| 1 | Supply only calcium hypochlorite granules containing 65% free chlorine in 45 kg container complete all as specified and directed.Note : (i) Disinfectant will be brought out site in sealed container.(ii) Disinfectant will be of Approved Make as per E-in-C branch. |
| 2 | Attending day to day complaints pertains to Electric driven motors and LT panels, Starter panels of any capacity as and when required with skilled Electrician and helper, with necessary T&P for checking the equipment at existing location and find out the faults/ defects and rectify the defects in situ, cleaning/ normal maintanance to the euipments (including fixing lugs, nuts, bolts, etc as required on site) complete to make the equipment functional in all respect complete all as spceified and directed by Engr-in-charge.Note : (i) Spare parts wiil be measured and paid separately in subsequent items |
| 3 | Supply only following spare parts of Starter panels/ LT panels etc. all as specified and directed: |
| 4 | Indicating lamp Make - As per existing |
| 5 | Voltmeter 0 – 500 V. Make - As per existing |
| 6 | Ammeter 0–100A. Make - As per existing |
| 7 | Single phase preventer system of supply 415 Volt 50 Hz. Make - As per existing |
| 8 | Start/ Stop switch. Make - As per existing |
| 9 | Power contactors as per existing make.Make : As per existing |
| 10 | Star-delta Electronic timers. Make - As per existing |
| 11 | Overload relay range of 9-65A or as per existing Make -As per existing |
| 12 | Copper thimble 4/ 6Sqmm |
| 13 | Copper thimble 10/ 16Sqmm |
| 14 | Attending complaint of repair of chemical dozing pump,detection of fault and rectification of the defects at site and comprising of replacement of spare parts kit, pipe, foot valve, Injector nozzle, NRV, filter etc.complete all as specified and directed. |
| 15 | S&F in replacement changeover switch, off load, 4 Pole, 125 Amps capacity, including its sheet metal enclosure all as specified and as directed. |
| 16 | S&F in replacement changeover switch, off load, 4 Pole, 200 Amps capacity, sheet metal enclosure all as specified and as directed. |
| 17 | S&F in replacement MCCB, 3 pole, 415 volts, 125 Amps, 25KA breaking capacity with adjustable thermal settings and adjustable magnetic settings all as specified and directed. |
| 18 | S&F in replacement MCCB, 4 pole, 415 volts, 160Amps, 36KA breaking capacity with adjustable thermal settings and adjustable magnetic settings all as specified and directed. |
| 19 | S&F in replacement MCCB, 4 pole, 415 volts, 200Amps, 36KA breaking capacity with adjustable thermal settings and adjustable magnetic settings all as specified and directed. |
| 20 | S&F in replacement MCCB , 125 Amps, 4Pole with adjustable thermal magnetic release type setting knob and rupturing capacity 16 kA complete all as specified and directed. |
| 21 | Supply & Fixing in replacement including making connection testing and commissioning of new MCCB 3 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA.Note: The make of MCCB shall be L &T , GE , Havells, Strandard, crompton, C & S or any other make as per the make in the existing panel board or exactly suitable to the existing frame size. In case only one particular make is procuring by the bidder necceasry alteration required to fix the same at no extra cost shall be done by the bidder . |
| 22 | Complete all as per iitem No. 11.00 here in above but MCCB TP 400 Amps, 415 Volts, 36 KA, 50 Hz complete with extended terminals and PVC spreader complete all as specified and directed. |
| 23 | Complete all as per iitem No. 11.00 here in above but MCCB TP 630 Amps, 415 Volts, 50 KA, 50 Hz complete with extended terminals and PVC spreader complete all as specified and directed. |
| 24 | Complete all as per iitem No. 11.00 here in above but 4 Pole, 125 Amps, 415 V, 25 KA, 50 hz complete with extended terminals and PVC spreader complete all as specified and directed. |
| 25 | Complete all as per iitem No. 11.00 here in above but 4 Pole, 250 Amps, 415 V, 25 KA, 50 hz complete with extended terminals and PVC spreader complete all as specified and directed. |
| 26 | Complete all as per iitem No. 11.00 here in above but 4 Pole, 400 Amps, 415 V, 36 KA, 50 hz complete with extended terminals and PVC spreader complete all as specified and directed. |
