| 1 | M&L for Periodical mainteneance of DG Sets for proper functioning as per manufacturer's recommendations of following capacities of Make : Kirloskar/Greaves/ Mahindra/Cummins/Ashok Leyland all as per existing site by replacing Filters (Fuel filter, Lube Oil Filter, By Pass Filter), Air Cleaner both inner and outer element, Water seperator, Engine oil of suitable grade as per OEM recommendation upto upper level, Checking for diesel leakage and Cleaning of Diesel Tank thoroughly, Cleaning of Radiator after removing of old coolant completely with water and suitable radiator Cleaning agent, Oiling and Greasing of Engine Parts, Checking of all hose pipes, tightening of all pipes, cable conncections, Cleaning and Servicing of alternator, Cleaning of Exhaust Pipe, Silencer including checking for leakage of smoke alongwith replacement of minor spare parts if any, complete all as specified and directed by Engr-in-charge. Note :- (i) Rate Quoted shall include the cost of distilled water for batteries and Fuel filters, Lube oil filters, By pass filter, Air filter and minor spares. (ii) Engine Oil and Coolant shall be measured and paid separately under respective items. |
| 2 | DG Set 30 to 50 KVA Capacity |
| 3 | DG Set 62.5 to 82.5 KVA Capacity |
| 4 | DG Set 100 to 125 KVA Capacity |
| 5 | DG Set 160 to 200 KVA Capacity |
| 6 | DG Set 400 KVA Capacity |
| 7 | Supply only Coolant of approved make as per OEM in sealed containers complete all as specified and directed. |
| 8 | Supply only Synthetic Engine Oil (Type : SAE 20W40) of approved make as per OEM in sealed containers complete all as specified and directed. |
| 9 | S&F in replacement of Fan Belt for following capacities DG Sets of existing make complete all as specified and directed by Engr-in-charge. |
| 10 | DG Set 30 to 50 KVA Capacity |
| 11 | DG Set 62.5 to 82.5 KVA Capacity |
| 12 | DG Set 100 to 125 KVA Capacity |
| 13 | DG Set 160 to 200 KVA Capacity |
| 14 | DG Set 400 KVA Capacity |
| 15 | S&F in replacement of V-Belt for following capacities DG Sets of existing make complete all as specified and directed by Engr-in-charge. |
| 16 | DG Set 30 to 50 KVA Capacity |
| 17 | DG Set 62.5 to 82.5 KVA Capacity |
| 18 | DG Set 100 to 125 KVA Capacity |
| 19 | DG Set 160 to 200 KVA Capacity |
| 20 | DG Set 400 KVA Capacity |
| 21 | M&L as in repair of fuel injection pump (FIP) by dismantling and segregation all parts, replacement of new parts such as filter screen shut down valve, valve elbow, pulsation clamp, idle adjusting screw, high speed spring, governer plug, nozzle etc in replacement of existing u/s parts re-assembling the pump after repair / replacement of parts and testing by caliberation as per sample of Cap 30-82.5 KVA. |
| 22 | M&L as in repair of fuel injection pump (FIP) by dismantling and segregation all parts, replacement of new parts such as filter screen shut down valve, valve elbow, pulsation clamp, idle adjusting screw, high speed spring, governer plug, nozzle etc in replacement of existing u/s parts re-assembling the pump after repair/replacement of parts and testing by caliberation as per sample of Cap 100-180 KVA. |
| 23 | M&L as in repair of fuel injection pump (FIP) by dismantling and segregation all parts, replacement of new parts such as filter screen shut down valve, valve elbow, pulsation clamp, idle adjusting screw, high speed spring, governer plug, nozzle etc in replacement of existing u/s parts re-assembling the pump after repair/replacement of parts and testing by caliberation as per sample of Cap 400 KVA. |
| 24 | M&L for taking down and servicing of radiator assembly and replacement of minor parts, de-scaling of tubes with chemical solution, welding/brazing leak testing including transportation to workshop and re-fixing after repairs and testing commissioning complete all as specified and directed by Engr-in-charge. |
| 25 | DG Set 30 to 50 KVA Capacity |
| 26 | DG Set 62.5 to 82.5 KVA Capacity |
| 27 | DG Set 100 to 125 KVA Capacity |
| 28 | DG Set 160 to 200 KVA Capacity |
| 29 | DG Set 400 KVA Capacity |
| 30 | S&F in replacement of maintenance free Tubular Battery 12V, 180 AH with minimum 36 months warranty complete all as specified and directed by Engr-in-charge. |
