| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : GE 881 EWS C/O 56 APO NAME OF WORK: SPL REPAIR TO OH TO UG CABLE ALONGWITH ALLIED WORK (8 FD) AND SPL REPAIR TO LT PANEL AND CONNECTED WORKS AT POONCH UNDER GE 881 EWS. Contract No : GE/PNH-121/2025-26 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Rates only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sch. itemNo. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Rs. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Excavation in trenches not exc. 1.5 mtr wide and not exc. 1.5 mtr in depth for foundation of poles, stay assambly etc. and getting out in any type of soil complete all as specified and directed. |
| 3 | Excavation in trenches not exc. 1.5 mtr wide and exc 1.5 mtr in depth for foundation of poles, stay assambly etc. and getting out in any type of soil complete all as specified and directed. |
| 4 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm, in any type of soil, complete all as specified and directed. |
| 5 | Removing surplus excavated material (soil) not exceeding 50 mtr and depositing where directed at a level not exceeding 1.50 mtr above the starting point, all as specified and directed. |
| 6 | DWC HDPE pipe for protection of power cable (orange in colour) of size 80 mm dia complete with fittings and including cutting , jointing and clamping all as specified and directed . |
| 7 | DWC HDPE pipe for protection of power cable (orange in colour) of size 50 mm dia complete with fittings and including cutting , jointing and clamping all as specified and directed . |
| 8 | Supply, install and errect in true vertical position steel tubular swaged welded pole, 9.0 meter long, conforming to IS-2713 part-II, type 410 SP-31, complete with cast iron/MS base plate 6mm thick and of size 300x300mm, finial taper, pole cap, bolts, nuts, washers & screws etc., pole made out of ERW M.S. tubing including holes of required Nos and size for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embedded in concrete, painting three signal red colour bands at lower portion of exposed pole starting from plinth block , each band of 300mm height at 300mm spacing, marking pole No. with black paint by stenciled letters/figures of 8cm height including taking down old unserviceable PCC pole and removing away complete all as specified and directed by Engr-in-charge. Note: Excavation, earth work and PCC in foundation of poles, coping etc shall be measured and paid separately in respective items. |
| 9 | GI bracket of 40mm bore light grade pipe of length 2mtr, bent to shape and welded including 02 Nos of clamp of MS flat iron of size 50x6mm, nut & bolts etc complete all as specified and directed. |
| 10 | Factory made PVC pole mounted street light junction box, three phase and neutral, 415 volts, weather proof of size 325x220x150mm depth, accomodated with properly insulated 04 Nos of aluminium busbar of 40 Amps rated current cap, 02Nos of insulator as per each busbar, nut bolts & clamps of MS flat iron of size25x3mm for fixing of junction box etc. and including MCB SPN 6 Amps-01 Nos for connecting of security light fittings, with hinged door and locking bolt complete all as specified and directed. |
| 11 | LED street light fitting 70 Watt 230 V AC out door type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 12 | PVC insulated PVC sheathed multi core flexible cable copper conductor 1100 volts grade conforming to IS-694/2010 of size 1.5 sqmm 3 core including 25mm PVC conduit from junction box to light fittings connecting up complete all as specified and directed by Engineer-in-charge. |
| 13 | Supply, laying, jointing and testing LT XLPE PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sqmm 3.5-core, including taking down old unserviceable cable complete all as specified and directed. |
| 14 | Supply, laying, jointing and testing LT XLPE PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95 sqmm 3.5-core, including taking down old unserviceable cable complete all as specified and directed. |
