| 1 | Transporting one HT TW /RSJ/Rail pole by hand cart- normally limited to 4km (excluding loading and unloading) |
| 2 | Providing one Earth using earth pipeof size 38.1mm dia 2.5m length including digging separate pit (0.45 x 0.45 x 2.5 m)at a minimum distance of 1.5 m away from the pole/structure and maintaining standard distance between different earth pipes in ordinary soil and backfilling |
| 3 | Fitting one Additional 2.4m/3m Channel cross arm (100x50x6mm), in existing 11KV DP incl. conveyance of materials. |
| 4 | Transporting poles by hired vehicle to a distance up to 5km and carrying up to 4 poles excluding loading & unloading |
| 5 | Drilling holes of various sizes on existing Channel/cross arm |
| 6 | Conveyance of one km 11 kV line materials from section store /stacking place to the work site (excluding poles) |
| 7 | Fitting one Additional 75x40mm, 1.8m channel cross arm in existing single pole incl. conveyance of materials |
| 8 | Additional rate for excavation of one pit for A type pole in laterite |
| 9 | Labour charges for loading HT A type pole from the stacking place and unloading the same at work site (transport by vehicle). |
| 10 | Fitting and erecting one HT DP using PSC pole in position incl. fitting 2 channel cross arms, digging & back filling pit in ordinary soil, drawing sufficient length of GI earthing leads through all cross arms to ground for earthing (excluding provision of earthing) |
| 11 | Fitting one additional V cross arm in existing single pole including conveyance of materials |
| 12 | Labour charges for loading HT PSC pole from the stacking place and unloading the same at work site (transport by vehicle). |
| 13 | Fitting and providing one HT stay for 11KV pole incl. digging and back filling pit in ordinary soil |
| 14 | Providing one Coil Earth using No8 GI earth wire (50 mm dia,115 turns) including digging separate pit (0.45x0.45x1.5m) at standard distance away from the pole/structure in ordinary soil & backfilling |
| 15 | Fitting one set AB switch on existing DP giving connection and drawing sufficient length of GI earthing leads to the ground for earthing excluding provision of earthing |
| 16 | Stringing of one km 11 kV line with ACSR Racoon (3 conductors) after fitting insulators and giving jumper connections including cutting and removing tree branches wherever necessary excluding cut point works |
| 17 | Additional rate for refitting/redoing one shackle set including re shackling one span while renewing any type of LT pole |
| 18 | Fitting and providing one strut using HT PSC pole incl. digging and back filling pit in ordinary soil |
| 19 | Disconnecting and lowering down the Single phase WP service connection with guy wire from the OH line and reconnecting the same after completing the line work |
| 20 | Disconnecting and lowering down the three phase WP service connection with guy wire from the OH line and reconnecting the same after completing the line work |
| 21 | Additional rate for excavation of one pit for HT pole/HT stay in laterite |
| 22 | Additional rate for excavation of one pit for A type pole in hard laterite |
| 23 | Transferring LT single phase 2/3 wire OH line to newly erected HT/LT pole including dismantling existing cross arm and insulators refitting the same on the new pole,binding etc complete |
| 24 | Transferring LT 3 ph 4/5 wire OH line to newly erected HT/LT pole including dismantling existing cross arm and insulators refitting the same on the new pole,binding etc complete |
| 25 | Dismantling (without damage) LT stay including digging pit in all classes of soil and backfilling |
| 26 | Additional rate for providing one disc set,PG clamp etc complete on any type of HT pole for making cut point |
| 27 | Fitting and erecting one HT PSC single pole in position incl. fitting cross arm, digging & back filling pit in ordinary soil(as per standards) , drawing sufficient length of GI earthing leads from F clamp through V cross arm to ground for earthing (excluding provision of earthing) |
| 28 | Fitting and erecting one HT A type single pole in position incl. fitting cross arm,digging & back filling pit in ordinary soil(as per standards) , drawing sufficient length of GI earthing leads from F clamp through V cross arm to ground for earthing (excluding provision for earthing) |
| 29 | Fitting and providing one HT Fly stay for 11KV Pole using HT PSC pole incl. digging and back filling pit in ordinary soil drawing sufficient length of GI earth leads to the ground for earthing (excluding provision for earthing) |
| 30 | Object marking (traffic signal painting) in one HT,LT,HT/LT pole for a height of 1.5m from groundlevel using approved quality primer one coat and two coats anti algal black and fluroscent white paint in alternate rings of 25 cm width including cost of paints |
| 31 | Pole numbering using printed Aluminium sheets of 22 SWG having size 20x12 cm or Painting the surface of line supports where numbers are to be inscribed .Pole numbers shall be painted in circular/rectangular background using approved quality anti algal yellow paint in two coat after scrapping and cleaning the surface at a height of 2.5m above ground level.The number and letters should be in black synthetic enamel paint.The size of the number should be atleast 2 cm in height x 1.5 cm in width including cost of paint |
| 32 | Providing concrete muffing of size (0.45x0.45x1.5m) ( 0.5m above GL and 1m below GL).Excavation 0.45x0.45x1m concrete (1:3:6 20mm) 0.45x0.45x1.5m.Plastering (1:3) 12mm 0.45mx0.45mx 5 sides |
| 33 | Dismantling ( without damage ) one LT PSC/RCC pole after disconnecting stays, strut etc.attached thereon and stacking the same |
| 34 | Dismantling one damaged one LT PSC/RCC pole after disconnecting stays, strut etc.attached thereon and stacking the sameand stacking the same Please Enable Macros to View BoQ information |