| 1 | Comprehensive maintenance of 320 KVA DG Set including draining out and refilling of engine oil / lubricant coolant, taking out of unserviceable oil filter element, fuel filter element, fuel flexible pipe, V-belt for water pump and alternator, air filter element, cleaning of fuel tank, etc. and replace faulty/defective parts and make DG set serviceable to the entire satisfaction of the Engineer-in-Charge complete all as specified and as directed. Make : KirloskarLocation : Sub-station at Mechuka & Tuting.Notes :(i) Spares parts and lubricants to be measured and paid separately.(ii) Job wii be carried out at Mechuka and Tuting by authorised service engineers. |
| 2 | Supply only spare parts for replacement against faulty/ defective one DG Set of 320 KVA complete all as specified and as directed of the followings :-. Make : Kirloskar |
| 3 | Fuel Filter element |
| 4 | Lub Oil Filter element |
| 5 | Fuel filter cartridge |
| 6 | Air Filter element (outer) |
| 7 | Air Filter element (inner) |
| 8 | V' Belt |
| 9 | Hose rubber |
| 10 | Hose Fuel Pipe |
| 11 | Expansion Bellow |
| 12 | Fuel pipe |
| 13 | Comprehensive maintenance of 62.50 KVA DG Set with draining out engine oil / lubricant coolant, taking out of unserviceable oil filter element, fuel filter element, fuel flexible pipe, V-belt for water pump and alternator, air filter element, cleaning of Fuel tank etc and replace faulty/defective parts and make DG set serviceable serviceable to the entire satisfaction of the Engineer-in-Charge complete all as specified and as directed. Make : KirloskarLocation : Sub-station at Vijaynagar .Notes :-(i) Spares parts and lubricants to be measured and paid separately. (ii) Job wii be carried out at Vijaynagar by authorised service engineers.. |
| 14 | Supply only spare parts for replacement against faulty / defective one DG Set of 62.50 KVA complete all as specified and as directed of the followings :- Make : Kirloskar |
| 15 | Air Filter element (outer) |
| 16 | Air Filter element (inner) |
| 17 | Hose rubber |
| 18 | V' Belt / Fan belt |
| 19 | Fuel Filter element |
| 20 | Lub Oil Filter element |
| 21 | L.O. Hose (FIP) |
| 22 | Fuel pipe (Feed pump to fuel filter) |
| 23 | Fuel pipe (Fuel filter to fuel pump) |
| 24 | Comprehensive maintenance of 30-40 KVA DG Set with draining out engine oil / lubricant coolant, taking out of unserviceable oil filter element, fuel filter element, fuel flexible pipe, V-belt for water pump and alternator, air filter element, cleaning of Fuel tank etc and replace faulty/defective parts and make DG set serviceable to the entire satisfaction of the Engineer-in-Charge complete all as specified and as directed. Make : KirloskarLocation : Sub-station at Mechuka & Tuting .Notes : (i) Spares parts and lubricants to be measured and paid separately. (ii) Job wii be carried out at Mechuka and Tuting by authorised service engineers. |
| 25 | Supply only spare parts for replacement against faulty / defective one DG Set of 30-40 KVA complete all as specified and as directed of the followings :- .Make : Kirloskar. |
| 26 | Air Filter element (outer) |
| 27 | Air Filter element (inner) |
| 28 | Hose radiator |
| 29 | V' Belt / Fan belt |
| 30 | Fuel Filter element |
| 31 | Lub Oil Filter element |
| 32 | L.O. Hose (FIP) |
| 33 | Fuel pipe (Feed pump to fuel filter) |
| 34 | Fuel pipe (Fuel filter to fuel pump) |
| 35 | M&L for dismantling of radiator assembly of 30/40 KVA DG set and re-fixing the same after proper cleaning of the copper cooling tubes with caustic soda and brazing the tube if any leakage observed during cleaning complete all as per specified and as directed. |
| 36 | All as per Serial item No. 7 here-in-before but of 62.50/63 KVA capacity DG set. |
| 37 | All as per Serial item No. 7 here-in-before but of 320 KVA capacity DG set. |
| 38 | Supply only Kirloskar Care Premium genuine oil 50 Ltr cane having Cat Part No. 82.060.10.0.50 engine oil to top up/ refilling of all DG sets of various capacity, model and location as per the standard engineering practice complete all as specified and as directed. |
| 39 | Supply only Kirloskar Care Premium genuine coolant premix 26 Ltr can having Cat Part No. 82.020.35.1.26 suitable for DG set of various capacity, model and location as mentioned above as per the standard practice complete all as specified and as directed. |
| 40 | Supply and pouring distilled water/acid mixture as per sample approved and suitable for battery and radiator complete all as specified and as directed. |
| 41 | M&L for repairing of AMF panel suitable for 320 KVA DG set inclufing internal wiring complete all as specified and as directed. |
| 42 | Labour only for disconnecting the self starter (24 V) from the engine body, dismantling the same, checking for identification of faulty spares and re-assembling the same after replacement/renewal of faulty spares, if required, including refixing to its original position (for 320 KVA DG) complete all as specified and as directed. Note : Spares required to be replaced shall be measured and paid separately. |
