| 1 | Providing and fixing of insulated robber matting suitable for 11 KV installation 1 M x 2 M x 12 mm thick (IS code 15652-40091) as per specification complete and as per directions of Engineer-in-charge |
| 2 | G.O.SWITCHSupply, erection, testing & commissioning of G.O. Switch two poles, with blade, pin 6 insulators operating handle with GI pipe 25 mm class B complete in all respects |
| 3 | Supply and erection of MS cable tray , duly pained as required including erection of the same on wall or ceiling with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the workMS perforated cable tray painted with powder coating 200 X 50 X 2 mm3. |
| 4 | Supply and erection of High Tension Voltage caution notice plate of size 250*200 mm in three languages. |
| 5 | Supply and erection of shock restoration chart in glass frame. |
| 6 | Supply & Erection of mild steel bucket stand suitable for 6 Nos. fire buckets,(but without bucket) including the cost of welding and painting of complete stand will one coat of red oxide and 2 coats of approved paint of red colour with all labour and material required to complete the job in all respect up to the entire satisfaction engineer in charge of the work (size 6'x4' made of GI pipe 32mm dia). |
| 7 | Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required. |
| 8 | Earthing with tinned copper earth plate 600mmx600mmx3mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) etc. complete as required. |
| 9 | Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode. |
| 10 | Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required. |
| 11 | Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. |
| 12 | Providing and fixing 25 mm x5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required. |
| 13 | Providing and fixing 25 mm x 5mm copper strip on surface or in recess for connections etc. as required with all labour and material. |
| 14 | Supply and erection of suitable compression type brass cable glands for underground Cable :-120 sqmm to 185 sqmm Cable 3 to 3½ Core |
| 15 | Supply and erection of aluminium lugs heavy duty including crimping etc. upto the entire satisfaction of the Engineer-in-charge of the work.50 sqmm |
| 16 | 70 sqmm |
| 17 | 150 sqmm |
| 18 | 300 sqmm |
| 19 | Supply and erection of cable route marker made of 50 cm long 10 mm dia M.S. Rod welded/revitted at the top with 10 cm dia 3 mm thick MS plate inscribed with 'cable' word on it, having a cross arm 30 cm long of the same dia welded at the bottom, in exiting trench 45 cm below ground level. |
| 20 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 150 to 185 sqmm |
| 21 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 150 to 185 sqmm |
| 22 | S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Mtr below ground level including diging and refilling of earth including cost of suitable size socket/cuppler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work.DWC/HDPE pipe 145/123 mm outer dia/ inner dia |
| 23 | RCC FOUNDATIONS FOR DG SET Providing RCC foundation of M20 grade (1 Cement:1.5 Stone aggregate: 3 Coarse sand) i/c excavation, steel reinforcement (Fe 500) @ 50 kg/cum of concrete contents, concrete cover 50mm, over a bed of 75mm thick PCC 1:5:10, of required dimensions as per OEM recommendations as per following specifications for 250 KVA DG set to provide levelled surface for placement of the DG set complete in all respects and as per directions of Engineer-in charge. Note: As size and dynamic load of DG sets vary from manufacturer to manufacturer, item of DG set foundation have been included on the basis of cubic contents of RCC. 250 KVA DG Set (For panel, RMU etc.) |
| 24 | 750 KVA DG Set (For substation) |
| 25 | Providing & erection/ laying of PVC/ XLPE insulated underground aluminium conductor underground cable loose in existing pipe or trenches complete in all respect with necessary connection upto the entire satisfaction of engineer in charge of the work. 150 Sq mm 3.5 core (Arm.) |
| 26 | 300 Sq mm 3.5 core (Arm.) |
| 27 | Providing & erection/ laying of PVC/ XLPE insulated underground aluminium conductor underground cable on surface/ existing cable tray complete in all respect with necessary connection upto the entire satisfaction of engineer in charge of the work 50 Sq mm 3.5core (Arm.) |
| 28 | 70 Sq mm 3.5 core (Arm.) |
| 29 | 150 Sq mm 3.5 core (Arm.) |
| 30 | 300 Sq mm 3.5 core (Arm.) |
| 31 | Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in 1 per meter below ground level with sand and bricks with alllabourandmaterial including digging and refilling of trench as required to complete the job in all respect upto the entire satisfaction of the Engineer-In- Charge of the works. 185 Sq mm 3 core |
| 32 | Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in Existing Pipe/Trenches /Surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In-Charge of the works. 185 Sq mm 3 core |