| 15 | Supply, laying, jointing and testing LT XLPE PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sqmm 3.5-core, including taking down old unserviceable cable complete all as specified and directed. |
| 16 | Supply, laying, jointing and testing LT XLPE PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sqmm 3.5-core, including taking down old unserviceable cable complete all as specified and directed. |
| 17 | Supply, laying, jointing and testing LT XLPE PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sqmm 4 core, including taking down old unserviceable cable complete all as specified and directed. |
| 18 | Supply, laying, jointing and testing LT XLPE PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sqmm 2 core, including taking down old unserviceable cable complete all as specified and directed. |
| 19 | Supply, laying, jointing and testing LT XLPE PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sqmm 2 core, including taking down old unserviceable cable complete all as specified and directed. |
| 20 | Earthing complete with galvanized steel earth plate electrode 600x 600x6.3mm thick buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level, including alternate layers of common salt and charcoalconnected to galvanized iron earth lead strip 32x6mm by means of bolts, nuts and washers of galvanized iron or steel, protected by GI light grade pipe 40mm bore including GI medium grade water pipe 20mm dia with funnel all as shown in electric plate No. 3 of 2009 SSR Pt-I and testing complete including earth work in any type of soil, PCC 1:2:4 type B-1 as in earthing pit and cover 50mm thick reinforced with 6mm dia MS round bar @ 10cm C/C both way and MS frame and testing on completion including taking down old unsv earthing, complete all as specified and directed. |
| 21 | Supplying, installing, testing and commissioning LT outdoor type panel board factory fabricated cubical kiosk type whether proof, dust & vermin proof, CPRI approved with locking arrangement and made out of powder coated CRCA sheet of 3.15 mm thick & angle iron frame of size 40 x 40 x 6 mm and suitable size of channel for base complete with 400 Amps rated Aluminium bus bar and separate cabinet for housing & mounting for each MCCBs, starter, change over, metering eqpt etc. and prewired with suitable size of copper conductor, cable glands etc. including mounted on PCC (1:4:8) type D-2 plateform 600mm high above GL with suitable width and length and including connecting up complete with the following:- Incoming :- (a) MCCB 250 Amps Cap 35 KA, 4 pole - 01 No Outgoing :- (b) MCCB 100 Amps Cap 25 KA 4 pole - 01 Nos (c) MCCB 63 Amps Cap 16 KA 4 pole - 5 Nos (d) MCB 40 Amps Cap 10 KA 4 pole - 02 Nos (e) MCB 40 Amps Cap 10 KA 2 pole - 02 Nos (f) Digital type Ammeter flush pattern type square dial 96 X 96 mm along with selector switch 01 No. and suitable CT ratio. (g) Digital type Volt meter flush pattern type square dial 96 X 96 mm along with selector switch & LED indicator - 01 No. (h) Digital timer switch for street light along with suitable contactor, relay, MCB, selector switch incl bypass arrangemets suitable for 0 to 40 Amps. |
| 22 | Supplying, installing, testing and commissioning LT outdoor type panel board factory fabricated cubical kiosk type whether, dust & vermin proof, CPRI approved with locking arrangement and made out of powder coated CRCA sheet of 3.15 mm thick & angle iron frame of size 40 x 40 x 6 mm and suitable size of channel for base complete with 300 Amps rated Aluminium bus bar and separate cabinet for housing mounting for each MCCBs, starter, change over, metering eqpt etc. and prewired with suitable size of copper conductor, cable glands etc. including mounted on PCC (1:4:8) type D-2 plateform 600mm high above GL with suitable width and length and including connecting up complete with the following:- Incoming :- (a) MCCB 160 Amps Cap 35 KA, 4 pole - 01 No Outgoing :- (b) MCCB 63 Amps Cap 16 KA 4 pole - 04 Nos (c) MCCB 40 Amps Cap 10 KA 4 pole - 02 Nos (d) MCB 40 Amps Cap 10 KA 2 pole - 04 Nos (e) Digital type Ammeter flush pattern type square dial 96 X 96 mm along with selector switch 01 No. and suitable CT ratio. (f) Digital type Volt meter flush pattern type square dial 96 X 96 mm along with selector switch & LED indicator - 01 No. |
