| 1 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in charge. |
| 2 | All kinds of soil. |
| 3 | Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 sqm on plan including getting out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as directed by Engineer-in- Charge: |
| 4 | All kinds of soil. |
| 5 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : |
| 6 | 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size) |
| 7 | Centering and shuttering including strutting, propping etc. and removal of form for : |
| 8 | Foundations, footings, bases of columns, etc. for mass concrete |
| 9 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. |
| 10 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 11 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by vibrating earth rammer and watering, lead up to 50 and for all lift. |
| 12 | Supplying and stacking at site. |
| 13 | Good Earth |
| 14 | Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge. |
| 15 | Providing and laying at or near ground level factory made kerb stone of M 25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in- charge). |
| 16 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : |
| 17 | Two or more coats on new work |
| 18 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. |
| 19 | Hot finished welded type tubes |
| 20 | Supplying and fixing 5A to 32A rating, 240/415V,10kA,\\"C\\"curve,miniature circuit breaker suitable for inductive load of following poles in the existing MOBDB complete with connections,testing and commissioning etc. as required. |
| 21 | Single pole |
| 22 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.with charcoal/coke and salt as required. |
| 23 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 24 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 25 | Upto 35 sq. mm |
| 26 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 27 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 28 | 2 X 16 sq. mm (22mm) |
| 29 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 30 | 40 mm dia (00-40 mm & ID-32 mm nominal) |
| 31 | Supply and installation of decorative garden post with height of 2440mm and dia 60.3mm and bottom dia 139.7mm including base plate with the size of 200mmx200mmx 8mm thick. 4 elongated hole (38x19) to suit for M16 bolt at CC of 140mm & cable entry hole 70mm and 4Nos of 300mm length “J” type bolt with 2Nos of plain washer & 2Nos of M16Nuts each with necessary elmax connector block and internal wiring etc. as required. (K-Lite: KP-4280) |
| 32 | Supply of aluminium Armoured XLPE UG CABLE 1.1KV as per ISI Specification IS:7098/(Part-I) 1988 with latest amendments. |
| 33 | 2x16sq mm |
| 34 | Supplying and fixing of following size ISI marked PVC insulated and PVC unsheathed copper single core and multi-core shaethed bright annealed bare copper flexible cables for voltage grade 1.1 KV grade as required.(Make:Finolex,Gloster,Havells and Polycab) |
| 35 | 3x1.5 sqmm |
| 36 | Supply and installation of Street light pole with a height of 3000 mm and 3 mm thick ,Top 70,Bottom-130mm, including base plate with the size of 200x200 mm and 12mm thick. 4 elongated hole (20x34) to suit for M16 bolt at CC of 140mm & cable entry hole 65mm and 4Nos of 16x450mm length “J” type bolt with 4 Nos of plain washer & 4Nos of M16x450LG Bolts each,1 no's of M10 Bolt for Earthing, 63 dia Pvc pipe for cable entry,Foundation RCC M20 Concrete (450x450x1100)mm and 36W,120 lm/W LED post top Street luminaries Epoxy powder coated pressure die-cast aluminium housing,Weatherproof gaskets provided for LEDs and control gear compartments and with size of dia 265mm x 185mm with IP66 protections,Surge protection 4kV with necessary elmax connector block and internal wiring etc. as required. The rate should be inclusive of 1. pole 2.Foundation bolt 3. Light fixture 4. 500mm Cross Arm 5.45mm dia pipe for cable entry (Preferred Make: Bajaj-BAJAJ ENXT P 36W WH PO PC SD_114113 or Equivalent) as required |
| 37 | Supply and fixing of Terminal connector/ led indicators/Terminal Block. Please Enable Macros to View BoQ information |