning after filling complete as specified and as directed.Note: Punned thickness shall only be measured and paid |
| 5 | Supply and lay un-reinforced precast concrete cable cover , class , LV , Type I flat size 250 x 150 x 40 mm laid dry in treches over under ground cables complete all as speicifed and directed. |
| 6 | S & F GI pipe, light grade, of size 50 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection complete all as speicifed and directed. |
| 7 | Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls of size 2 core 10 sqmm etc. complete all as specified and directed. |
| 8 | Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls of size 4 core 10 sqmm etc. complete all as specified and directed. |
| 9 | Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls of size 4 core 16 sqmm etc. complete all as specified and directed. |
| 10 | Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls of size 4 core 25 sqmm etc. complete all as specified and directed. |
| 11 | Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls of size 3.5 core 35 sqmm etc. complete all as specified and directed. |
| 12 | Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls of size 3.5 core 50 sqmm etc. complete all as specified and directed. |
| 13 | Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls of size 3.5 core 70 sqmm etc. complete all as specified and directed. |
| 14 | Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls of size 3.5 core 95 sqmm etc. complete all as specified and directed. |
| 15 | M&L for Disconnecting, taking out, removing old existing unserviceable LT underground cable of any size complete all as specified and directed. |
| 16 | Material and labour for bring the van mounted full automated underground cable fault locator machine at site for find out LT cable fault in underground completely all as specified and directed.Note: (a) Fault machine,cable & T&P required shall be arranged by the contractor.(b) Cable jointing kit for LT is measured separately |
| 17 | M&L for refreshing of incomming and all outgoing XLPE cable of any size including excavation for removing cable loop , refreshing of exsiting all cable by removing insulation ,including removing old damaged lugs and fixing of suitable size lugs, PVC conncetor,dressing of all cables . nuts ,bolts,washer to all incomming and outgoing MCCB , insulating all bare conductor with insulating cable of suitable colour all as sepcfiedc and directed.Note: Lugs and insulation top will be measured as separate item. |
| 18 | Supply and distribution of 50mm crushed stone aggregate of suitable thickness at various transformer location including removing old stone layer and reuse after removing dust same all as specified and directed. |
| 19 | Supply only Cordless angle Grinder 11,000 rpm, M10, Brushless Motor, Restart Protection, 2 x 18V 4.0Ah battery with quick charger, min 1 year warranty complete all as specified and directed. |
| 20 | Supply only Square Drive Socket Set 27 pcs made up of Chrome vanadium steel complete all as specified and directed. |
| 21 | Supply, erecting and fixing in true vertical position, Prestressed cement concrete pole 9 mtr long confirming to IS-1678 (latest) with minimum cross sectional area 102 mm x 152 mm at top and 102 mm x 289 mm at bottom , class - 10 ,removing of old pole to side and refixing of MS channel , restringing of conductor, providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30cm in between 2 bands and numbering of poles, and numbering of the poles shall be done with synthetic enameled painted letter of shape & size complete( M&L)all as specified and directed. (Note -SSR part I clause No.19.5 & 19.52 and other relevant clauses of SSR refers for execution of work and poles shall be procured directly from the manufacturer mentioned in tender documents.) |
| 22 | Excavation in trenches not exceeding 1.5m wide and exceeding 1.5m in depth and not exceeding 3.0m depth for foundation, laying of cable/pipe etc or for shaft, walls, cesspts, manholes, pier holes etc not exceeding 10 sqm on plan and getting out in hard/dense soil complete all as specified & directe |
| 23 | M&L for PCC (1:3:6) type C-2 using 40 mm graded crushed stone aggregate in foundation, filling and mass concrete for poles/struts etc including necessary formwork as required complete all as specified and directed. |
