| 1 | Supply & Fixing in replacement for circuit/submain wiring along with earth wire 2 x 1.5 Sq mm + 1x 1.5 Sq mm (size) of FR PVC insulated copper conductor, single core cable in surface/recessed in existing PVC casing capping / conduit as required on site and as specified and directed by Engr-in-Charge |
| 2 | Supply & Fixing in replacement for circuit/submain wiring along with earth wire 2 x 2.5 Sq mm + 1x 2.5 Sq mm (size) of FR PVC insulated copper conductor, single core cable in surface/recessed in existing PVC casing capping / conduit as required on site and as specified and directed by Engr-in-Charge |
| 3 | Supply & Fixing in replacement for circuit/submain wiring along with earth wire 2 x 4.0 Sq mm + 1x 4.0 Sq mm (size) of FR PVC insulated copper conductor, single core cable in surface/recessed in existing PVC casing capping / conduit as required on site and as specified and directed by Engr-in-Charge |
| 4 | Supply & Fixing in replacement for circuit/submain wiring along with earth wire 2 x 6.0 Sq mm + 1x 6.0 Sq mm (size) of FR PVC insulated copper conductor, single core cable in surface/recessed in existing PVC casing capping / conduit as required on site and as specified and directed by Engr-in-Charge |
| 5 | Supply & Fixing in replacement for circuit/submain wiring along with earth wire 2 x 10 Sq mm + 1x 10 Sq mm (size) of FR PVC insulated copper conductor, single core cable in surface/recessed in existing PVC casing capping / conduit as required on site and as specified and directed by Engr-in-Charge |
| 6 | Taking down carefully aluminum / copper point wiring on Teak Wood Batten / in conduit / with conduit / in casing and capping(light /Fan / socket or power) complete with and including taking down fittings such as switches, ceiling roses, pendants, Regulators, sockets, light fittings etc complete all as specified and directed by Engineer-in-Charge. Notes:(i) The weight of aluminium scrap, copper scrap and scrap iron for schedule of credit shall be ascertain by BOO as ordered by GE.The copy of BOO duly countersinged by GE shall be enclosed with final Bill.(ii) The rate of cutting chases (as required) and making good surfaces to match with adjoining surface shall be measured and paid seperately under serial item nos. 7.00 to 9.00 of BoQ. |
| 7 | Material and labour for Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits),with 1.5 Sqmm two single core PVC insulated, multistranded, unsheathed, FRLSH copper conductor cable 1100 volt grade ISI Marked , with and including PVC casing and capping of medium grade of suitable size and run on wall / surface with all fittings (ISI Marked) with and including one single core 1.5 Sqmm FRLSH PVC insulated multi strand copper conductor cable 1100 volt grade (ISI marked ) (as in green colour) as continues earth wire connected to earth dolly etc. controlled by one switch for one light point/ fan point with and including CI/MS/ wooden sunk box of required size with and including 3mm thick plastic laminated sheet cover & as directed by Engineer- in- Charge including cutting, chases to wall making good the disturbed surfaces to match with the existing specification complete all as specified and directed by Engineer-in-Charge. Notes for serial item nos.7.00 to 9.00 : (i) switches one way 5 /6 Amp , switches one way 15 /16 Amp, socket out lets 5 /6 Amp & socket out lets 15 1/6 Amp shall be measured and paid seperately under respective items of Schedule'A' BoQ.(ii) The rate of cutting chases (as required) and making good surfaces to match with adjoining surface is included in this item and nothing shall be paid extra on this account. |
| 8 | All as per srl item No.7.00 here- in- before but for bell point complete all as specified and directed by Engineer-in-Charge. |
| 9 | All as per srl item No 7.00 of BoQ here-in-before but 2.5 Sqmm two single core PVC insulated, multistranded, unsheathed, FRLSH copper conductor cable 1100 volt grade ISI Marked with and including one single core 2.5 Sqmm FRLSH PVC insulated multi strand copper conductor cable 1100 volt grade (ISI marked ) as continues earth wire connected to earth dolly etc for 3 pin socket outlet 15 Amps with complete all as specified and directed by Engineer-in-Charge. |
| 10 | Supply and fixing Switch piano flush type 5 Amp single pole one way ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 11 | Supply & Fixing Switch socket combination 2 in 1, 3 pin, 15 Amp flush type universal 240 volt (ISI Marked )complete all as specified and directed by Engineer-in-Charge. |
| 12 | Supply & Fixing Switch socket combination 2 in 1, 3 pin, 5 Amp flush type universal 240 volt (ISI Marked ) complete all as specified and directed by Engineer-in-Charge. |
| 13 | Supply and fixing Switch Bell push, piano flush type, 5 Amp 250 Volts, AC supply,ISI marked complete all as specified and directed by Engineer-in-charge. |