| 43 | Supply only following spares for fixing in repair against the faulty one for the self starter (24 V) suitable for engine of 320 KVA complete all as specified and as directed :- |
| 44 | Clutch assemblyMake : LUCAS TVS |
| 45 | Bendex pinionMake : LUCAS TVS |
| 46 | Solenoid switchMake : LUCAS TVS |
| 47 | Carbon Brush Make : LUCAS TVS |
| 48 | Armature Field Coil Make : LUCAS TVS |
| 49 | Bush Make : LUCAS TVS |
| 50 | Self armature coil Make : LUCAS TVS |
| 51 | Disconnecting the self starter (12 V) from the engine body, dismantling the same, checking for identification of faulty spares and re-assembling the same after replacement/ renewal of faulty spares, if required, including refixing to its original position (for 35 to 62.50 KVA DG) complete all as specified and as directed. Note : Spare parts required for replacement shall be measured and paid separately. |
| 52 | Supply only spares against the faulty one for the self starter (12 V) suitable for engine of 35 to 62.50 KVA complete all as specified and as directed of the followings:- |
| 53 | Clutch assembly Make : LUCAS TVS |
| 54 | Bendex pinion Make : LUCAS TVS |
| 55 | Solenoid switch Make : LUCAS TVS |
| 56 | Carbon BrushMake : LUCAS TVS |
| 57 | Armature Field Coil Make : LUCAS TVS |
| 58 | Bush Make : LUCAS TVS |
| 59 | Self armature coil Make : LUCAS TVS |
| 60 | S&F automatic voltage regulator of the following DG Set 62.5/63 KVA capacity including taking down old unserviceable one complete all as specified and as directed of the followings:-Make : Stamford/Kirloskar/MRI /Crompton Greaves |
| 61 | Suitable for 35/40 KVA DG set |
| 62 | Suitable for 62.5/63 KVA DG set |
| 63 | Suitable for 320 KVA DG set |
| 64 | S&F as in repairs battery, 12 V, 180 AH, heavy duty battery complete all as specified and as directed. |
| 65 | All as per Serial Item No.19 here-in-before but battery capacity 12 V, 100 AH. |
| 66 | S&F door lock assembly with keys suitable for aqustic enclosure for DG sets of any capacity including all accessories complete all as specified and as directed. |
| 67 | S&F as in repairs Automatic Battery Charger, I/P-230 Volt, AC, O/P - 24 Volt DC, 10 Amps. having electric circuit consisting of triodes rectifiers, capacitors and resistance, etc. The battery charger should be able to charge the battery at all the time whenever electric supply given to battery charger though control panel or electric power point complete all as specified and as directed. |
| 68 | S&F power contactor of 500 Amps, 4 pole with 2 NO & 2 NC and auxilary contact block of coil rating 415 volt, 50 Hz, including taking out old unserviceable one complete all as specified and as directed. |
| 69 | S&F voltage monitoring relay suitable for 35 KVA to 62.5/63 KVA DG set including taking down old unserviceable one complete all as specified and as directed. |
| 70 | All as per Serial item No. 24 here-in-before but for 320 KVA DG set. |
| 71 | S&F as in repairs water hose pipe suitable for 35.00 to 62.50 KVA DG set complete all as specified and as directed. |
| 72 | S&F as in repairs water hose pipe suitable for 320 KVA DG set complete all as specified and as directed. |
| 73 | S&F as in repairs coolant reserve box with pipe of suitable size for DG set as existing size complete all as specified and as directed. |
| 74 | S&F as in repairs brass battery terminal connectors with all accessories for DG set battery complete all as specified and as directed. |
| 75 | S&F as in repairs controller suitable for 35 to 63 KVA DG set complete all as specified and as directed. |
| 76 | S&F as in repairs controller suitable for 320 KVA DG set complete all as specified and as directed. |
| 77 | S&F as in repairs thermostat valve suitable for 35 to 63 KVA DG set complete all as specified and as directed. |
| 78 | S&F as in repairs thermostat valve suitable for 320 KVA DG set complete all as specified and as directed. |
| 79 | S&F as in repairs magnetic pick up suitable for 320 KVA DG set complete all as specified and as directed. |
| 80 | S&F as in repairs centrifugal filter suitable for 320 KVA DG set complete all as specified and as directed. |
| 81 | S&F as in repairs base card for the following DG set complete all as specified and as directed:- |
| 82 | 320 KVA DG set |
| 83 | 35 KVA DG set |
| 84 | S&F as in repairs controller assembly with all accessories for 320 KVA DG set complete all as specified and as directed. |
| 85 | S&F as in repairs with new water pump of 35 KVA DG Set with all accessories complete all as specified and as directed |
| 86 | S&F as in repairs with new water pump of 320 KVA DG Set with all accessories complete all as specified and as directed |
| 87 | S&F as in repairs control relay with AC coil 10 Amps with 2 NO and 2 NC contact arrangement fixed in repairs and including taking down old unserviceable one complete all as specified and as directed. |
| 88 | S&F as in repairs indicator lamp LED type, 220 volt AC (RED/GREEN) for each capacitor showing ON/OFF and including taking down old unserviceable one complete all as specefied and as directed. |