| 24 | M&L for PCC 1:2:4 type B-1 using 20 mm graded aggregates as in copings, kneelers, apex stones, bed plates, kerbs etc., water troughs and the like including weathering, slightly rounded for chamfered angles and throating including necessary form work complete all as specified and as directed. |
| 25 | M&L for cross arms bracings, supports, clamps and back plates fabricated from structural steel sections incl nut & bolts , washers welding, bending cold or hot drilling holes for bolts, washers in any shape of size as indicated or directd . |
| 26 | M&L for repair of LT panel doors using 75 mm SS hinges, SS latch, including welding & cutting work as per site requirement all as specified and directed. |
| 27 | M&L for spray painting of LT panel inside and outside surface, including surface prepration by scrubbing of existing paint, and applying two coat of synthtic enamel paint over one coat of red oxide, colour of paint & pattern as per exsiting all as specfied and directed. |
| 28 | Supply and fix in repiars the following items and disconnecting,taking out the old unserviceable one, including necessary replacemnet of lugs ,nuts,bolts lugs , cutting existing CRCA sheet of any size and capacity wherever reqd :- |
| 29 | MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 63 Amps 16 KA complete all as specified and directed. |
| 30 | MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 100 Amps 16 KA complete all as specified and directed. |
| 31 | MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 160 Amps 36 KA complete all as specified and directed. |
| 32 | MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 250 Amps 36 KA complete all as specified and directed. |
| 33 | MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 400 Amps 36 KA complete all as specified and directed. |
| 34 | M&L for removing shrub and creeper on electrical pole ,electrical panel ,at substation ,chain link fencing on hardstanding pcc all as specfied and directed. |
| 35 | supply and fix in repiar on load changeover 415V 250A with enclosure, disconncetion & taking down and reconnection with proper size of lugs all as specfied and directed. |
| 36 | Material and labour for cutting of existing road ,insert the required size pipe for drawn of cable etc and repair the same with PCC 1:2:4 type B2 (using 40 mm graded stone aggregate) for filling the disturbed road opening for cable crossing include levelling with road surface and smooth finishing complete all as specified and directed. ( for Road Cutting Repair) |
| 37 | Maintaning of LT over head lines by trimming the of tree branches tuching to the HT/LT over head conductors lines upto 03 mtr away from the live conductors surrounding area complete all as directed at site complete all as specified and directed. Note :- cost of labours deemed to be including cutting the tree branches and depositing the tree branches away 50 Mtr away from the poles or as directed at sie complete. |
| 38 | Fabricate, Supply, Install, Testing and Commissioning LT Panel Board outdoor type factory made CPRI tested made out of CRCA sheet steel enclusure 3.15 mm thick including aluminium bus bar 4 pole for all incoming MCCB to outgoing MCCB , wiring of rated capacity PVC insulated copper conductor cable for SPNs, front back openable, , IP 65 , Gasket insulators, fasteners etc with Digital Ammeter & Voltmeter, selector switches for voltmeter and ammeter, indicator lamp RYB (01 Set), moulded (resign cast) CTs , copper tin spreader link, spring washer, busbar spacing should be 30mm minium for phase to phase , including MS Angle Frame of size 50x50x5 mm structure at bottom,minimum 0.8 meter height from ground level,marking of outgoing area as per site, Air vent , PCC foundation 1:2:4 for foundation etc, taking down old LT panel comprising for the following :-Note : The contractor shall submit detail Schematic Layout of the Panel Board for approval from Engr-in-Charge before procurement.Location :Main LT panel (52 Medium Gun Park )(a) Aluminium Bus Bar 600 A rating for 3 Phase and 300 A for Neutral - 01 Set(b) 3 Line digital multimeter for measuring basic electrical parameter-1(c) LED Indication Lamp for 3 Phase for incoming and for all outgoing (d) MCCB 4 Pole 400 Amps 36 KA, Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 01 Nos (01 No for Incoming)(e) MCCB 4 Pole 250 Amps 36 KA,Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 02 Nos(f) MCCB 4 Pole 100 Amps 36 KA, Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 02Nos(g) MCCB 4 Pole 160 Amps 36 KA, Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 01Nos (g) MCCB 4 Pole 63 Amps 16 KA, Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 01Nos (j) 5KW automatic timer panel -01 Nos |
