Tender For Work Of Providing And Configuration Of Gateway And Sending Data To Alds Panki And Sldc Lucknow From 132 Kv S/S Bamauli Under Etd Hathras, Mathura-Uttar Pradesh
TDR : 54898246
Tender Notice
BOQ
17 Days Left
Mathura
Uttar Pradesh
Tender For Work Of Providing And Configuration Of Gateway And Sending Data To Alds Panki And Sldc Lucknow From 132 Kv S/S Bamauli Under Etd Hathras
Name of Work:- Work of Providing and Configuration of Gateway and Sending Data to ALDS Panki and SLDC Lucknow from 132 KV S/S Bamauli under ETD Hathras
Sl. No.
Item Description
1
Providing & Installation of New Gateway at 132 KV S/S Bamauli with following specification as follows - (1)Multiple -master communication capability (2) Support IEC60870-5-101/103/104,DNP3serial/TCP MODBUS RTU/ASCII/TCP,IEC62056DLMS,IEC61850,SNMP,SNTP,MQTT(3) Data Point Support:- 5000 (4) Port Connectors :- 4 Serial(RS232/485) and 2 Ethernet (5) Power Supply (AC-DC) 85-265VAC 50-60HZ,100-370VDC (6) Realiability :- IEC61850-3 complitant hardware, DNV certified IEC61850 server, HOT- Standby redundancy (7) Time Sync based on NTP/SNTP/NEMA/Protoco specific Synchronization(IEC104/DNP3.0etc) Suitable for Existing Siemens Make SCADA System as Installed at 132 KV S/S Bamauli, work Included as Installation & all Software configuration and its testing if required as per site condition and all other associated work to complete the job satisfactory
2
Following work to be carried out for Lucknow SLDC -Work Included:-(a)Complete checking of SAS gateway panel included architecture and settings. (b) Programming and Configuration of gateway with address & settings (provided by client) to link from Substation to data centre Lucknow(c) Complete testing of SAS gateway and complete data communication link b/w Substation to data centre Lucknow
3
Following work to be carried out for ALDC PankiWork Included:-(a) Complete checking of SAS gateway panel included architecture and settings. (b) Programming and Configuration of gateway with address & settings (provided by client) to link from Substation to data centre Panki.(c) Complete testing of SAS gateway and complete data communication link b/w Substation to data centre Panki.
4
Inspection and rectification Siemens make Substation Automation System, installed al 132 KV S/S Bamauli.
5
The following work are inlcuding of BCU,s relays configuration and its ICD files for healthy communications with SCADA, restoring the rectified backup files of SCADA, checking the data healthiness at local SCADA, Replacing the defective FO multimode patch cord, Checking & Rectifying the healthiness of 1.11 Is and it communication ports, Checking the healthiness of IF(' 61850-7 Ethernet switches. Replacing the defective CAT-5/LAN cables and checking its healthiness Re-installation of old backup to SCADA if required. Checking the healthiness of all protection relay's communication to SCADA. Checking of all required events, alarm. numerical data's status and signals to SCADA from various bays & feeders Checking the SLD of S/S to SCADA screen checking the all required operations of equipment from SCADA if required. At the time of rectification all required material and computer parts will be arranged by department without extra charges, except the following given material will be arranged by department without extra charges, except the following given material will be provided by contractor, Scada license key. activation key, old SAS backup, and software CD will be provided by department. Note - After the completion of above work contractor has to submit the restored files and backup to the department representative via CD/Hard Drive.
6
Supply & fixing of Fibre optical Multimode patch cards for ST-ST, LC-LC, ST-LC port (As per requirement at site, having length of 05 mtr each.)
7
Providing & Installation of 4U Rackmountable Industrial CPU with following specification as follows -(1) Intel core i3-3220 3rd Gen.CPU(2) 8GB DDR3 Memory(3) 1-TB SATA HDD(4) DVD-RW Drive(5) 10/100/1000 Mbps LAN Ethernet onboard(6) USB,2*Serial and 1* VGA part on board(7) USB Keyboard and optical mouse(8) 400 watt single power supply(9) Window 7-64 Bit O.S. Without monitor(10) BIS Approved HSN -Code -8471Suitable for Existing Siemens Make SCADA System as Installed at 132 KV S/S Bamauli, Hathras work Included as Installation & all Software configuration and its testing if required as per site condition and all other associated work to complete the job satisfactory
8
Supply & Installation of Ethernet Switch at 132 KV Sub-Station Bamauli 16RJ4510/100MBPS+4x1GB FO Port(ST Port)+Dual Power Supply (With all other accessories) As per UPPTCL Norms Please Enable Macros to View BoQ information
We takes all possible care for accurate & authentic tender information, however Users
are requested to refer Original source of Tender Notice / Tender Document published by
Tender Issuing Agency before taking any call regarding this tender.