| 1 | M & L XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor. 11000 volts, grade cross sectional area 240 sq.mm. of 03 Core. Make:- Finolex/Polycab/Havells/KEI |
| 2 | M & L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sq.mm. Make:- Raychem/ 3M/ Mahindra. |
| 3 | M & L Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sq.mm. Make:- Raychem/3M/Mahindra. |
| 4 | M & L XLPE insulated, armoured heavy duty electric power cables with aluminium conductor. 1100 volts, grade cross sectional area 300 sq.mm. of 3.5 Core. Make:- Finolex/Polycab/Havells/KEI |
| 5 | S & F Earthing complete with galvanised steel earth plate electrode 600X600X6mm thick, burried directly in ground (earthpit not less than 2.25m deep below ground level) with top edge of the plate not less thanb 1.5m below normal ground level, connected to galvanised iron strip 32X6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised or steel all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion. Earth strip should be proiperly weld on the pole in cluding testing on completion and all as diredted by EIC. Exposed earth strip should be painted with green colour. |
| 6 | M & L earth continuity conductor or main earthing lead fixed to wall on batten or recess or buried in ground or drawn in conduit /pipe or fixed to poles or any other indicated situation for loop earthing etc. as require 32 X 6mm galvanised iron strip. |
| 7 | Supply & Laid dry old size brick work with sub-class B-Bricks straights or curved on plan exc 6m mean radius. |
| 8 | Excavation in trenches in soft /loose soil n.exc 1.5 mtrs wide and n.exc 1.5 mtr. Depth; for under grond cable and getting out including forming bottom surface to required level or slope as per standard mentioned in MES SSR Part-II for HT & LT cable. |
| 9 | Returning, filling including spreading, levelling, watering and well ramming in layers not exc 25 cm in hard/dense soil complete as specified & directed. Deduction may be done in case of non execution. |
| 10 | Supply , spreading & levelling of Ganga sand in trenches for cushioning of cable in layers not exc. 25cm thick as per standard mentioned in MES SSR Part-II for laying of cable. |
| 11 | M & L writing letters or figures (block, Roman, Italic, or Indian) of 6 cm of height but n.exc 30 cm high. Make of paint-Asian /Shalimar / Berger/ ICI Paint. |
| 12 | M & L for stops, commas, short lines, dashes, hyphens, brackets, etc. |
| 13 | M/L for priming of pipe/pole with red oxide zinc chrome surfaces of any description over 10 cm. In width or girth, not otherwise described. Make-Asian /Shalimar / Berger/ ICI Paint. |
| 14 | M/L for Synthetic enamel (ordinary tint) a coat on GI steel pipe pole surfaces of any desciption, over 10 cm. in width or girth, not otherwise and as directed by EIC. Make- Asian / Shalimar / Berger /ICI Paint |
| 15 | M&L Tubes, medium grade, galvanised laid in trenches of 100 mm. Bore dia. Make- TATA/SAIL/Jindal . |
| 16 | Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required and directed by EIC. |
| 17 | Boaring under the Road as replaced to insert upto 100 mm. GI pipe. |
| 18 | S & F cable tag, size 50 mm x 15 mm x 1 mm including fixing arrangement made up of stainless steel with necessary embossing as required and directed by EIC. |
| 19 | S& F of cable termination including with cable gland (ss) and necessary numbers of aluminium lugs at LT panel and overhead distribution line with jointing material and accessories suitable for 3.5 core PVC armoured aluminium conductor cable of size 300 Sqmm. Make-: 3M/Mahindra/Raychem. |
| 20 | M & L Heat shrink LT straight through joints for PVC / XLPE Al. cable kit5 suitable for 300 sq.mm X 3.5 core and as required & directed. Make- 3M/Mahindra/Raychem.. |
| 21 | Supply and Fixing of Switch Board Panel in modular design, sheet metal enclosure, free standing, air insulated, floor mounting and compartmentalized type suitable for indoor use with ON -Load changeover switch 630Amp,50KA, 4 pole and microprocessor base MCCB 630 Amp, 50KA 4 pole with over current and short circuit protection at incoming side and microprocessor based MCCB 400 Amp,50KA, 4 pole with over current and short circuit protection at outgoing side pre wired with suitable current rating, R-Y-B indication lamp at incoming side, three pahse panel voltmeter 10-300V (L-N), 18-520V (L-L), 3 Row, 4 digit display at incoming side and three phase panel ampere meter, 3 row, 4 digit display at out going side along with 400 Amp/5A CT, IP 54 degree of protection with polyurethene foam gasket. colours RAL-7035, Sheet thickness 2.0mm CRCA sheet for enclosure and mounting plate, 1.6 mm CRCA for doors & covers, 1.2 mm CRCA for separation plates., 4 point locking arrangement. Make- of MCCBs, Changeover switch, Ampere meter & Voltmeter- Lauritz Knudsen/C&S/ Schneider/ BCH/ABB/Legrand/Siemens. Make of CT-RISSABH/SELEC/AE/ABB/SIEMENS/AMREST. Please Enable Macros to View BoQ information |