| 1 | S&F in repairs 15mm bore dia gun metal gate valve with iron wheel head screwed both ends for iron pipe complete all as specified and as directed.(Make:- KIRLOSKAR/ LEADER / VENUS/ ZOLOTO/ AUDCO) |
| 2 | S&F in repairs 20 mm bore dia gun metal gate valve with iron wheel head screwed both ends for iron pipe complete all as specified and as directed.(Make:- KIRLOSKAR/ LEADER / VENUS/ ZOLOTO/ AUDCO). |
| 3 | S&F in repairs 25 mm bore dia gun metal gate valve with iron wheel head screwed both ends for iron pipe complete all as specified and as directed.(Make:- KIRLOSKAR/ LEADER / VENUS/ ZOLOTO/ AUDCO). |
| 4 | S&F in repairs 15mm bore dia PTMT connection pipe of length 450mm including PVC washer on both side complete all as specified and as directed. |
| 5 | S&F in repair of Rotational moulded polyethylene water storage tanks of cap 1000 litrs, 3 layers (cylindrical vertical with closed top) hoisted and fixed in position incoming line valves and fittings all as specified and directed by engineer in charge. |
| 6 | S&F in repair complete including all fittings GI pipe medium grade of 25 mm dia to walls and ceilings with saddle clamps or laid in floors in short lengths complete all as specified and directed by engineer in charge. |
| 7 | S&F in repair complete including all fittings GI pipe medium grade of 20 mm dia to walls and ceilings with saddle clamps or laid in floors in short lengths complete all as specified and directed by engineer in charge. |
| 8 | S&F in repair complete including all fittings GI pipe medium grade of 15 mm dia to walls and ceilings with saddle clamps or laid in floors in short lengths complete all as specified and directed by engineer in charge. |
| 9 | S&F in repair Ball valves high pressure of PTMT with epoxy coated Aluminium Rod & high density plastic ball screwed for iron pipe of size 20 mm dia bore and fixed complete all as specified and directed by engineer in charge. |
| 10 | M&L for taking down unserviceable ducts and Supply, Fabrication, Installation, Balancing and Commissioning of Site fabricated GSS sheet metal rectangular ducting of 0.79mm thick (22 gauge) with supports as per IS 655-2010 complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports & mounting ,connecting unit to duct, controller fixation, joint gasket , nut, bolts ,flanges, cleats, etc. complete all as specified and directed by engineer in charge. |
| 11 | M&L for taking down unserviceable ducts and Supply, Fabrication, Installation, Balancing and Commissioning of Site fabricated GSS sheet metal rectangular ducting of 0.79mm thick (24 gauge) with supports as per IS 655-2010 complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports & mounting ,connecting unit to duct, controller fixation, joint gasket , nut, bolts ,flanges, cleats, etc. complete all as specified and directed by engineer in charge. |
| 12 | M&L in repair for Sub main wiring with four (04) runs of single core 4 Sqmm (nominal area) PVC insulated copper conductor FRLS (Confirming to IS-694) multi stranded, unsheathed 1100 volts grade in PVC conduit (medium grade) of adequate size on surface of wall/ceiling with all fittings & accessories including one (01) run 4 Sqmm single core unsheathed multi stranded, copper cable FRLS (Confirming to IS-694) as earth continuity wire complete all as specified and directed by engineer in charge. |
| 13 | S&F in repair of TPN DB, 4 way, double door, 415 volt complete all as specified and directed by engineer in charge. |
| 14 | S&F in repair of MCB of TPN 240 volts, 40 to 63 Amp, 10KA 'C' curve all as specified and as directed. |
| 15 | S&F in repairs of MCB SP 240 volts 6 to 32 Amps, 10 kA, 'C' curve complete all as specified and as directed. |