| 39 | Fabricate, Supply, Install, Testing and Commissioning LT Panel Board outdoor type factory made CPRI tested made out of CRCA sheet steel enclusure 3.15 mm thick including aluminium bus bar 4 pole for all incoming MCCB to outgoing MCCB , wiring of rated capacity PVC insulated copper conductor cable for SPNs, front back openable, , IP 65 , Gasket insulators, fasteners etc with Digital Ammeter & Voltmeter, selector switches for voltmeter and ammeter, indicator lamp RYB (01 Set), moulded (resign cast) CTs , copper tin spreader link, spring washer, busbar spacing should be 30mm minium for phase to phase , including MS Angle Frame of size 50x50x5 mm structure at bottom,minimum 0.8 meter height from ground level,marking of outgoing area as per site, Air vent , PCC foundation 1:2:4 for foundation etc, taking down old LT panel comprising for the following :-Note : The contractor shall submit detail Schematic Layout of the Panel Board for approval from Engr-in-Charge before procurement.Location : (a) Aluminium Bus Bar 500A rating for 3 Phase and 250 A for Neutral - 01 Set(b) 3 Line digital multimeter for measuring basic electrical parameter-1(c) LED Indication Lamp for 3 Phase for incoming and for all outgoing (d) MCCB 4 Pole 320 Amps 36KA, Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 01 Nos (01 No for Incoming)(e) MCCB 4 Pole 160 Amps 36 KA,Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 02 Nos(f) MCCB 4 Pole 100 Amps 36 KA, Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 02Nos (g) MCCB 4 Pole 63Amps 36 KA, Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 01Nos (h) Onlaod change over 320 A,415V at incoming-1 Nos (j) 5KW automatic timer panel -01 Nos |
| 40 | Fabricate, Supply, Install, Testing and Commissioning LT Panel Board outdoor type factory made CPRI tested made out of CRCA sheet steel enclusure 3.15 mm thick including aluminium bus bar 4 pole for all incoming MCCB to outgoing MCCB , wiring of rated capacity PVC insulated copper conductor cable for SPNs, front back openable, , IP 65 , Gasket insulators, fasteners etc with Digital Ammeter & Voltmeter, selector switches for voltmeter and ammeter, indicator lamp RYB (01 Set), moulded (resign cast) CTs , copper tin spreader link, spring washer, busbar spacing should be 30mm minium for phase to phase , including MS Angle Frame of size 50x50x5 mm structure at bottom,minimum 0.8 meter height from ground level,marking of outgoing area as per site, Air vent , PCC foundation 1:2:4 for foundation etc, taking down old LT panel comprising for the following :-Note : The contractor shall submit detail Schematic Layout of the Panel Board for approval from Engr-in-Charge before procurement.Location : (MAP OR Qtrs )(a) Aluminium Bus Bar 250 A rating for 3 Phase and 125 A for Neutral - 01 Set(b) 3 Line digital multimeter for measuring basic electrical parameter-1(c) LED Indication Lamp for 3 Phase for incoming and for all outgoing (d) MCCB 4 Pole 160Amps 36KA, Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 01 Nos (01 No for Incoming)(f) MCCB 4 Pole 63 Amps 36 KA, Ics=100%ICu, thermal adjsutable, shortcircuit adjsutable - 05Nos |
| 41 | Supply, installing ,testing and commissioing factory made and tested LT Outdoor Street/Flood Light Control Panel having platform mounted,suitable for 415 Volts 3 Phase and neutral 4 wire,50 HZ AC supply system shall be dust and vermin proof,protection class(IP-65) and made of CRCA sheet steel enclusure 3.15 mm thick suitable framework/Support made out of 40x40x5 mm MS Iron angle frame ,front opening type with aprons for cable entry,with proper ferrul and cable gland,internal wiring with PVC insulated multistranded copper conductor FRLS Cable of adequate size but not less than 4 sqmm,minimum 0.5 meter height from ground level,marking of outgoing area as per site, Air vent , PCC foundation 1:2:4 for foundation etc complete. Note : The contractor shall submit detail Schematic Layout of the Panel Board for approval from Engr-in-Charge before procurement.The scope of work also comprising of the following :-(i) RYB Phase indicating LED type -01 set. (ii) MCB TPN 40Amps 4 polez,10 KA,50 HZ,415 Volts-01 No (iii) Power contactor 3 Pole,40 Amps.50 Hz,415 Volts-01 No. (iv) Time switch Digital Type,one dial daily,240/415 Volts,50 Hz-01 No. (v) Auto/Manual selector switch 6A-01 No.(vi) RYB Phase indicating light LED Type -03 No. |