| 23 | Supplying, installing, testing and commissioning LT outdoor type panel board factory fabricated cubical kiosk type whether, dust & vermin proof, CPRI approved with locking arrangement and made out of powder coated CRCA sheet of 3.15 mm thick & angle iron frame of size 40 x 40 x 6 mm and suitable size of channel for base complete with 300 Amps rated Aluminium bus bar and separate cabinet for housing mounting for each MCCBs, starter, change over, metering eqpt etc. and prewired with suitable size of copper conductor, cable glands etc. including mounted on PCC (1:4:8) type D-2 plateform 600mm high above GL with suitable width and length and including connecting up complete with the following:- Incoming :- (a) MCCB 160 Amps Cap 35 KA, 4 pole - 01 No Outgoing :- (b) MCCB 63 Amps Cap 16 KA 4 pole - 04 Nos (c) MCCB 40 Amps Cap 10 KA 4 pole - 02 Nos (d) MCB 40 Amps Cap 10 KA 2 pole - 02 Nos (e) Digital type Ammeter flush pattern type square dial 96 X 96 mm along with selector switch 01 No. and suitable CT ratio. (f) Digital type Volt meter flush pattern type square dial 96 X 96 mm along with selector switch & LED indicator - 01 No. |
| 24 | PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete complete all as specified and directed. |
| 25 | PCC 1:4:8 Type D-2 using 40 mm graded stone aggregate for mass filling in foundation of steel tubular poles including necessary form work and finishing the exposed surface even and smooth without using extra cement complete all as specified and directed. |
| 26 | PCC 1:2:4 Type B-1 using 20 mm graded stone aggregate for coping of steel tubular poles including necessary formwork and finishing the exposed surface even and smooth without using extra cement complete all as specified and directed. |
| 27 | DWC HDPE pipe for protection of power cable (orage in colour) of size 40 mm dia complete with fittings and including cutting , jointing and clamping all as specified and directed . |
| 28 | Supply, laying, jointing and testing LT XLPE PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 sqmm 3.5-core, including taking down old unserviceable cable complete all as specified and directed. |
| 29 | Supplying, installing, testing and commissioning LT outdoor type panel board factory fabricated cubical kiosk type whether, dust & vermin proof, CPRI approved with locking arrangement and made out of powder coated CRCA sheet of 3.15 mm thick & angle iron frame of size 40 x 40 x 6 mm and suitable size of channel for base complete with 400 Amps rated Aluminium bus bar and separate cabinet for housing mounting for each MCCBs, starter, change over, metering eqpt etc. and prewired with suitable size of copper conductor, cable glands etc. including mounted on PCC (1:4:8) type D-2 plateform 600mm high above GL with suitable width and length and including connecting up complete with the following:- Incoming:- (a) MCCB 250 Amps Cap 35 KA, 4 pole - 01 No Outgoing:- (b) MCCB 160 Amps Cap 25 KA 4 pole - 01 Nos (c) MCCB 100 Amps Cap 25 KA 4 pole - 02 Nos (d) MCB 63 Amps Cap 16 KA 4 pole - 01 Nos (e) MCB 40 Amps Cap 10 KA 2 pole - 06 Nos (f) Digital type Ammeter flush pattern type square dial 96 X 96 mm along with selector switch 01 No. and suitable CT ratio. (g) Digital type Volt meter flush pattern type square dial 96 X 96 mm along with selector switch & LED indicator - 01 No. (h) Digital timer switch for street light along with suitable contactor, relay, MCB, selector switch incl bypass arrangemets suitable for 0 to 40 Amps |
