| 1 | Disconnecting, dismantling and taking out old U/S XLPE LT cable , 240 Sqmm to 10 Sqmm any Core carefully all as specified and directed. |
| 2 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 3½ core 240 sq mm. |
| 3 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 3½ core 150 sq mm. |
| 4 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 3½ core 120 sq mm. |
| 5 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 3½ core 95 sq mm. |
| 6 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 3½ core 70 sq mm. |
| 7 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 3½ core 35 sq mm. |
| 8 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 4 core 25 sq mm. |
| 9 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 4 core 16 sq mm. |
| 10 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 4 core 10 sq mm. |
| 11 | Supply laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip or wire armored,electric power cables (heavy duty ) with stranded aluminum conductor, 1100 volts grade,of size 2 core 10 sq mm. |
| 12 | Supplying, laying & jointing GI water tubing, 100 mm bore,Light grade as in sleeving etc laid in trenches / ducts / horizontal bore hole complete all as specified and directed. |
| 13 | Supplying, laying & jointing GI water tubing, 80 mm bore,Light grade as in sleeving etc laid in trenches / ducts / horizontal bore hole complete all as specified and directed. |
| 14 | Supplying, laying & jointing GI water tubing, 40 mm bore,Light grade as in sleeving etc laid in trenches / ducts / horizontal bore hole complete all as specified and directed. |
| 15 | Supply, instal, testing and commission of LT Panel outdoor type IP-54 protection as per IS-2147 CPRI Approved suitable for AC supply 3 phase 4 wire, 415 V, 50 Hz having dust and vermin proof MS sheet with suitable appropriate size complete painting , PCC etc comprising of the following accessories |
| 16 | A :- Incoming (a) MCCB 630 Amps, ICU-50 KA, 3 Pole -01 No(b) Phase indicating lamps LED type RYB including holder with 0.5 A MCB-01 set (set of three)(c) Volt meter digital type 0.500 volts with selector switch -01 No(d) Ammeter digital square type 0.0250A with selector switch and set of die cast CTs-01 No B: Bus Bar Eclectronic high conectivity aluminium bus bar of appropriate X-sectionel area -04 Nos C: Outgoing (a) MCCB - 400 Amps, ICU 36 KA, 4 Pole -01 No. (b) MCCB - 125 Amps, ICU 25 KA, 4 Pole -02 Nos (c) MCCB - 100 Amps, ICU 25 KA, 4 Pole -01 Nos (d) Isolator 40 Amp 4 Pole -01 No (e) Supply and fixing inside of panel time switches astro type (having logitude and latitude of Indian cities in memory including air break power contactor) 230 V single phase of 15 Amp rating with cotactor fitted inside steel enclosure. |
| 17 | Supply, install, testing and commission of LT Panel outdoor type IP-54 protection as per IS-2147 CPRI Approved suitable for AC supply 3 phase 4 wire, 415 V, 50 Hz having dust and vermin proof MS sheet with suitable appropriate size complete painting , PCC etc comprising of the following accessories :- |
| 18 | A :- Incoming (a) MCCB 350 Amps, ICU-50 KA, 3 Pole -01 No(b) Phase indicating lamps LED type RYB including holder with 0.5 A MCB-01 set (set of three)(c) Volt meter digital type 0.500 volts with selector switch -01 No (d) Ammeter digital square type 0.0250A with selector switch and set of die cast CTs-01 No B: Bus Bar Eclectronic high conectivity aluminium bus bar of appropriate X-sectionel area -04 Nos C: Outgoing (a) MCCB - 150 Amps, ICU 25 KA, 4 Pole -01 No. (b) MCCB -100 Amps, ICU 25 KA, 4 Pole -01 Nos(c) MCCB - 63 Amps, ICU 16 KA, 4 Pole -02 Nos |
| 19 | S&F LT Feeder Pillar boxes and Supply, Installation, factory made LT Feeder Pillar Box of Size 60CMx45CMx30CM for 3 Phase, 4 Wire, 415 Volts, AC, 50 Hz, Outdoor, Cubical Type, Weather, Dust and Vermin proof, Pedestal mounting type, front operated applications having size of Aluminium bus bar rating capacity 200 Amps and neutral 100 Amps rating capacity mounting of insulators, canopy on top and gland provision in the bottom made out of 3.15 mm thick MS sheet duly powder coated of approved shade with using 40mmX40mmX6 mm angle iron frame and supports including necessary excavation and grouting work in PCC 1:2:4 Mix, Type B1 complete all as specified and directed. |
| 20 | M&L for PCC (1:4:8) Type D-2 using 40mm graded stone aggregate as in foundation/repairs to damaged road/footpath/plinth for panels etc. including necessary formwork complete all as specified. |
| 21 | M&L for PCC (1:2:4) Type B-1 using 20mm graded stone aggregate as in repair to footpath/hard standing/plinth for panels etc. including necessary formwork complete all as specified. |
| 22 | Supplying and fixing in position new PVC (Synthetic) boxes of size 280mm X 170mm X 115mm depth, made out with Sinthetic. The box shall be provided with and including 10 cm long aluminium bus bar of size 20x3 mm size 2 Nos mounted on porcelain insulators including one No. MCB SP of ‘C’ series, 5/6 Amps of Make Legrand/L&T/ Siemens and connecting the bus bars to cables with using suitable GI nut, bolts and washers and aluminum lugs etc fixed on pole using 30x5 mm GI clamps, nuts, bolts & washers etc complete all as specified and directed. |
| 23 | M&L Boring of holes under road, pavement, hard standing by trenchless technology using Manual boaring technique and necessary machine including HDPE pipe of 100 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. |
| 24 | Demolition for cement concrete/road in ground floor and paving n. exc 15 cm thickness below or above ground level including removal of rubbish to a distance exc 50 mtr etc complete all as specified |
| 25 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth strip 32x6 mm (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit , internal surface of concrete shall be given 10mm thick plaster in CM 1:4 and 40 mm thick precast RCC cover 1 : 2 : 4 ,type B-1( using 20 mm graded crushed stone aggregare ) reinforced with 8 mm dia TMT bars @ 75 mm c/c both ways with 12mm dia round bar as in handle including taking down of existing earthing complete all as specified & directed. |
| 26 | Excavation in trenches in soft/loose soil n. exc 1.5 Mtr wide and not exc. 1.5 M deep and getting out including forming bottom surface for laying of pipes complete all as specified and directed. |
| 27 | Returning filling in including spreading, leveling, watering and well ramming in layers not exc 25 mm thick complete all as specified and directed. |
| 28 | Removal of excavated material to a distance not exc 50 Meter and depositing where directed at a level not exc 1.5 M above the starting point complete all as specified and directed. |
| 29 | Supplying, laying and cushioning for cable protection in trenches 8 cm deep before laying cable and 15 cm deep over the cable including well punning complete all as specified and dierected |
| 30 | Supplying, laying sub class 'B' bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection complete all as specified and directed. |
| 31 | Notes :-The amount or Schedule 'A' Part-ll shall be deducted from total quoted amount of BOQ to arrive at the contract sum Please Enable Macros to View BoQ information |