| 16 | M&L for earthing with galvanised steel earth plate electrode of size 60cmx60cm x6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead 25x4mm by means of bolts, nuts check nuts and washers of galvanised iron wire 4mm as earth lead as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI medium grade watering pipe, 40mm dia GI medium grade earth lead protection pipe and pre-cast earth pit cover 50mm thick made of RCC (1:1.5:3) type A1 duly reinforced with 8mm dia TMT bar @100mm c/c both ways, one lifting handle made out of 10mm dia TMT bar 250mm long embedded in cover slab and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternate layer of 15cm thick including taking down old unserviceable one complete all as specified and directed. (Make of GI Pipe:-JINDAL/ TATA/ BST/ PRAKASH TUBES/ OSWAL)(Note:- Each protection pipe and earthing lead upto and including 7.5 meter lenght is deemed to be included in the qouted rate of this item.) |
| 17 | Supply, laying testing and commissioning of cable sizes 4 core x 16 sqmm of XLPE insulated PVC sheathed round wire armoured aluminium conductor cable of 1.1 kV grade on trenches/cable tray/surface including clamps,connection with cable lugs ties connection of cables with suitable size lugs etc. complete including taking down old cable all as specified and directed. Note : Necessary excavation & earth work will be measured & paid separately. |
| 18 | M&L for Excavation in trenches not exceeding 1.5 m wide and n. exc 1.5 m in depth for laying of cables in soft/loose soil all as specified and directed by engineer in charge. |
| 19 | M&L for Returning, filling in including spreading leveling, watering and well ramming in layers not exceeding 25 cm all as specified and directed by engineer in charge. |
| 20 | M&L for Removing excavated material n. exc 50 m and depositing where directed at a level n. exc 1.5 m above the starting point all as specified and directed by engineer in charge. |
| 21 | M&L for sand cushioning to the full width of trenches for protection of cables including spreading watering and consolidation all as specified and directed by engineer in charge.(Note- Only punned down column of sand to be measured). |
| 22 | M&L for old size sub class \\"B\\" bricks laid in trenches as cable covers complete all as specified and as directed by Engr-in-Charge Please Enable Macros to View BoQ information 12.0 5.0 60.0 10.0 1.0 10.0 4.0 55.0 220.0 50.0 40.0 2000.0 4.0 20.0 80.0 60.0 35.0 2100.0 4.0 5.0 20.0 50.0 22.0 1100.0 5.0 1.0 5.0 50.0 25.0 1250.0 1.0 5.0 5.0 14.0 50.0 700.0 60.0 5.0 300.0 6.0 1.0 6.0 12.0 1.0 12.0 3.0 50.0 150.0 53.5 300.0 16050.0 90.0 8.0 720.0 4.0 1.0 4.0 10.0 10.0 100.0 12.0 1.0 12.0 8.0 50.0 400.0 5.0 100.0 500.0 120.0 1.0 120.0 6.0 2.0 12.0 60.0 2.0 120.0 20.0 1.0 20.0 120.0 20.0 2400.0 17300.0 30.0 5.0 150.0 15.0 5.0 75.0 8.0 100.0 800.0 250.0 1.0 250.0 250.0 1.0 250.0 10.0 20.0 200.0 11.0 20.0 220.0 10.0 20.0 200.0 13321.0 30621.0 |
| 23 | M&L for old size sub class \\"B\\" bricks laid in trenches as cable covers complete all as specified and as directed by Engr-in-Charge Please Enable Macros to View BoQ information 12.0 5.0 60.0 10.0 1.0 10.0 4.0 55.0 220.0 50.0 40.0 2000.0 4.0 20.0 80.0 60.0 35.0 2100.0 4.0 5.0 20.0 50.0 22.0 1100.0 5.0 1.0 5.0 50.0 25.0 1250.0 1.0 5.0 5.0 14.0 50.0 700.0 60.0 5.0 300.0 6.0 1.0 6.0 12.0 1.0 12.0 3.0 50.0 150.0 53.5 300.0 16050.0 90.0 8.0 720.0 4.0 1.0 4.0 10.0 10.0 100.0 12.0 1.0 12.0 8.0 50.0 400.0 5.0 100.0 500.0 120.0 1.0 120.0 6.0 2.0 12.0 60.0 2.0 120.0 20.0 1.0 20.0 120.0 20.0 2400.0 17300.0 30.0 5.0 150.0 15.0 5.0 75.0 8.0 100.0 800.0 250.0 1.0 250.0 250.0 1.0 250.0 10.0 20.0 200.0 11.0 20.0 220.0 10.0 20.0 200.0 13321.0 30621.0 |