| 14 | Supply and fixing Bell Multi music ISI marked complete all as specified and directed by Engineer-in-Charge |
| 15 | Supply and Fixing in replacement Decorative ultra slim linear LED 20 Watt 4 Feet Long lighting fixture with extruded aluminium heat sink,environment friendly, Energy efficient , ready to use pack with and including LED Tube complete , with inbuilt electronic driver, PCB, Connector block complete all as per manufactureres instructions with and including connecting up with theree copper flexible cable from ceiling rose to fitting including connectiong up and fixed on with and including two nos.square box of required size complete all as specified and directed by Engineer-in-charge. Notes:(a) Contractor has to furnish a replacement warranty of 02 years for LED light fittings complete including from the certifiy date of completion of CA. The product will be replaced free of cost in the following case :-(i) Manufacturing defects.(ii) Failure due to mechanical and electrical impact. (iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries. (b) All LED light must meet the provision laid down in IS - 16101, 16102 Part -I/II,16103 Part -I, 16104,16105,16106, 16108/2012 and 15885 Part -II / Section 13. (c) Scope of work shall include LED fittings walls/ceiling which includes needful T & P and required accessories etc if any, complete including making connection, testing etc complete. No extra payment is admissible on these account. |
| 16 | Supply & Fixing in replacement LED Security street light fitting 35 Watt 230 V AC outdoor type, energy saving and environment friendly light fitting with electronic gear housed with high pressure die cast aluminum housing LED street light luminaires complete with IP66 protection including all accessories complete all as specified and directed by Engineer-in-Charge. Notes:-(a) Contractor has to furnish a replacement warranty of 02 years for LED Light fittings complete including from the certifiy date of completion of CA. The product will be replaced free of cost in the following case :-(i) Manufacturing defects.(ii) Failure due to mechanical and electrical impact. (iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries. (b) All LED light must meet the provision laid down in IS - 16101, 16102 Part -I/II,16103 Part -I, 16104,16105,16106, 16108/2012 and 15885 Part -II / Section 13. (c) Scope of work shall include LED Light fittings walls/ceiling which includes needful T & P and required accessories etc if any, complete including making connection, testing etc complete. No extra payment is admissible on these account. |
| 17 | Supply & Fixing Lamp holder, PVC/Polycarbonate type with cord grip cap suitable for pendant all as specified and directed by Engr-in-Charge. |
| 18 | Supply & Fixing LED Lamp 9 W all as specified and directed by Engr-in-Charge. |
| 19 | Supply & Fixing in replacement LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp complete all as per manufacturer's instructions suitable for roof ceiling with and including connecting up with driver from ceiling rose with three core flexible copper conductor cable of suitable size complete all as specified and directed by Engineer-in-Charge. Notes:-(a) Contractor has to furnish a replacement warranty of 02 years for LED Light fittings complete including from the certifiy date of completion of CA. The product will be replaced free of cost in the following case :-(i) Manufacturing defects.(ii) Failure due to mechanical and electrical impact. (iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries. (b) All LED light must meet the provision laid down in IS - 16101, 16102 Part -I/II,16103 Part -I, 16104,16105,16106, 16108/2012 and 15885 Part -II / Section 13. (c) Scope of work shall include LED Light fittings walls/ceiling which includes needful T & P and required accessories etc if any, complete including making connection, testing etc complete. No extra payment is admissible on these account. |
| 20 | S&F in replacement LED luminaire round/squre shape 15 watts 220 V AC surface/recessed type with hight efficiency PMMA diffuser soft glare free light complete with driver, holder & LED lamp suitable for foof ceiling/surface complete all as per manufacturer's instructions suitable for roof ceiling with and including connecting up with driver from ceiling rose with three core flexible copper conductor cable of suitable size complete all as specified and directed by Engineer-in-Charge. Notes:-(a) Contractor has to furnish a replacement warranty of 02 years for LED Light fittings complete including from the certifiy date of completion of CA. The product will be replaced free of cost in the following case :-(i) Manufacturing defects.(ii) Failure due to mechanical and electrical impact. (iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries. (b) All LED light must meet the provision laid down in IS - 16101, 16102 Part -I/II,16103 Part -I, 16104,16105,16106, 16108/2012 and 15885 Part -II / Section 13. (c) Scope of work shall include LED Light fittings walls/ceiling which includes needful T & P and required accessories etc if any, complete including making connection, testing etc complete. No extra payment is admissible on these account. |
