| 1 | SITC of Heat pump Outdoor Type (IPX4/IPX5) or Better, with Heating Capacity: 50KW, Cooling Capacity: 42.1, COP of Heating: 4.55 to 6.70 according to weather condition, COP of Cooling: 3.83tc 5.70 according to Weather Condition, Max Output Water Temp: 45°C, Power Supply: 380~415V/50Hz/3Ph, Input Power: 7.4 KW, Current: 16A, Max Input Power: 11 KW, Max Current: 23A, Evaporator Coil: Blue Finned Evaporator Coll, Throttling Valve: Thermostatic Expansion Valve / Electronic Expansion Valve, Heat Exchanger (Condenser): PVC Shell Titanium Condenser, Refrigerant: R410a/R407C, Compressor: Scroll Number of Compressor: 2, Fan Quantity: 2 nos., Fan Discharging: Vertical, Water Flow: 22-25m³/hr, Pipe Size (Inch): Rc2, Noise: ≤66 dB(A), Dimension (mm): 1450 X 890 X 1110, Weight: 320Kg, Test Condition: Ambient Temp.(DB/WB)= 24deg C./19 deg C., Inlet Water Temp. = 26 deg C., Outlet Water Temp. = 28 deg C. (Ε.Τ. 10 deg C./ C.T. 40 deg C.). Cooling condition: Inlet Water Temp. = 18 deg., Outlet Water Temp. = 16 deg. (Ε.Τ. 10 deg./C.T. 40 deg.), Reverse mode for heating & cooling - voltage protection inbuilt-GI Cabinet powder coated for rust free use - Titanium heat exchanger in PVC shell - compressor for higher cop-smart touch control panel. Microprocessor Bassed, IP55, With Sort Ckt, 10 w flow rate, overload, Earth Fault Protection. |
| 2 | SITC of Water Circulating Pump with Flow rate: 22-25 m3/hr @ Suitable Head (Actual capacity may differ as per site requirements) |
| 3 | Plumbing work as per Requirement of site, |
| 4 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) Pipes Having Thermal Stability for hot and cold water supply and all CPVCplain and brass threated fittings, including Fixing the pipe with clams at 1 m spacing. This includes Jointing of pipes and fittings with one step CPVC solvent cement and testing of joints complete as per Direction of Engineer In Charge. |
| 5 | Providing and fixing Gun Metal Gate Valve with C.I. wheel of Approved Quality (scruwed end) 50 mm nominal bore |
| 6 | Providing and fixing Gun Metal Non Return Valve with C.I. wheel of Approved Quality (sc@wed end) 50 mm nominal bore |
| 7 | Supply and errection of factoty fabricated dust and vermin proof floor mounting panel complete with following rating and breaking capacity 36 KA 01 No, 100 amp 4 Pole MCCB As Main Incommer, and 04 No, 32/40 Amp/ 25 KA 4 pole MCCB as Outgoing with thermomagnetic release and terminal spreaders digital ameter, voltmeter selector switches and suitable size Al. Busbar as per 8623 insulated with heat shrink sleeving & mounted on non hygroscopic support in cubicle panel board Including drilling holes in cubicle panel, making connections, etc. as required. The Job includes the grouting of the board as per direction of engineer in charge. the switch board shall be fabricated with CRCA sheet with a minimum thick ness 1.6 mm/2 mm cubical type switch board. Main Panel Switch Gear. |
| 8 | Supply Installation Testing nad Commissioning of 100 Amp, 36 ΚΑ Breaking Capacity, 4 Pole MCCB, With thermal magnetic release in the Existing Main Panel, to Supply the power to the Distribution Panel for Heat pump System For Sweaming Pool. |
| 9 | Supplying, Laying, testing and commissioning of 3.5 core 70 sq.mm, Aluminium Conductor, XLPE insulated, PVC sheathed, steel armoured, Cable 1.1 kV grade, FRLS compliant LT power cable conforming to IS 7098 (Part- 1), including drawing and laying the cable in the existing masonry-protected DWC/HDPE pipe network, ensuring uniform pulling, proper bend radius, mechanical protection of armour, Identification tagging, continuity verification, Insulation resistance testing, and completing the work as per IE Rules, site engineering practice and standard specifications, all complete.3.5 Core 70 Sq mm XLPE AI Armoured Cable |
| 10 | Supplying, Laying, Testing and Commissioning of 4 core x 10 sq.mm Aluminium Conductor, XLPE insulated, PVC sheathed, steel armoured Cable 1.1 kV grade, FRLS compliant LT power cable conforming to IS 7098 (Part-1), including drawing and laying the cable in the existing masonry-protected DWC/HDPE pipe network, ensuring uniform pulling, proper bend radius, mechanical protection of armour, identification tagging, continuity verification, insulation resistance testing, and completing the work as per IE Rules, site engineering practice and standard specifications, all complete 4 Core 10 Sq mm XLPE Al Armoured Cable |
| 11 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC Insulated and PVC sheathed/XLPE S aluminium conductor cable of 1.1 KV grade as required.3.5 X 70 sq. mm (38mm) |
| 12 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE 9 aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq. mm (22mm) |
| 13 | Supplying and laying of following size DV/C HDPE pipe ISI marked along w all accessories like socket, bend, couplers etc. conforming to IS 14930, Pam II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) Including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 14 | Earthing Work:- Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick Including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 15 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.. |
| 16 | Providing and laying cement concrete foundation of size 1600 mm x 1040 mm x 700 mm (volume 1.1648 Cum), in cement concrete mix 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate), including excavation i all kinds of soil, dressing and leveling of bed, ramming, providing and layim cement concrete with proper mixing, placing, compaction, finishing and curing, including cost of all materials, labour, T&P, dewatering if required, and disposal of surplus excavated earth within lead and lift as per direction of Engineer-in-Charge, complete. (DSR 2023 Item 2.1.1+4.1.3) |
| 17 | Supply and Installation of tin shade for 3 no. Heat pump unit Size L-20 feet width= 6 feet, height - 9 Feet Including Suitable size MS Pipe and Angle Iron 0.80mm thickness colour coated metal sheet including fabrication and Labour charges and cement concrete plinth for grouting of MS pipe and fixing of netting around shade and suitable sizę gate etc. complete in all respect. Please Enable Macros to View BoQ information |