| 31 | S&F in replacement of maintenance free Tubular Battery 12V, 150 AH with minimum 36 months warranty complete all as specified and directed by Engr-in-charge. |
| 32 | S&F in replacement of maintenance free Tubular Battery 12V, 115/120 AH with minimum 36 months warranty complete all as specified and directed by Engr-in-charge. |
| 33 | S&F in replacement of Battery lead copper conductor of size 50 Sqmm multistranded PVC insulated with suitable terminals at both ends of required length for each battery complete all as specified and directed. |
| 34 | M&L for repair of self starter with replacament of carbon bushes, pinion, rewinding of stator and rotor winding with approved quality of winding wire as per existing and replacement of defective parts to make the starter fully functional and commissioning and testing of DG set of any type and capacity all as specified and directed by Engr-in-Charge. |
| 35 | Supply and Fix Battery Lugs/Connectors of suitable capacity as per the site all as directed by Engr-in-Charge. |
| 36 | S&F in replacement of Hose Pipe Set suitable for the following capacities of DG sets complete all as specified:- |
| 37 | Up to 62.5 KVA DG Set |
| 38 | 82.5 KVA to 180 KVA DG Set |
| 39 | 200 KVA to 400 KVA DG Set |
| 40 | M&L for preparing old rusted surface of DG sets by thoroughly cleaning the surface to remove dust, rust flakes, paint flakes using wire brush or sand paper, primimg the affected surface with anti-corrosive primer and applying paint using suitable sprayer to get a smooth glossy surface finish and writing MES Number of DG Set (both Engine and Alternator) at existing site in Block capital letters all as specified and directed by Engr-in-Charge. |
| 41 | M&L as in repairs to DG Set Control Panel of capacity 30-82.5 KVA incl replacement defective sensors like AMF module, relay card/board, current transformer, Key switch , Indicators, Warning, Push button and checking control wiring complete including made functional all the system/controls complete all as specified and directed by Engineer in charge |
| 42 | M&L as in repairs to DG Set Control Panel of capacity 100-400 KVA incl replacement defective sensors like AMF module, relay card/board, current transformer, Key switch , Indicators, Warning, Push button and checking control wiring complete including made functional all the system/controls complete all as specified and directed by Engineer in charge. |
| 43 | M&L in replacement of Coolant Tempetarure Sensor suitable for 30-400 KVA Cummins/Kirloskar/Ashok Leyland/Mahindra DG set including connection with circuit panel, starting and testing on load all as specified and directed by Engineer-in-Charge. |
| 44 | M&L in repair of old hinges and fixing new with fitting/welding as per existing size complete all as specified and as directed. |
| 45 | M&L in replacement of GI Strip 32x6.00 mm as roof conductor or down conductor or along the pole/pipe complete with saddles/insulators made out of porcelain or fibre alongwith fixing screws all as specified and directed by Engr-in-Charge. |
| 46 | S&F in replacement of Battery Charger of 6 Amps rating 12V Battery all as specified by directed by Engr-in-Charge. |
| 47 | S&F in replacement of Battery Charger of 6 Amps rating 24V Battery all as specified by directed by Engr-in-Charge. |
| 48 | M&L for complete fixing in repairs for DG set accoustic enclosure door Hinges / Aldrops/Locks with 02 Keys including carrying out necessary modifications complete all as specified and directed by Engr-in-Charge. |
| 49 | M&L for earthing complete with galvanized steel earth plate electrode of size 600x600x6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of the earth plate not less than 1.5 mtr below normal ground level connected to galvanised iron strip 32x6 mm as earthing lead connectd by means of bolts, nuts, washers and check nuts all as shown in electrical plate No 3 of MES SSR Part-I, including testing on completion complete all as specified and as directed. |
| 50 | Supply & fixing in replacement MCCB thermal relay range 200- 250 Amps, 4 pole 415V of breaking capacity 36 KA and and connecting to bus bars and cable end termination with suitable lugs complete all as specified and directed. |