| 42 | Taking down & Supply and fixing cable junction box with new pole mounted polycarbonate cable junction box of size 255x205x112mm or next higher size for street light with IP-66 protection, weather proof with metric knockouts for cable entry for outdoor installation with front door opening system, cable gland, cable terminal for incoming and outgoing cable according to cable size including terminals for one incoming and one outgoing cables of size 16/25 sqmm 4 core, tapping of 3 Core 2.5/1.5sqmm from terminals, with one MCB SP 6 Amp 240V AC with mounting on DIN rail, pole clamp of flat iron, nut, bolt and washers complete all as specified and directed . Make : National/Sintex/Hansel |
| 43 | Supply and fix and heating of insulating PVC sleeve of size suitable for LT cable of szie 25 sqmm to 180sqmm as per colour code including refreshing end of cable on pole or LT panel complete all as specified and directed. |
| 44 | Supply install testing,commissioning of CRI tested Copper earthing electrode of length 3 metres, 40mm dia and back fill compound of 50kgs ,and conductive gel to retain moisture should be filled layer wise and inter connceted by exothermic brazing & copper strip of size 32x6mm should be suppllied and fix upto testpoint protected by GI pipe of size 50mm dia up to test point including disconnection of old earth strip and fix to new chemical earthing, PCC earth pit of standared size as per SSR part-1 and submmision of earth results and painting of Date of test , value obtain at site and complete all as specified and directed. |
| 45 | Material and labour for earthing complete with GI earth plate electrode 600x600x6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground lavel) with top edge of the plate not less than 1.5mtr below normal ground lavel connected to Galvanised iron earth strip 32x6 mm by mean of bolts, nuts, check nuts and washer of brash all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including PCC pit and CI cover fullel with watering pipe, wire mess and copper lugs etc GI protection pipe 40 mm dia medium grade including testing on completion all as specified and directed.Note :- (i) Earthing shall be tested as specified in casul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On testing after complataion of earthing , if the desired earth resistance is not obatined the earthing wiil be re done by the contractor at his on risk and cost to the entire satisfaction of the GE. |
| 46 | Supply and fix 2 core aluminium service cale of size 16sqmm complete all as specified and directed. |
| 47 | Supply and fix 2 core aluminium service cale of size 10sqmm complete all as specified and directed. |
| 48 | Supply and fix aluminium lugs of following size including insulation on lugs as per colour code complete all as specified and directed. |
| 49 | a) 16sqmm |
| 50 | b) 25sqmm |
| 51 | c) 35sqmm |
| 52 | d) 50sqmm |
| 53 | e) 70sqmm |
| 54 | f) 120sqmm |
| 55 | g) 150sqmm |
| 56 | h)185sqmm |
| 57 | i) 250sqmm |
| 58 | j) 300sqmm |
| 59 | M&L for cable jointing kit LT 1.1KV straight through joint 185sqmm ,heat shrinkable type with all accessories complete all as specified and directed. |
| 60 | M&L for cable jointing kit LT 1.1KV straight through joint 120sqmm ,heat shrinkable type with all accessories complete all as specified and directed. |
| 61 | M&L for cable jointing kit LT 1.1KV straight through joint 95 sqmm ,heat shrinkable type with all accessories complete all as specified and directed. |
| 62 | M&L for cable jointing kit LT 1.1KV straight through joint 70 sqmm ,heat shrinkable type with all accessories complete all as specified and directed. |
| 63 | M&L for cable jointing kit LT 1.1KV straight through joint 50sqmm ,heat shrinkable type with all accessories complete all as specified and directed. |
| 64 | M&L for cable jointing kit LT 1.1KV straight through joint 35sqmm ,heat shrinkable type with all accessories complete all as specified and directed. |
| 65 | M&L for cable jointing kit LT 1.1KV straight through joint 25sqmm ,heat shrinkable type with all accessories complete all as specified and directed. |