| 21 | Supply and fixing Batten fitting square profile type LED mirror light fiting 9/10 watt, 6000K, polycarbonate body and all other accessories fitting arrangements all other accessories fitting arrangements complete all as per manufacturer's instructions with and including electric connection connecting with using flexible copper wire twin core upto ceiling rose/connector complete all as specified and as directed by Engineer-in-Charge. Notes:(a) Contractor has to furnish a replacement warranty of 02 years for LED Light fittings complete including from the certifiy date of completion of CA. The product will be replaced free of cost in the following case :-(i) Manufacturing defects.(ii) Failure due to mechanical and electrical impact. (iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries. (b) All LED light must meet the provision laid down in IS - 16101, 16102 Part -I/II,16103 Part -I, 16104,16105,16106, 16108/2012 and 15885 Part -II / Section 13. (c) Scope of work shall include LED Light fittings walls/ceiling which includes needful T & P and required accessories etc if any, complete including making connection, testing etc complete. No extra payment is admissible on these account. |
| 22 | S&F in replacement LED Flood light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, Lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection all other accessories fitting arrangements all other accessories fitting arrangements complete all as per manufacturer's instructions with and including electric connection connecting with using flexible copper wire twin core upto ceiling rose/connector complete all as specified and as directed by Engineer-in-Charge. Notes:(a) Contractor has to furnish a replacement warranty of 02 years for LED Light fittings complete including from the certifiy date of completion of CA. The product will be replaced free of cost in the following case :-(i) Manufacturing defects.(ii) Failure due to mechanical and electrical impact. (iii) Drop in lumen (or lux at 1 m) below 90% of clamied values of lumen(or lux at 1 m) of the LED /Luminaries. (b) All LED light must meet the provision laid down in IS - 16101, 16102 Part -I/II,16103 Part -I, 16104,16105,16106, 16108/2012 and 15885 Part -II / Section 13. (c) Scope of work shall include LED Light fittings walls/ceiling which includes needful T & P and required accessories etc if any, complete including making connection, testing etc complete. No extra payment is admissible on these account. |
| 23 | Supply and fixing MCB SP 6 to 32 Amps, 230 volts , AC supply , rupturing capacity not less than 10KA,' C' Curve ,ISI Marked, with and including necessary attachment , thimbles etc complete all as specified and directed by Engineer-in-charge. |
| 24 | Supply and fixing MCB SPN 32 Amp , rupturing capacity not less than 10 KA 'C' curve 230 V AC, 50 Hz ,ISI Marked, with and including necessary attachment , thimbles etc. complete all as specified and directed by Engineer-in-charge. |
| 25 | Supplying and fixing MCB TPN 32Amps -63 Amps , 415 Volt AC, 'C' curve, ISI Marked, rupturing capacity not less than 10KA, with and including necessary attachment , thimbles etc complete all as specified and directed by Engineer-in-charge. |
| 26 | Supply and fixing in replacement sheet metal enclousers made out of CRCA mild steel sheet , IP-43 protection, flush mounted with metal door, powder coated DB SPN 8 way 230 V AC with 200 Amp rated copper bus bar, Double Door,08 modules, dust and vermin proof suitable for incorporation of MCBs / MCCBs/ Isolators etc.conforming to IS/IEC-61439-2:2011, BS-5484 complete all as specified and directed by Engineer-in-charge. Notes: (i)MCBs / MCCBs/ Isolators shall be measured and paid seperately under appropriate items.(ii) The rate of 200 Amps copper bus bar is included in this item and nothing shall be paid extra on this account. |
| 27 | Suply & Fixing in replacement ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 63 Amps complete ,all as specified and as directed by Engineer-n-charge.. |
| 28 | Suply & Fixing in replacement ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 160 Amps complete ,all as specified and as directed by Engineer-n-charge.. |
| 29 | Supply & Fixing in replacement Plug Top15 Amps,complete all as specified and as directed by Engineer-in-charge. |
| 30 | Supply & Fixing in replacement Plug Top 5 Amps,complete all as specified and as directed by Engineer-in-charge. |