| 51 | Supply & fixing in replacement MCCB thermal relay range MCCB 160-200 Amps, 4 pole, 415 V, breaking capacity 36 KA complete all as specified and directed. |
| 52 | Supply & fixing in replacement MCCB thermal relay range 4 pole MCCB 63-80 Amps,415 V, breaking capacity 18 KA complete all as specified and directed. |
| 53 | Supply and fixing in replacement of burnt/ unsv 3 pole power contactor Type ML-1.5/MNX 25, 25 Amp ,415/220 volts ,50 Hz coil voltage 415 Volts alongwith NO/NC as applicable all as specified and directed. |
| 54 | Supply and fixing in replacement of burnt/unsv 3 pole power contactor Type ML-2.0/MNX 32, 32 Amp ,415/220 Volts ,50 Hz coil voltage 415 Volts alongwith NO/NC as applicable all as specified and directed. |
| 55 | Supply and fixing in replacement of burnt/unsv 3 pole power contactor Type ML-3/Suitable MNX Type, 40 Amp ,415/220 Volts ,50 Hz coil voltage 415 Volts alongwith NO/NC as applicable all as specified and directed. |
| 56 | Supply and fixing in replacement of burnt/unsv 3 pole power contactor Type ML-4/MNX Type, 70 Amp ,415/220 Volts ,50 Hz coil voltage 415 Volts alongwith NO/NC as applicable all as specified and directed. |
| 57 | Supply and fixing in replacement of burnt/unsv 3 pole power contactor Type ML-6/Suitable MNX Type, 110 Amp ,415/220 Volts ,50 Hz coil voltage 415 Volts alongwith NO/NC as applicable all as specified and directed. |
| 58 | Supply and fixing in replacement of thermal over load relay type ML-1.5/MNX type relay range 13-21 Amps complete all as specified and as directed. |
| 59 | Supply and fixing in replacement of thermal over load relay type ML-2.0/MNX type relay range 20-32 Amps complete all as specified and as directed. |
| 60 | Supply and fixing in replacement of thermal over load relay type ML-3.0/MNX type relay range 28-42 Amps complete all as specified and as directed. |
| 61 | Supply and fixing in replacement of thermal over load relay type ML-3.0/MNX type relay range 30-50 Amps complete all as specified and as directed. |
| 62 | Supply and fixing in replacement of thermal over load relay type ML-4.0/MNX type relay range 45-75 Amps complete all as specified and as directed. |
| 63 | Supply and fixing in replacement of thermal over load relay type ML-6.0/MNX type relay range 66-110 Amps complete all as specified and as directed. |
| 64 | M&L for comprehensive periodical maintenance of RO Plants for their proper functioning as per manufacturer's recommendations of following capacities of any make as per site by complete unit checkup incl electrical machinery, general cleaning, backwashing, chemical cleaning of cartridge and replacement of all type of filters on quarterly basis as per the complaint during the contract Period, testing and commissioning complete all as specified and directed. Note :- Membrane and other consumables as well as spare items shall be measured and paid separately under respective items. |
| 65 | RO Plant of 10 LPH Capacity |
| 66 | RO Plant of 100 LPH Capacity |
| 67 | RO Plant of 200 LPH Capacity |
| 68 | RO Plant of 3000 LPH Capacity |
| 69 | RO Plant of 10000 LPH Capacity |
| 70 | Supply only RO membranes of following capacities of approved make as per OEM in complete all as specified and directed. |
| 71 | RO Plant of 10 LPH Capacity |
| 72 | RO Plant of 100 LPH Capacity (Type : 4012) |
| 73 | RO Plant of 200 LPH Capacity (Type : 4040) |
| 74 | RO Plant of 3000 LPH Capacity (Type : 8040) |
| 75 | RO Plant of 10000 LPH Capacity (Type : 8040) |
| 76 | M&L for opening dual media FRP vessel of size existing at site by taking out old unserviceable items and refilling the vessel with filter media items all as specified and directed by Engr-in-Charge. |
| 77 | Supply only Filter media items of approved quality and make complete all as specified and directed. |
| 78 | Carbon 1200 ID (For commercial water treatment plant) |
| 79 | Pebbles |
| 80 | Silex/Silica |
| 81 | Supply only following chemicals of approved make and quality as per OEM: |
| 82 | Antiscalant Chemical |
| 83 | Sodium Bicarbonate Solution for pH correction |
| 84 | Supply only following items and spares for RO plant of approved make and quality as per OEM: |
