| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mmFRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.a) Group C |
| 2 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)a) 8 way , Double door |
| 3 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single pole |
| 4 | b) Single pole and neutral |
| 5 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.a) 20 mm |
| 6 | b) 25 mm |
| 7 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface / recessed steel / PVC conduit as required.a) 3 x 1.5 sq.mm |
| 8 | b) 3 x 4 sq.mm |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 10 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V \\"C\\" curve TP MCB complete with connections, testing and commissioning etc. as required. |
| 11 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 63 A 415 V \\"C\\" curve TP MCB complete with connections, testing and commissioning etc. as required. |
| 12 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 13 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 14 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 15 | Supplying. Installation, testing and commissioning of 300 mm sweep metallic heavy duty 900 rpm exhaust fan suitable for operation on 230V, 50 Hz single phase AC supply complete with louvers / shutters in the existing opening including making the hole to suit the size of the above fan making good the damage and connections etc. as reqd. |
| 16 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.a) Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 17 | b) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 18 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. a) Above 35 sq. mm and upto 95 sq. mm |
| 19 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. a) 4 X 16 sq. mm (28mm) |
| 20 | c) 3½ X 50 sq. mm (35mm) |
| 21 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. a) 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 22 | Dismantling manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge :a) bituminous road/concerte path |
| 23 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 24 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level a) 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size de rived from natural sources) |
| 25 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer -in - charge. a) Nominal concrete 1:4:8 or leaner mix (including equivalent design mix) |
| 26 | Taking out existing CC interlocking paver blocks from footpath/ central verge, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in-Charge. |
| 27 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisationthickness not less than 50 microns) with perforationnot more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. a) 150 mm width X 50 mm depth X 1.6 mm thickness |
| 28 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required.a) 150 mm width X 50 mm depth X 1.6 mm thickness |
| 29 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. a) 150 mm width X 50 mm depth X 1.6 mm thickness |
| 30 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. a) 150 mm width X 50 mm depth X 1.6 mm thickness |
| 31 | Supply, installation, testing and commissioning of panel board with dust & vermin proof IP-42 protection compartmentalized indoor type cubical panel board made out of not less than 1.6 mm thick CRCA sheet, the sheet steel member shall be stiffened by angle iron framed. The depth of cubical panel shall not be less than 300 mm and suitable sizes earth strip shall be provided around the cubical panel. The cubical panel shall be of suitable size to incorporate following switchgear i/c connections, powder coating of approved colour and shades complete etc. as reqd. Panel should be fixed on CC foundation/ angle iron frame work. 250A, 25KA, 4P incomer MCCB-1 No.100A 4P 25KA outgoing MCCB-02 Nos.125A 4P 25KA outgoind MCCB-02 Nos. 32/40A DP 10KA MCB- 4 NosCT's 250/5A class-1.0 15VA-03 NosDigital MFM -1 NoR,Y,B Phase Indicating Lamp-03Nos400A TPN, Aluminium Bus BarExtended Rotating Handle & Spreader -05 Nos |
| 32 | Supplying. Installation, testing and commissioning of 600 mm sweep wall mounted heavy duty industrial fan suitable for operation on 230V, 50 Hz single phase AC supply and connections etc. as reqd. |
| 33 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder Coated CRCA Sheet Body (Thickness >0.50 mm) a) 36 watt |
| 34 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt).Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). a) 70watt Please Enable Macros to View BoQ information |