| 27 | M&L for installing, 1 HP sludge pump, single phase, ISI marked, including necessary accessories required for fixing accessories nylon rope of suitable size for carrying the pump in sludge well, including taking out existing unserviceable pump set from sludge well, and disposing off complete all as specified and as directedMake : Crompton/ Kirloskar/ KSB or equivalent makes mentioned in List of approved makes |
| 28 | Supply only chemical dozing pump of capacity 5LPH, maximum pressure 5.5kg/sqcm, stroke speed 100 duly fixed with suction/delivery pipes, duly synchronosing with the present system and fixed including disposing off old/unserviceable pump complete all as specified and as directed.Make : Toschon Jesco M/s Sathya sai aqua pure/ Decrin or equivalent makes mentioned in List of approved makesNote: Fixing shall be done under the complaint item No. 04. |
| 29 | S&F in replacement of Discharge pressure gauges 100 mm nominal dia with control valve, socket, union and adopter, range 0-300 PSI fixed with 150 mm long, 15mm dia GI pipe medium grade with suitable arrangement for fixing on 80/100/150/200 mm DI/CI by using clamps, etc, including taking down existing unserviceable item complete all as specified and directed. |
| 30 | Excavation of soft/loose soil in trenches not exc 1.5 meter wide & not exc 1.5 mtr in depth: for foundationetc or for manholes, laying of pipe in any type of soil and getting out complete all as specified |
| 31 | Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete. |
| 32 | Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete. |
| 33 | M & L for dry sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying and stretching of cable all as specified and directed .Note : Compacted Thickness 18 cm shall be considered for measurement and payment purpose. |
| 34 | M & L for Old size sub class ‘B’ bricks, laid in trenches as cable covers complete . |
| 35 | M & L for Cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate in foundations, filling and mass complete. |
| 36 | M & L for Cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundations, filling and mass concrete complete. |
| 37 | M & L for cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate in copings to poles & the like, etc including weathering, slightly rounded or chamfered angles and throating as directed including necessary form work complete. |
| 38 | M & L replacement for PVC insulated, stranded aluminium conductor served with inner sheathing PVC tape and over all PVC sheathed in service connection suspended by insulating hanger not more than 1 meter apart including 4 mm dia GI suspension wire , two single core cable of 10 Sqmm , complete all as specified and directed by Engr-In-Charge.Makes : Finolex/ IndoAsian/Standard or equivalent makes mentioned in Approved Make list . |
| 39 | Cleaning and upkeeping the area including uprooting of shrubs/grass and removing creepers from fencing or poles / posts and brooming the complete area of sub station around panels,transformers, four pole structures etc upto 3 feet from fencing or pole externally , all around complete and maintaining the same during currency of contract period, removing the debris to a distance not exc 50m and depositing where directed complete all as specified & directed. Note : The payment will be made one time and nothing extra will be admissible to upkeep the area during currency of contract period. The cost of brooms, showels, pick axe etc shall be deemed to include in the rate quoted by tenderer. |
| 40 | Supply and fixing cable route indicator, made of MS sheet of size 200 mm x 150 mm x 3 mm thick, spot welded with angle iron of size 40 x 40 x 5 mm thick, 750 mm long embedded in PCC (1:2:4) type B-2( using 40mm graded crushed stone aggregate) block 30cm x 30cm x 40cm in ground including one coat of synthetic enamel black paint over one coat of red oxide zinc chrome primer and writing with white paint showing size of cable HT /LT complete all as specified & directed . Please Enable Macros to View BoQ information |
| 41 | Supply and fixing cable route indicator, made of MS sheet of size 200 mm x 150 mm x 3 mm thick, spot welded with angle iron of size 40 x 40 x 5 mm thick, 750 mm long embedded in PCC (1:2:4) type B-2( using 40mm graded crushed stone aggregate) block 30cm x 30cm x 40cm in ground including one coat of synthetic enamel black paint over one coat of red oxide zinc chrome primer and writing with white paint showing size of cable HT /LT complete all as specified & directed . Please Enable Macros to View BoQ information |