| 85 | Pressure Gauge |
| 86 | Pressure Switch |
| 87 | Level Switch |
| 88 | Flow Indicator |
| 89 | HDPE Dozing Tank of Cap-100 Litres |
| 90 | M&L for repair to high pressure pump of rating upto 10 HP of discharge upto 15 Cum/Hr at 14.5 Kg/cm sqauared pressure, SS-304 impeller vertical centrifugal pipe all inclusive of replacement of spare parts all as specified and directed by Engr-in-Charge. |
| 91 | M&L for repair to Raw water pressure pump of rating upto 20 HP of discharge upto 15 Cum/Hr at 14.5 Kg/cm sqauared pressure, SS-304 impeller vertical centrifugal pipe all inclusive of replacement of spare parts all as specified and directed by Engr-in-Charge. |
| 92 | Preventive maintenance of electric motor driven Chlorine dosing system any make including cleaning of electrode rod, HDPE/FRP tank of capacity up to 150 Ltr tank and checking functionality and performance of level gauge, Dosing pump, High pressure single head gear motor, pressure gauge, power pack incl oiling and greasing of all moving parts.Note : Spare Parts reqd for replacement in maintenance work will be measured & paid separately. |
| 93 | Opening the motor of capacity 0.5HP, rewinding the motor with super enammeled copper wire of existing gauge,weight etc, reparing the same by replacing the unserviceable spare parts and re-assembling the motor in orignal position to make it functional complete all as specified and as directed. |
| 94 | Supply Only of Gear Motor 230 volt 50 Hz suitable for decrin dosing pump Part No PM 682 CE |
| 95 | Supply only of Rotor assembly with bearing brackets and tolerance rings. Part No PMBR PL2 |
| 96 | Supply only of Coil 250 volt, 50Hz Part No. MP 6 J222 |
| 97 | Supply only of Single head feed rate control with shaft Part No FC 5040D |
| 98 | Supply only of Pump head (Ferrules 1/4\\" including duckbill Part No UCPH 7 FD |
| 99 | Supply only of Roller assembly Part No. MC3ASYD |
| 100 | Supply only of Pump tube. Part No MCCP 207 |
| 101 | Supply only of Injection check valve 3/8\\" Part No MCINJ 38 |
| 102 | Supply only of Weighted suction line strainer 3/8\\" Part No. ST 138 |
| 103 | Supply only of White suction/discharge tube Part No. MAL T002 |
| 104 | Supply only of chloroscope for water testing range of 0.1 ppm to 2.0 ppm |
| 105 | Supply only of ORTO-TOLUDINE regent solution in 500 ml bottle |
| 106 | Supply only of first Aid kit (PVC container) as per the specification including first aid medical treatment materials complete . Make: Standard or equivalent make approved by the Engr-in-charge (Note : All the medicine and First Aid will be of latest date and should be having atlest 12 months expiry date from the date of actual supply) |
| 107 | Supply only Knob of speed/stroke complete all as specified and directed. |
| 108 | Supply only main indicator lamp assembly complete. |
| 109 | Supply only valve seat cap of suction/discharge complete. |
| 110 | Supply only fixing bolts made of stainless steel or supplied by OEM only |
| 111 | Supply only main indicator lamp assembly |
| 112 | Supply only Diaphragm seal |
| 113 | Supply only Diaphragm |
| 114 | Supply only Shaft(Diaphragm) |
| 115 | Supply only strainer only(Foot valve) |
| 116 | Supply only Pipe(Discharge/suction) |
| 117 | Supply only Foot valve assembly (complete with ball,seal &spring) |
| 118 | Supply only pulser circuits & speed potentiometer |
| 119 | Supply only power transformer. |
| 120 | Supply only fuse assembly including fuse complete. |
| 121 | Supply and fixing in replacement of antisyphon valves (comlete with ball, seal & Spring) all as directed. |
| 122 | Supply and fixing in replacement of FRP construction solution preparations cum settling Tank with level gauge, lid, inlet / outlet connection, drain connection and fitted with speed reducer, motor and SS agitator of capacity 100 Ltr complete all as specified and directed. |
| 123 | Supply and fixing in replacement of FRP construction solution preparations cum settling Tank with level gauge, lid, inlet / outlet connection, drain connection and fitted with speed reducer, motor and SS agitator of capacity 150 Ltr complete all as specified and directed. |