| 66 | Supply and drawing through the pole for making connections to the light fittings, three core, PVC insulated and sheated, Heavy duty,1100 volts grade,multistranded copper conductor (FRLS) cable 3Cx1.5 sqmm complete all as specified and directed. |
| 67 | Supply and fixing PVC pipe 25/20 mm through FRP Junction to street light clamp on the pole including all connecting accessories to the pole complete all as specified and directed. |
| 68 | Supply and fixing PVC flexible pipe 25/40 mm for protection of cable etc complete all as specified and directed. |
| 69 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 16 Sqmm, 2 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 70 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 16 Sqmm, 4 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 71 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 35 Sqmm, 4 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 72 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 50 Sqmm, 3.5 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 73 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 70 Sqmm, 3.5 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 74 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth in hard/dense soil for laying of cable/ GI pipe and getting out complete all as specified and directed. |
| 75 | Returning, filling in including spreading levelling watering well ramming in layers not exceeding 25cm each complete all as specified and directed. |
| 76 | Removing surplus soil to a distance outside MD land and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 77 | Material and labour for dry clean river sand for cushioning of cable in trenches for cable protection including spreading, leveling and hand punning complete all as specified in SSR Part-I and complete all as specified and directed. Note :- Only compacted thickness of sand will be measured and paid separately. |
| 78 | Supplying and laying un-reinforced precast concrete cable cover, Class LV, Type 1, flat as per size 250mm x 150mm x 40mm for LT cable and laid dry in trenches over underground cables complete all as specified and directed. |
| 79 | Supply, erecting and fixing in true vertical position, Prestressed cement concrete pole 9 mtr long confirming to IS-1678 (latest) with minimum cross sectional area 102 mm x 152 mm at top and 102 mm x 289 mm at bottom , class - 10 ,removing of old pole to side and refixing of MS channel , restringing of conductor, providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30cm in between 2 bands and numbering of poles, and numbering of the poles shall be done with synthetic enameled painted letter of shape & size complete( M&L)all as specified and directed. (Note -SSR part I clause No.19.5 & 19.52 and other relevant clauses of SSR refers for execution of work and poles shall be procured directly from the manufacturer mentioned in tender documents.) |
| 80 | M&L for PCC (1:3:6) type C-2 using 40 mm graded crushed stone aggregate in foundation, filling and mass concrete for poles/struts etc including necessary formwork as required complete all as specified and directed. |
| 81 | M&L for PCC 1:2:4 type B-1 using 20 mm graded aggregates as in copings, kneelers, apex stones, bed plates, kerbs etc., water troughs and the like including weathering, slightly rounded for chamfered angles and throating including necessary form work complete all as specified and as directed. |
| 82 | M&L for restraining of HT/LT Over head aluminium conductor of any size including taking down aluminium conductor and refixing the same conductor to insulator including aluminium binding works for connceting insulator and conductor , tighting of pin insulator , MS channel refixing of outgoing conductor ,removing all old unservicable tapping from pole complete all as specified and directed. |
| 83 | Supply and fix of line (spiral) spacer as per IS code 1445/1977 of 1 phase 2 run of dia not less than 10mm of suitable length complete all as specified and directed. |
| 84 | Supply and fix of 2.5sqmm 3 core aluminium conductor from every street light fitting to OH line, junction box complete all as specified and as directed. |
| 85 | Supply and fixing stay assembly complete with accessories as showing in electrical plate No. 1 with 16mm dia stay rod (loop type insulator, stay strand, stay clamps and excavation, PCC will be measured and paid separately on as required basis) complete all as specified and as directed. |