| 33 | Supply, Erection, testing and commissioning of Transformer-800 KVA 11/0.433 K. V.3 Phase-50 cycles copper wound outdoor type as per latest IS specification efficency level 3 confirming to IS 1180 and IS 2026 with losses at 50% load 2015W (maximum), 100% load 5323 W (maximum) along with petty works required up to the entire satisfaction of the Engineer-in-charge of work as per detailed specification given as under: No. load voltage ratio 11/0.433 K V. No. of Phase = 3 Frequency cycles = 50HZType- double wound core type copper wound Cooling = ONANDuty = Outdoor Vector group/ISS-DYN 11 Tapping on HV Compensation +5.0% To - 10% in steps of 2.50% each.Temperature rise (oil/Res = 0C) 40/45 C Attitude= upto 1000metres above M.S.L. Fitting/Accessories Provided. Bucholez relay with alarm and trip contact. OFF LOAD TAP CHANGER Externally hand operated.Oil conservator with Filling hole & cap. Plain oil level guage with minimum Level marking. other specifications as per DNIT in PDF. |
| 34 | Supply, installation, testing and commissioning of HT panel 1 way RMU type V+M outdoor type Make ABB/Siemens/ Schneider complete upto the entire satisfaction of the Engineer - in - Charge as per specification as under : with standard protection devices VACCUM CIRCUIT BREAKER other specifications as per DNIT in PDF. |
| 35 | Designing, fabricating, transporting, unloading, storing, fixing in position, testing and commissioning the following outdoor type panel fabricated from 2.0mm thick CRCA sheet, dead-front construction, dust and vermin proof, indoor type TPN Panels with hinged lockable doors fabricated from 2mm thick CRCA sheet, suitable for 415V, 3 phase 4 wire 50Hz AC supply with separate cable alley and lockable bus-bar chamber including supplying and fixing following switchgears and accessories, inter-connections, bonding to earth, powder coated painting as per following specifications :- other specifications as per DNIT in PDF. |
| 36 | Supply, installation, testing & commissioning of outdoor type APFC panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel with IP 54 (outdoor type). 280 KVAR CAPACITOR PANEL INCOMER 630A TP MCCB (50KA) with thermal magnetic base for O/L, S/C & E/F protection = 1 no. make LK / Siemens / Schneider Extended Rotating Handle & Spreader = 1 no. make LK / Siemens / Schneider METERING & INDICATION : other specifications as per DNIT in PDF. |
| 37 | Supply and erection of stay set with stay wire suitable for 11M long PCC pole made out of 7/3 SWG GI wire with U type M.S. Rod 5/8\\" dia duly threaded by means of angle iron of size 50 x 50 x 6 mm x 30 cm 6 feet long M.S. Rod buried in ground after fixing with cross channel size 75 x 40 x 6 mm x 60 cm long the stay wire will be binded on the top of the pole with help of suitable size of double U type M.S. Clamps and stay fixed with nuts and bolts the stay wire shall be insulated in the middle point with the help of egg insulator including all labour and material required to complete the job in all respect to the entire satisfaction of Engineer-in-charge of work. |
| 38 | S/E of M.S. chanel, MS angle, MS flat & nuts & bolts of required size including painting and cutting etc. with labour and material required to complete the job including fixing the same on existing pole complete in all respect (Make and specification as per UHBVNL/DHBVNL) |
| 39 | Supply & erection of fire extinguisher ISI marked Co 2 type 4.5 Kg. Capacity as Per ISI 7285 duly erected on wall with hook including the cost of hook, screw etc. with all the labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer In charge of the work. Make: Ajay, Zenith, Minimax. |
| 40 | Supply & Erection of fire buckets of 9 ltr. capacity made out of 24guage G.l sheet and duly painted with one coat of red oxide and 2 coats of approved paint in red colour and written with the fire' as per fire protection necessar sand filling in the bucket hung the bucket on stand with all labour and material required to complete the job all respect up to entire \satisfaction of the Engineer in charge of the work |
| 41 | Supply & erection of lighting arrestor model ALPRO / Alastem / LEMCO make suitable for 11KV 3 Phase 50 HZ ground neutral system comprising of spare gape type queen gap type in series with non linger resitar element house in Horizontally scale poreclam bushing with line and ground terminal along with mounting clamps conforming to ISS 3070 (Part-I) of 1985 with latest amendment with all labour and material required to the complete in all respect up to entire satisfaction of the Engineer-in-Charge of the works. |
| 42 | Supply & erection, Commissioning and testing of 11 KV indoor HT metering panel complete with Ct's PT's cubical & electronics meter with accuracy class 0.5. as par requirement / approved by DHBVN consisting of the followings : Cubical panel box standing floor mounting type made out of sheet steel 14 SWG CRCA sheet with channel iron base frame, spray painted with strong synthetic light grey enemal paint as per size and design approved by DHBVN. other specifications as per DNIT in PDF. |
| 43 | Supply & installation of MS shade of dimensions 15 (L) x 12 (W) x 12 (H) feet to be covered by 2 mm thick metero sheet (Approx. area to be covered 220 sq. feet) including 5 mm MS parking jali having approximate area of 700 sq.ft. Metro sheet to be supported by MS pipe of dimension (50x75x3 mm) having approximate length of 240 feet and MS angle of size 60x 6 mm) having approximate length of 200 feet complete upto the entire satisfaction of the Engineer - in - Charge as per specification. Please Enable Macros to View BoQ information |