| 124 | Supply only of PVC/Rubber Hand glove suitable for handling of liquid Chlorine ISI marked complete all as specified and directed. |
| 125 | Excavation in trenches not exc 1.5 metres wide and not exc1.5 metres deep for pipe line in soft/loose soil, getting out and levelling of bottom surface to required level all as specified and as directed by Engineer-in-Charge |
| 126 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exc. 25 cm thick all as specified and directed by Eng. In Charge |
| 127 | Removal of excavated material from site to a distance not exceeding 50 meters away and depositing where directed at a level not exceeding 1.5 meters above the starting point as directed by Engr-in-Charge. |
| 128 | Excavation in trenches by cutting of road crossing, PCC hard standing for taking out/laying of pipe lines including PCC (1:2:4) type B-2 (with 40 mm graded aggregate) in foundations,filling and mass concrete complete including making good the existing surface all as specified and directed. |
| 129 | M&L for taking out old unserviceable LT cable of any size/make from trenches/wall/ducts/roof all as specified and direcyted by Engr-in-Charge. |
| 130 | Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable with stranded aluminium conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole of the following sizes:- |
| 131 | 16 Sqmm x 4 Core |
| 132 | 25 Sqmm x 3.5 Core |
| 133 | 35 Sqmm x 3.5 Core |
| 134 | 50 Sqmm x 3.5 Core |
| 135 | 70 Sqmm x 3.5 Core |
| 136 | Supply & spread unwashed dry river sand for sand cushioning and covering the under ground cable in trenches/ducts. (Note :- Punning thickness shall be measured.) |
| 137 | M&L for brick protection with sub Class`B` bricks old size laid dry, flat over cable perpendicular across the cable in trenches complete all as directed. |
| 138 | Supply and fixing in replacement 60 watt LED street light new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having TOP Opening seperate driver compartment with IP-66 protection and impact resistance of IK07 including making connections with GI pipe 0.6 mtr angle bracket fixing on wall using suitable fastners and connectng to ceiling rose with appropriate copper wire complete all as specified and directed. |
| 139 | Supply and fixing exhaust Fan, heavy Duty 450 mm sweep, 1400 RPM Single pole 230V , 50Hz complete all as specified Make: Orient/Havells/CG/Usha |
| 140 | Supply and fixing ceilling fan 1200 mm sweep Single pole 230V , 50Hz complete with fan regulator and down rod connection complete all as specified and directed. |
| 141 | S&F in replacement new generation post-top Gate Light, energy saving, environment friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source 25W, 5700K complete with provision and fixing of GI pipe with necessary civil works involved complete all as specified and directed. |
| 142 | Repair and replacement of DG Set Governor analog speed control unit used to regulate engine speed in generators for capacity of 160 KVA to 180 KVA as per exixting site with connection complete all as specified and directed by Engr-in- Charge. |
| 143 | Supply, Installation, testing and commissioning of retrofit emission control device (RECD) for 180 KVA DG Set The RECD must be Cat-con technology, with Active Regeneration Trap which reduce particular matter (PM 2.5), Carbon Monoxide and Hydrocarbons emitted from Diesel Engine, Guaranteed specified Particulate matter (PM ) Carbon Monoxide, Hydrocarbon reduction efficiency (Min). Guaranteed specified Particular Matter (PM 2.5) with connection complete all as specified and directed by Engr-in- Charge. |
| 144 | Supply, Installation, testing and commissioning of retrofit emission control device (RECD) for 400 KVA DG Set The RECD must be Cat-con technology, with Active Regeneration Trap which reduce particular matter (PM 2.5), Carbon Monoxide and Hydrocarbons emitted from Diesel Engine, Guaranteed specified Particulate matter (PM ) Carbon Monoxide, Hydrocarbon reduction efficiency (Min). Guaranteed specified Particular Matter (PM 2.5) with connection complete all as specified and directed by Engr-in- Charge. |
| 145 | An amount of Rs 31,225.00 shall be deducted from BOQ on account of schedule of credit Please Enable Macros to View BoQ information |