| 31 | Supply & Fixing in replacement steped type electronic fan regulator flush type . AC, 230 volts, duly ISI marked with and including connector complete all as specified and as directed by Engineer-in-charge. |
| 32 | Supply and fixing ceiling rose surface bakelite 65mm x 50mm three terminals ISI Marked complete all as specified and directed by Engineer-in-Charge. |
| 33 | Supply & Fixing in replacement Single pole and neutral enclosure with a two pin and earth plug and socket complete with and including one MCB single pole 20 Amps , 240 volt 'C' curve , complete all as specified and as directed by Engineer-in-charge.The rate of one MCB single pole 20 Amps , 240 volt 'C' curve is included in this item and contractor shall quote his rate accordingly. Nothing shall be paid extra on this account. |
| 34 | Supply and fixing in replacement sheet metal enclousers made out of CRCA mild steel sheet , IP-43 protection, flush mounted with metal door, powder coated Vertical Type TPN, 8 Way 415 V, double door, earth bar, copper bus bar 200 Amp and neutral link, protection class IP-43 suitable for mounting MCBs / MCCBs/ Isolators, conforming to IS/IEC-61439-2:2011, BS-5484 dust and vermin proof, complete all as specified and directed by Engineer-in-charge. Notes:(i)MCBs / MCCBs/ Isolators shall be measured and paid seperately under appropriate items.(ii) The rate of 200 Amps copper bus bar is included in this item and nothing shall be paid extra on this account. |
| 35 | Supply & Fixing in re[;ace,emt MCCB 100 Amps 4 pole rupturing capacity16 kA 4 pole 415 volts fixed type complete all as specified and as directed by Engr-In- Charge |
| 36 | Taking down old unsrviceable service cable/UG cable of cross-sectional area 35 Sq mm 3.5 core and 70 Sqmm x 3.50 core including old uservicable bricks/ PCC concrete cable cover all as specified and directed by Engr-in- Charge. |
| 37 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 70 Sqmm x 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 38 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 35 Sqmm x 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 39 | Supply & Fixing in replacement casing caping 25 mm all as specified and directed by Engineer - in - Charge |
| 40 | Supply & Fixing in replacement PVC rigid conduit 25mm dia ( heavy duty ) ISI marked with valid CML No.(IS-9537-1983 for conduits and IS:3419:1976 for conduit accessories) with all new fittings and all accessories i.e pipe bend pipe hook, elbow,junction box, |
| 41 | Taking down ceiling fan of any type and size, cable ends, dimantling blades and removing fan and balde to deposit in the store yard of AGEM GE861EWS and recollect from store yard for Hanging/fixing only after repairing / reconditioned fan of any type and size and connecting up including provision of cable from ceiling rose or connector to fan complete all as specified and directed by Engineer - in - Charge . |
| 42 | Collection of unserviceable ceiling fan 1200mm/1400mm sweep 230V, AC single phase from store yard of AGEM GE861EWS and transporting to local market, cutting unserviceable winding from fan stator & rewinding the same with super enamelled copper winding wire of existing gauge size including throughly cleaning all the components, oiling greasing & replacement of rusted unserviceable screws, hanging clamps with rubber reel, canopy condensers, bush, bearing & flexible copper connection wire etc complete all as specified and directed by Engineer - in - Charge .Note : 1.The rate of Hanging clamps, canopy, condenser of appropriate capacity and flexible copper connection wire of suitable size , down rod, bearing, bush, clamps is included in this item and contractor shall quote the rate accordingly and nothing shall be paid extra on this account.2. Painting shall be measured and paid seperately under appropriate item of Schedule 'A' BoQ. |
| 43 | All as per item No 42.00 here-in-before but exhaust fan 300 mm sweep complete all as specified and directed by Engineer - in - Charge . |
| 44 | Material & Labour for Scraping down old paint of ceiling fan/Exahust fan of any size sweep complete body & blade including down rod filling the cavities with filler and making smooth surface by applying sand paper painting the ceiling/exhaust fan by means spray gun/brush with synthetic enamel while paint complete all as specified and directed by Engineer - in - Charge . |
| 45 | Material & Labour for lathe work for proper filling/fixing of bearing/bushes in the top cover of the fan by filling a layer of material after blazing & bottom cover of fan complete all as specified and directed by Engineer - in - Charge . |
| 46 | Supply and fixing in replacement Ball bearing Ser No 6201 or 6202 complete all as specified and directed by Engineer - in - Charge . |
| 47 | Supply and fixing in replacement Ball bearing Ser No 6203/6204 complete all as specified and directed by Engineer - in - Charge . |