| 89 | S&F as in repairs push button actuator Red / Green and as approved including contact element and including taking down old unserviceable one, suitable for as existing one with contact element NO/NC complete all as specefied and as directed. |
| 90 | S&F as in repairs wiring harness for the following DG sets complete all as specified and as directed:- |
| 91 | 320 KVA DG set |
| 92 | 35 KVA DG set |
| 93 | Supply and install ON Load front handle operated change over switch in sheet enclosure of current rating 630 Amps, 4 pole, 415 Volts complete all as specified and as directed. |
| 94 | All as per Serial item No. 44 here-in-before but of capacity 200/250 Amps. |
| 95 | All as per Serial item No. 44 here-in-before but of capacity 63 Amps. |
| 96 | Supply and laying synthetic rubber insulated mats 3mm thick for voltage upto 3.3 KV for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and as directed. |
| 97 | M&L for earthing complete with copper plate electrode of size 60cmx60cmx3mm thick, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to copper strip of size 20x3mm as earthing lead by means of bolts, nuts, check nuts, washers, etc. of galvanised iron or steel all as shown in Electrical Plate No. 3 in SSR Part-I, connected to earthing test point all as specified and directed complete including necessary excavation and earth work, PCC pit in cement concrete (1:3:6) type C-2 (using 40mm graded stone aggregate) and 50mm thick RCC cover of size 450x450x50mm in RCC (1:2:4) type B-1 (using 20mm graded stone aggregate), reinforced with and including 8mm dia TMT bar @ 100mm centre to centre both ways, having suitable handle (10mm MS rod), 20mm dia GI pipe, medium grade as watering pipe with GI funnel with wire mesh 40mm bore GI pipe, medium grade, for protection of earth lead conductor and including testing on completion complete all as specified and as directed. |
| 98 | M&L for earthing complete with mild steel galvanised plate electrode of size 60cmx60cmx6.0mm buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to galvanised iron strip of size 32x6mm as earthing lead by means of bolts, nuts, check nuts, washers, etc. of galvanised iron or steel all as shown in Electrical Plate No. 3 in SSR Part-I, connected to earthing test point including necessary excavation and earth work, PCC pit in cement concrete (1:3:6) type C-2 (using 40mm graded stone aggregate) and 50mm thick RCC cover of size 450x450x50mm in RCC (1:2:4) type B-1 (using 20mm graded stone aggregate) reinforced with and including 8mm dia TMT bar @ 100mm centre to centre both ways, having suitable handle (10mm MS rod), 20mm dia GI pipe, medium grade for watering pipe with GI funnel with wire mesh 40mm bore GI pipe, medium grade, for protection of earth lead conductor and including testing on completion complete all as specified and as directed. |
| 99 | S&F as in repairs copper rod, 12mm dia and 300mm long air termination, single pointed after taking down old unserviceable air termination rod complete all as specified and as directed. |
| 100 | S&F as in repairs aluminium rod, 12mm dia and 300mm long air termination, single pointed after taking down old unserviceable air termination rod complete all as specified and as directed. |
| 101 | S&F 40mm dia galvanised iron pipe with all fittings, 'medium grade', for mechanical protection of earth strip, etc. including taking down old existing unserviceable steel tubing of any grade with connections and removal from site complete all as specified and as directed. |
| 102 | S&F for 20mmx3mm copper strip as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing, etc. complete all as specified and as directed. |
| 103 | M&L for 25mm x 3mm aluminium strip as earth continuity conductor fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing, etc. complete all as specified and as directed. |
| 104 | S&F thermoplastic weather proof empty box (IP-65) of size 170mm x 120mm x 70mm, fixed on wall with provision of nuts, bolts, washer, etc. including fixing of test point terminal block inside the box made out of gun metal or phosphorous bronze of size 75 x 75 x 25mm, drilled and screwed including 3 Nos 8mm dia, 25mm long hexagonal head screw after taking down old unserviceable complete all as specified and as directed.Make : Hensel, Cat No. DK 1000G or equivalent model in Sintex/Spelsberg. |
| 105 | S&F MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as per specified and as directed |
| 106 | M&L for MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 25 KA complete all as per specified and as directed |
| 107 | M&L for MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 35 KA complete all as per specified and as directed |
| 108 | M&L for MCCB 4 Pole, 415 V, Adjustable type, 630 Amps with breaking capacity 50 KA complete all as per specified and as directedNOTE : The contract sum shall be derived by deducting the amount shown in Schedule of Credit attached to this tender from total amount of Schedule 'A'/BOQ. Please Enable Macros to View BoQ information |