| 86 | Supply and erection of Cross arms, bracings, supports, clamps and back plates, equal channel, anchor for stay wire, stay strand fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or complete all as specified and as directed. |
| 87 | M&L for painting of pole by providing 6 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30cm in between 2 bands and numbering of poles, and numbering of the poles shall be done with synthetic enameled painted letter of shape & size complete all as specified and directed. (Gate No -1 TO Gate No 3 outer fencing side) |
| 88 | Supply and fixing pole mounted thermoplastic cable junction box for steet light with IP-66 protection, halogen free and weather proof with metric knockouts for cable entry for outdoor installation of size 200mm x 160mm x 98mm with front door opening system including terminals for one incoming and two outgoing cables of size 16 sqmm 4 core, one MCB SP 10 Amp 240V AC with mounting clamp of flat iron, nut, bolt and washers complete all as specified and directed. Make of J/B - HENSEL. |
| 89 | Supply and fixing in replacement of Street light fitting in new generation energy saving environemental friendly long life LED street light with single die ceramic base high power LED light source,PDC housing with top openable access to driver for ease maintenance , lumen output 12000-21000 , system effiency 100 lm/watt , color temp 5700 K , made up of LM6 high pressure die cast aluminium housing with toughned glass ,IP66 protection , PF 0.95 , operating voltage 140-270 Volt and impact of capacity 90 Watt, bracket as per site requirement including all accessories complete all as specified and directed. |
| 90 | M&L for removing shrub and creeper on electrical pole ,electrical panel ,at substation ,chain link fencing on Hardstanding PCC complete all as specified and directed. |
| 91 | Maintaning of HT/LT over head lines by trimming the of tree branches tuching to the HT/LT over head conductors lines upto 03 mtr away from the live conductors surrounding area complete all as specified and directed. (Note :- cost of labours deemed to be including cutting the tree branches and depositing the tree branches 50 Mtr away from the poles or as directed at sie complete and reqd suitable cutting tool by contractor.) |
| 92 | M&L for repair of LT panel doors using 75 mm SS hinges, SS latch, including Gas welding work all as specified and directed. |
| 93 | M & L for cable jointing kitfor LT 1.1 KV straight through joint 95 sqmm, 3.5 core, heat shrinkable type with all accessories complete all as specified and directed. |
| 94 | M & L for cable jointing kitfor LT 1.1 KV straight through joint 70 sqmm, 3.5 core, heat shrinkable type with all accessories complete all as specified and directed. |
| 95 | M & L for cable jointing kitfor LT 1.1 KV straight through joint 50 sqmm, 3.5 core, heat shrinkable type with all accessories complete all as specified and directed. |
| 96 | M & L for cable jointing kitfor LT 1.1 KV straight through joint upto 35 sqmm, 3.5 core, heat shrinkable type with all accessoriescomplete all as specified and directed. |
| 97 | Supply and fix in repiars the following items and disconnecting,taking out the old unserviceable one, including necessary replacemnet of lugs ,nuts,bolts, washer of any size and capacity wherever reqd :- |
| 98 | (a) MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 63 Amps 16 KA complete all as specified and directed. |
| 99 | (b) MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 100 Amps 16 KA complete all as specified and directed. |
| 100 | (c) MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 160 Amps 36 KA complete all as specified and directed. |
| 101 | (d) MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 200 Amps 36 KA complete all as specified and directed. |
| 102 | (e) MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 250 Amps 36 KA complete all as specified and directed. |
| 103 | (f) MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 400 Amps 36 KA complete all as specified and directed. |
| 104 | S & F GI pipe, light grade,upto of size 80 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection |
| 105 | NOTE APPLICABLE FOR ALL ITEMS :- If rate quoted for similar/identical items in same part of Sch ‘A’ is at variance, the lowest rate quoted shall only be considered for payment to the contractor. Please Enable Macros to View BoQ information |