| 48 | Supply and fixing in replacement Shackle type rubber reel,'U' clamps, bolts,split pin & washer complete all as specified and directed by Engineer - in - Charge . |
| 49 | Supply and fixing in replacement Canopy top/bottom suitable for 20 mm dia rod complete all as specified and directed. |
| 50 | Supply and fixing in replacement Down rod 300 mm long of size 20 mm dia ISI marked complete all as specified and directed. |
| 51 | Supply and fixing in replacement Fan blades suitable for 1200 mm sweep fan make & type as directed by Engr-in-Charge. |
| 52 | Supply and fixing in replacement Exhaust fan blade of 300 mm sweep complete as per sample as directed by Engr-in-Charge. |
| 53 | Supply and fixing in replacement Wall mounted fan blade of 450 mm sweep complete as per sample as directed by Engr-in-Charge. |
| 54 | Supply and fixing in replacement Exhaust fan clamps including frame and louvers with rubber bush, etc suitbale for 300 mm sweep complete as per sample as directed by Engr-in-Charge. |
| 55 | Supply and fixing in replacement of Ceiling fan motor winding of 1200 mm sweep complete as per sample of the following sizes as directed by Engr-in-Charge. |
| 56 | Supply and fixing in replacement of Exhaust fan Motor of 300 mm sweep complete as per sample of the following sizes as directed by Engr-in-Charge. |
| 57 | Supply and fixing in replacement of Exhaust fan Motor of 450 mm sweep complete as per sample of the following sizes as directed by Engr-in-Charge. |
| 58 | Taking down geyser carefully of any make and capacity 25/50ltrs, dismantling the geyser for inspection, cleaning of tank, repalcement of defective part such as heating element, thermostat switch, spacer ring, safety plug, glass wool, neon lamp, head assembly, rubber gasket, top and bottom cover, inspection plate, copper cable 3 core, 3 pin Top plug, element holding clamp, welding of studs for head assembly, defective inner and outer shell reassembling the geysers with one coat of milky white enameled, spray paint of approved quality after cleaning of all dust rust etc and writing of MES No on the geyser using black paint, Reinstallation of geysers to its original postion complete all as specified and as directed by Engineer-in-charge. Note : 1. Supply only Spare parts such as heating element thermostat switch, spacer ring, heon lamp, head assembly, glass wool, safety plug rubber, gasket, copper cable, top & bottom cover, inspection plate, CP & PVC connection, Plug Top, Outer & Inner shell element holding clamps etc shall be measured & paid for seperately in respective items of Schedule'A' BoQ .2. The labour element of these items is included in this item and nothing shall be paid extra on this account. |
| 59 | Supply only heating element any type (i.e; Cup,thread or triangular) 1.5 KW, 220/230 volts ISI marked. |
| 60 | Supply only heating element any type (i.e; Cup,thread or triangular) 2.0 KW, 220/230 volts ISI marked. |
| 61 | Supply only Thermostat ISI marked complete all as specified and directed by Engr-in-Charge. |
| 62 | Supply only Head Assy \\"Brass\\" 8 to 9 holes suitable for 25 ltrs capacity all as directed by Engineer-in-charge. |
| 63 | Supply only Safety plug \\"brass\\" ISI marked suitable for 25/50 ltrs geyers |
| 64 | Supply only Hot and cold water connection made of brass pipe,chrumium plated upto 18\\" length complete with rubber washer & brass nuts, ISI marked all as directed by Engineer-in-charge. |
| 65 | Supply only geyser inner assembly of brass with inlet/outlet & over flow provision rubber washer suitable for 25 ltrs capacity all as specified and directed by Engr-in-Charge. |
| 66 | Supply only bottom cover plate in two halves with self toppiry suitable and as per sample complete all as specified & directed by Engr-in-Charge. |
| 67 | Supply only phase indicator red colour circular/rectangular shape as suitable and as per sample complete all as specified and directed by Engr-in-Charge. |
| 68 | Supply only non return brass valve of 15mm bore, ISI marked as specified and directed by Engr-in-Charge. |
| 69 | Supply only pressure release brass valve of 15mm bore ISI marked all as specified and directed by Engr-in-Charge. |
| 70 | Supply only PVC connection wire woven with nickel plated brass adopter, both side threaded 45cm long the to suitable size of geysers complete all as specified and directed by Engr-in-Charge |
| 71 | Supply and laying or fixing or passing in replacement through pipe or binding with fencing/pole etc, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 16 Sqmm nominal cross section 2 core solid conductor all as specified and directed by engr-in-charge. |
| 72 | Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender from total amount of Schedule 'A'/BOQ Please Enable Macros to View BoQ information |