| 30 | Supplying, installing, testing and commissioning LT outdoor type panel board factory fabricated cubical kiosk type whether, dust & vermin proof, CPRI approved with locking arrangement and made out of powder coated CRCA sheet of 3.15 mm thick & angle iron frame of size 40 x 40 x 6 mm and suitable size of channel for base complete with 300 Amps rated Aluminium bus bar and separate cabinet for housing mounting for each MCCBs, starter, change over, metering eqpt etc. and pre wired with suitable size of copper conductor, cable glands etc.including mounted on PCC (1:4:8) type D-2 plateform 600mm high above GL with suitable width and length and including connecting up complete with the following:- Incoming:- (a) MCCB 200 Amps Cap 35 KA, 4 pole - 01 No (b) On load change over 200 Amps, 4 pole-01 No Outgoing:- (a) MCCB 160 Amps Cap 25 KA 4 pole - 01 Nos (b) MCCB 100 Amps Cap 25 KA 4 pole - 01 Nos (c) MCCB 63 Amps Cap 16 KA 4 pole - 01 Nos (d) MCB 40 Amps Cap 10 KA 2 pole - 02 Nos (e) Digital type Ammeter flush pattern type square dial 96 X 96 mm along with selector switch 01 No. and suitable CT ratio. (f) Digital type Volt meter flush pattern type square dial 96 X 96 mm along with selector switch & LED indicator - 01 No. (g) Digital timer switch for street light along with suitable contactor, relay, MCB, selector switch incl bypass arrangemets suitable for 0 to 40 Amps |
| 31 | Supplying, installing, testing and commissioning LT outdoor type panel board factory fabricated cubical kiosk type whether, dust & vermin proof, CPRI approved with locking arrangement and made out of powder coated CRCA sheet of 3.15 mm thick & angle iron frame of size 40 x 40 x 6 mm and suitable size of channel for base complete with 400 Amps rated Aluminium bus bar and separate cabinet for housing mounting for each MCCBs, starter, change over, metering eqpt etc. and pre wired with suitable size of copper conductor, cable glands etc. including mounted on PCC (1:4:8) type D-2 plateform 600mm high above GL with suitable width and length and including connecting up complete with the following:- Incoming:- (a) MCCB 250 Amps Cap 35 KA, 4 pole - 01 No (b) On load change over 250 Amps, 4 pole-01 No Outgoing:- (a) MCCB 100 Amps Cap 25 KA 4 pole - 03 Nos (b) MCCB 63 Amps Cap 25 KA 4 pole - 02 Nos (c) MCB 40 Amps Cap 10 KA 2 pole - 02 Nos (d) Digital type Ammeter flush pattern type square dial 96 X 96 mm along with selector switch 01 No. and suitable CT ratio. (e) Digital type Volt meter flush pattern type square dial 96 X 96 mm along with selector switch & LED indicator - 01 No. (f) Digital timer switch for street light along with suitable contactor, relay, MCB, selector switch incl bypass arrangemets suitable for 0 to 40 Amps |
| 32 | Supplying, installing, testing and commissioning LT outdoor type panel board factory fabricated cubical kiosk type whether, dust & vermin proof, CPRI approved with locking arrangement and made out of powder coated CRCA sheet of 3.15 mm thick & angle iron frame of size 40 x 40 x 6 mm and suitable size of channel for base complete with 400 Amps rated Aluminium bus bar and separate cabinet for housing mounting for each MCCBs, starter, change over, metering eqpt etc. and pre wired with suitable size of copper conductor, cable glands etc.including mounted on PCC (1:4:8) type D-2 plateform 600mm high above GL with suitable width and length and including connecting up complete with the following:- Incoming:- (a) MCCB 315 Amps Cap 35 KA, 4 pole - 01 No (b) On load change over 315 Amps, 4 pole-01 No Outgoing:- (a) MCCB 100 Amps Cap 25 KA 4 pole - 03 Nos (b) MCCB 63 Amps Cap 25 KA 4 pole - 02 Nos (c) MCB 40 Amps Cap 10 KA 2 pole - 02 Nos (d) Digital type Ammeter flush pattern type square dial 96 X 96 mm along with selector switch 01 No. and suitable CT ratio. (e) Digital type Volt meter flush pattern type square dial 96 X 96 mm along with selector switch & LED indicator - 01 No. (f) Digital timer switch for street light along with suitable contactor, relay, MCB, selector switch incl bypass arrangemets suitable for 0 to 40 Amps. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |