| 1 | Taking down the LED street light of any make any specification from existing PCC pole and refix the same LED street light in Steel tubular pole complete all as specified and as directed by Engr-in-charge. |
| 2 | Taking down of ACSR conductor of any specification complete all as specified and as directed |
| 3 | Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 mtr depth for laying cable at and getting out in soft/ loose soil all as specified and directed. |
| 4 | Excavation in trenches not exceeding 1.5 Mtr wide and exceeding 1.5 mtr depth up to 3 mtr for laying cable at and getting out in soft/ loose soil all as specified and directed. |
| 5 | Returning, filling in soil including spreading, levelling, watering and well ramming in layers, not exceeding 25 cm thick all as specified and directed |
| 6 | Removing surplus soil to a distance not exceeding 50 Mtr and deposited at a level not exceeding 1.5 mtr above from the starting point all as specified |
| 7 | M & L for PCC 1:2:4 type B1 using 20 mm graded stone aggregate coping of poles including forming work complete all as specified |
| 8 | M & L for PCC 1:3:6 type B2 using 40mm graded stone aggregate in foundations of poles, filling and mass concrete complete all as specified. |
| 9 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core |
| 10 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core |
| 11 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core |
| 12 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core |
| 13 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core |
| 14 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core |
| 15 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core |
| 16 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core |
| 17 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core |
| 18 | Supply and laying in trenches of 40 mm dia DWC HDPE pipe, Heavy Duty, conforming to IS 14930 Part 2, made of HDPE, with corrugated outer wall and smooth inner bore, suitable for passing 1.1 kV, 4C x 10 Sqmm to 3.5C x 35 Sqmm XLPE cable, including cost of couplers, jointing accessories, end caps, and laying as per site requirement Complete all as specified and directed by Engr-in-Charge direction. Make: SFMC, Reliance, Supreme. |
| 19 | All as per item No. 18.00 above 80 mm dia |
| 20 | All as per item No. 18.00 above 100 mm dia |
| 21 | All as per item No. 18.00 above 150 mm dia |
| 22 | M&L for cutting of road / hard standing up to a size not exceeding 20cm in width and not exceeding 60cm in depth for laying of LT UG cable/ protection pipe line making good the disturbed portion so as to match existing finishing with PCC 1:2:4 type B1/ cement mortar in CM(1:2) Complete all as specified and directed. |
| 23 | S & F Galvanised iron tubing, light grade with all fittings fixed complete to walls, poles, ceiling or laid in floors/ trenches/ road crossing/ beside steel tubular poles for the protection of cable for the following sizes all as specified and as directed. |
| 24 | 40 mm bore |
| 25 | 80 mm bore |
| 26 | Supply and fix steel tubular swaged poles In replacement of concrete/ strut poles, type 410 SP-31 (09 meter long) complete with CI base plate, final taper plug, bolts, nut, screws and finial including foundation and coping with Stickering of any type of street light pole with A1 graded radium strip of 100mm width three colour red, Yellow and green around the pole with 100mm gap in each strip at a distance of 1.1 metre high from the ground level complete all as directed complete all as specified and as directed.Note:- Foundation & coping measured and paid separately |
| 27 | S&F street light bracket single arm suitable to fix on the top of steel tubular swaged poles type 410 SP-31 (9 meter long) without making hole on pole complete all as specified and directed. |
| 28 | Supply and fix, Street light control junction box 230 x 170 x 105mm up to 25 Sqmm 3.5/ 4 core cables made out of FRP sheet moulded and arrangement for incoming and outgoing 3 phase 4 wire system with R, Y, B & N studs and control for incoming and outgoing cables with MCB SP 10 Amp 230 volts with neutral link including pole mounting kit, completed all as specified and directed.Make: HENSEL, HAGER, LEGRAND, PHOENIX.Note: Small variations in specification is acceptable as directed by GE. |
| 29 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor cable of size 3 core 4 sq mm served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 4 sq mm 3 core in service connections complete all as specified and directed. |
| 30 | Supply fixing connecting and testing in repairs/ replacement decorative LED Bollard light with opal diffuser & aluminium reflector of 8-10 watt 3 Feet LED including nut, bolts, washers, clamps etc complete all as specified and directed by Engr -in-charge. Make : Havells, Crompton, Bajaj, Philips, Wipro or as approved by GE . Note : Make, Model, colour temp as approved by GE irrespective of given make. |
| 31 | S&F in repair / replacement of old Unsv light with FLEXISTRIP IP 67 rated flexible LED strip to add great colour & dramatic effects with extensive pallet of colours of 36 watt DMX complete all as specified and directed. Make Bajaj, Crompton, Havells, Orient, Fortune Art or as approved by GE . |
| 32 | Supply and fixing LED Solar street light fitting 36 Watt, lithium ion battery, solar panel, charge controller with dusk down sensor complete all as specified and as directed by Engineer in Charge |
| 33 | S&F in repairs, Aesthetically designed decorative hot dipped galvanised mild steel step 3M pole with grey powder finish, Compatible for post top range. Window - Plasma cut & duly chamfered opening window of 300x110 mm for terminal connections & mounting accessories Window cover is fitted with allen screws to the pole complete all as specified and as directed. Make : Havells cat no - DECO POLE 3M TOP Ø 76 MM or equivalent in Crompton greaves or Bajaj. |
| 34 | S&F 60 W Circular LED post-top offering excellent uniform illumination and aesthetics in one go Made up of Pressure Die Cast aluminium body and opal PC cover., IP 66 and IK 07 rating complete all as specified and as directed. Make :- Havells cat no-RINKPT45WLED757PSYMTOPC or equivalent in Crompton greaves or Bajaj. or as approved by GE |
| 35 | Supply and fix steel tubular swaged poles type 410 SP-55 (11 meter long) complete with CI base plate, final taper plug, bolts, nut, screws and finial including foundation and coping complete all as specified and as directed.Note:- Foundation & coping measured and paid separately |
| 36 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 MPA working pressure. |
| 37 | Supply fabrication, and fixing of a circular ring arrangement for flood light mounting on a 11m high GI tubular pole, comprising a 600 mm diameter outer ring fabricated from 50 mm dia medium class MS pipe (IS:1239), reinforced with 4 spoke-type supports made of 25 mm dia MS pipe, all welded to a central hub ring of suitable dia for fix on pole . The central hub is mounted on the pole top using a fabricated MS base plate with GI U-bolts, nuts, and washers for firm attachment. The ring shall be provided with 4 equidistantly spaced flood light mounting arms made from 25 mm × 6 mm MS flats or angles, each approximately 250–300 mm long, with drilled 12 mm holes to accommodate bolt-on LED flood lights of 100–150 W rating. All MS components shall be thoroughly cleaned, given one coat of red oxide primer, and finished with two coats of weather-resistant black enamel paint. The entire assembly shall be installed securely at the pole top with proper alignment, ensuring structural stability and safe mounting of flood lights complete all as specified and directed. |
| 38 | Supply & fix 200 watts LED flood light fittings new generation energy saving, environmental friendly, long life, versatile pressure die cast aluminium IP65 complete all as specified and directed.Make: Havells cat no: JETAADORNNXTFLS200WLED757SSYMTOTGV2 or equivalent make of Crompton greaves or Bajaj or as approved by GE |
| 39 | S&F Weather proof outdoor bus bar chamber, made out of 3 mm thick MS sheet duly powder quoted comprising 4 Nos aluminium strips each of 125 Amps, 60cm long duly insulated mounted on insulators including MCCB 125 Amp with 4 No’s mounting legs made out of 25mm x 25mm x 6mm angle iron grouted in PCC block of size 30cm x 30cm x 90cm (30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), and connections with suitable size of aluminium thimbles, nuts, bolts & washers including cable glands at entry and outlet points including excavation and earth work, returning filling and removal of surplus soils complete all as specified and directed. |
| 40 | S&F Weather proof outdoor bus bar chamber, made out of 3 mm thick MS sheet duly powder quoted comprising 4 Nos aluminium strips each of 160 Amps, 60cm long duly insulated mounted on insulators including MCCB 160 Amp with 4 No’s mounting legs made out of 25mm x 25mm x 6mm angle iron grouted in PCC block of size 30cm x 30cm x 90cm (30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), and connections with suitable size of aluminium thimbles, nuts, bolts & washers including cable glands at entry and outlet points including excavation and earth work, returning filling and removal of surplus soils complete all as specified and directed. |
| 41 | S&F in replacement of LT panel, outdoor type, floor mounted, fabricated from minimum 3.0 mm thick CRCA sheet steel, dust, vermin and weather proof, IP-55 protected, epoxy polyester powder coated, suitable for 415 V ±10%, 3 phase, 4 wire, 50 Hz AC, conforming to IS 8623 / IEC 61439. The panel shall have 200 Amps aluminium busbars with separate neutral and earth busbars, fully shrouded and colour coded. Internal wiring shall be with 1100 V grade PVC insulated copper conductors. The enclosure shall have double doors, neoprene gasket, heavy duty hinges, padlock facility, danger notice, circuit labels, schematic inside, and weather-proof louvers. The panel shall be provided with two independent earth terminals connected to earth busbar. The panel size shall be as per internal arrangement and shall be mounted on MS frame / concrete plinth at minimum 0.5 m height above FGL or as directed by GE. All civil works including foundation, grouting, fixing and making good shall be included. All necessary cable glands, terminations, ferruling, mounting hardware, testing and commissioning shall be included, complete in all respects.Make of Panel & Switchgear: ABB / Siemens / Schneider / L&T / LegrandIncoming: 200 Amps, 16 kA TP&N MCCB Outgoing: 05 Nos 3-pin, 20 A, 240 V Socket and 01 No 5-pin, 50–63 A Socket, 415 V industrial socket outlets, IP-67 rated, interlocked, with independent MCB / MCCB protection complete all as specified and directed. |
| 42 | Supply, installing, testing and commissioning, factory made and tested, CPRI approved in replacement of LT panel board out door type, weather, vermin proof, cubical type, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary Aluminium bus bar arrangement with insulated bus bar 600 Amps rating, 4 strips, the panel should be dust proof, IP 65 class protection and made out of 3 mm thick CRCA mild steel sheet with 40x40x5mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement and duly powder coated on the out side and inside, cable glands and lugs for incoming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories :- |
| 43 | Incoming: (a) MCCB 4 Pole, 415 V 36 KA, capacity 315 Amps - 01 NoOutgoing : (b) MCCB 4 pole, 200 Amp, 415 Volts 16 KA – 02 No (c) MCCB 4 pole, 160 Amp, 415 Volts 25 KA – 02 No (d) 1 Nos of 3 - pin, 20 A, 215 V Socket(e) Indicating lamps (set 03 Nos) - 01 set (R, Y & B)(f) Digital panel mounted Voltmeter and ammeter flush type of size 96 X 96 mm three phase(g) 3 Phase Astronomical based Street light timer with contactor of suitable capacity - 01 No(h) Panel wiring with suitable size PVC insulated heavy duty 1100 volts grade single core cable with copper conductor multistranded with cable end termination lugs The panel size shall be as per internal arrangement and shall be mounted on MS frame / concrete plinth at minimum 0.5 m height above FGL or as directed by GE. All civil works including foundation, grouting, fixing and making good shall be included. All necessary cable glands (double compression brass), terminations, ferruling, mounting hardware, testing and commissioning shall be included, complete in all respects.MAKE: ABB / Siemens / Schneider / L&T / Legrand |
| 44 | Supply, installing, testing and commissioning, factory made and tested, CPRI approved in replacement of LT panel board out door type, weather, vermin proof, cubical type, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary Aluminium bus bar arrangement with insulated bus bar 250 Amps rating, 4 strips, the panel should be dust proof, IP 65 class protection and made out of 3 mm thick CRCA mild steel sheet with 40x40x5mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement and duly powder coated on the out side and inside, cable glands and lugs for incoming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories :- |
| 45 | Incoming: (a) MCCB 4 Pole, 160 A, 415 V 16 KA - 01 NoOut going : (b) MCCB 4 pole, 125 Amp, 415 Volts 16 KA – 02 No (c) MCCB 4 pole, 100 Amp, 415 Volts 25 KA – 04 No (d) 1 Nos of 3 - pin, 20 A, Socket 215 V (e) Indicating lamps (set 03 Nos) - 01 set (R, Y & B)(f) Digital panel mounted Voltmeter and ammeter flush type of size 96 X 96 mm three phase(g) 3 Phase Astronomical based Street light timer with contactor of suitable capacity -01 No(h) Panel wiring with suitable size PVC insulated heavy duty 1100 volts grade single core cable with copper conductor multistranded with cable end termination lugs The panel size shall be as per internal arrangement and shall be mounted on MS frame / concrete plinth at minimum 0.5 m height above FGL or as directed by GE. All civil works including foundation, grouting, fixing and making good shall be included. All necessary cable glands (double compression brass), terminations, ferruling, mounting hardware, testing and commissioning shall be included, complete in all respects.MAKE:ABB / Siemens / Schneider / L&T / Legrand |
| 46 | Supply, installing, testing and commissioning, factory made and tested, CPRI approved in replacement of LT panel board out door type, weather, vermin proof, cubical type, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary Aluminium bus bar arrangement with insulated bus bar 250 Amps rating, 4 strips, the panel should be dust proof, IP 65 class protection and made out of 3 mm thick CRCA mild steel sheet with 40x40x5mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement and duly powder coated on the out side and inside, cable glands and lugs for incoming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories :- |
| 47 | Incoming: (a) MCCB 4 Pole, 125 A, 415 V 16 KA - 01 NoOut going : (b) MCCB 4 pole, 100 Amp, 415 Volts 16 KA – 02 No (c) MCCB 4 pole, 63 Amp, 415 Volts 25 KA – 02 No (d) 1 Nos of 3 - pin, 20 A, Socket 215 V (e) 2 pole MCB 20 Amps - 6No(f) Indicating lamps (set 03 Nos) - 01 set (R, Y & B)(g) Digital panel mounted Voltmeter and ammeter flush type of size 96 X 96 mm three phase(h) Panel wiring with suitable size PVC insulated heavy duty 1100 volts grade single core cable with copper conductor multistranded with cable end termination lugs The panel size shall be as per internal arrangement and shall be mounted on MS frame / concrete plinth at minimum 0.5 m height above FGL or as directed by GE. All civil works including foundation, grouting, fixing and making good shall be included. All necessary cable glands (double compression brass), terminations, ferruling, mounting hardware, testing and commissioning shall be included, complete in all respects.MAKE:ABB / Siemens / Schneider / L&T / Legrand |
| 48 | Supply, installing, testing and commissioning, factory made and tested, CPRI approved in replacement of LT panel board out door type, weather, vermin proof, cubical type, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary Aluminium bus bar arrangement with insulated bus bar 400 Amps rating, 4 strips, the panel should be dust proof, IP 65 class protection and made out of 3 mm thick CRCA mild steel sheet with 40x40x5mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement and duly powder coated on the out side and inside, cable glands and lugs for incoming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories :- |
| 49 | Incoming: (a) MCCB 4 Pole, 260 A, 415 V 25 KA - 01 No(b) Change over of 260 Amp - 02 Outgoing : (c) MCCB 4 pole, 200 Amp, 415 Volts 16 KA – 03 No (d) MCCB 4 pole, 160 Amp, 415 Volts 25 KA – 03 No (e) 1 Nos of 5 - pin, 50-63 A, 415 V Socket(f) Timer plus power contactor- 1 No (g) Indicating lamps (set 03 Nos) - 01 set (R, Y & B)(h) Digital panel mounted Voltmeter and ammeter flush type of size 96 X 96 mm three phase(i) Panel wiring with suitable size PVC insulated heavy duty 1100 volts grade single core cable with copper conductor multistranded with cable end termination lugs The panel size shall be as per internal arrangement and shall be mounted on MS frame / concrete plinth at minimum 0.5 m height above FGL or as directed by GE. All civil works including foundation, grouting, fixing and making good shall be included. All necessary cable glands (double compression brass), terminations, ferruling, mounting hardware, testing and commissioning shall be included, complete in all respects.MAKE: ABB / Siemens / Schneider / L&T / Legrand |
| 50 | M & L earthing complete with Copper earth plate electrode 60cm x 60cm x 3.15 mm thick buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5m below ground level, connecting to the Copper earth strip 20 x 3 mm, by means of nuts, bolts, check nuts and washer etc of galvanised iron and earth lead protected by provision of GI pipe light grade 40mm bore from earth electrode to test point incl provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM sheet (weight not less than 4Kg/ Sqm) and frame of angle iron 25 x 25 x 6mm with lugs 2 Nos and with 8mm dia MS bar handle made to shape, GI pipe medium grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling test point with fixing arrangement, funnel, wire mesh and earth work in hard/ dense soil, returning in and removal of surplus soil to a distance not exceeding 50mtr, complete all as specified in electrical plate No 3 of SSR Part I and connection to earth test point including testing on completion all as directed. Note:- Item of earthing includes cost of 7.5m long Copper earth strip of 20 x 3 mm size and protection pipe of 40mm bore GI light grade. Please Enable Macros to View BoQ information |