| 1 | Supply and laying in trenches / ducts, passing through pipe / fixing on poles 1100 volts grade, ISI marked of size 150 Sqmm 3.5 core, LT cable (heavy duty), XLPE insulated served with an inner sheathing of PVC tape armoured with galvanized steel wire or tape and over all PVC sheathed with stranded aluminium conductor cable including commissioning and testing complete all as specified and directed.Note: (i) Necessary test results like continuity test, megger tests shall be submitted to Engineer-in-Charge before the cable is laid. (ii) Excavation & earth work will be measured and paid separately. |
| 2 | All as per Item No. 1 herein before but cable of size 95 sqmm, 3.5 core complete all as specified and directed. |
| 3 | All as per Item No. 1 herein before but cable of size 35 sqmm, 3.5 core complete all as specified and directed. |
| 4 | All as per Item No. 1 herein before but cable of size 16 sqmm 4core complete all as specified and directed. |
| 5 | M&L for LT cable straight through jointing kit heat shrinkable type suitable for XLPE/ PVC insulated cable of size 3.5 core, 70 sqmm to 120 sqmm complete including testing the cable joint for healthiness, cutting & removing unserviceable joint, preparation of both ends of cable to be joined with necessary stretching, alligning, making joint complete all as specified and directed |
| 6 | M&L for LT cable straight through jointing kit heat shrinkable type suitable for XLPE/ PVC insulated cable of size 3.5/4 core, 25 sqmm to 50 sqmm complete including testing the cable joint for healthiness, cutting & removing unserviceable joint, preparation of both ends of cable to be joined with necessary stretching, alligning, making joint complete all as specified and directed |
| 7 | Supply and Fixing of LED Street Light Fittings 70 Watt new generation energy saving and enviornmental friendly long life LED street light made up of pressure dia cast aluminium housing with high efficiency LED as lighting source and lens embedded PC cover having Bottom Opening seperate driver compartment with IP66 protection and impact resistance of IK08 complete with all acessories all as specified and directed. |
| 8 | M&L for Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized earth strip of 32X6mm size by means of bolts, nuts, check nuts and washers of galvanized iron or steel and connected from earth plate electrode to main switch board/ earthing test point including watering arrangement with PCC 1:3:6 type C1 chamber, MS funnel, wire gauge, 50mm thick precast RCC cover in Type B1, including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to a distance n.exc 50m, charcoal and salt complete all as shown in electrical plate No. 3 of SSR Part-I 2009 and connected to earthing test point all as specified and testing on completion as directed by EIC. |
| 9 | M&L for Horizontal Boring under hard standing/ pavements or roads manually using suitable auger for insertion of GI pipes up to 100 mm bore and making good the disturbed surface complete all as specified and as directed.Note: GI pipe will be measured and paid separately. |
| 10 | S&F GI tubes 80 mm bore dia light grade with all fittings laid in trenches or inserting in horizontal boring complete all as specified and as directed. |
| 11 | Supply, installation , testing and commissiong factory made LT Panel outdoor type platform mounted of size 1800 mm x 1200 mm x 450 mm suitable for 415 Volts 3 phase 4 wire system 50Hz supply having aluminum bus bar 600 Amps for phases and neutral, installed on porcelain / epoxy insulator. The panel shall be dust proof, vermin proof (IP54) and applying spray paintig with two coats of synthetic enameled paint over a coat of red oxide primer on sheet and made of out of 3.15 mm thick CRCA sheet self moulded type and 55x50x6 mm angle iron frame front and rear opening with double shutter and locking arrangement with 50mm lock and including grouting of panel with necessary PCC 1:2:4 type B-1 work complete all as specified and directed. The scope of work includes provision of housing the following acceessories:- |
| 12 | Incoming :- (i) MCCB having current rating 320 Amp 4 pole of breaking capacity 36 KA -01 No.(ii) Volt meter 0-500 Volts,Square flush pattern,digital type -01 No.(iii) Amp meter square flush pattern 0-600 Amps digital type-01 No.(iv) Indicating lamp LED type one set in incoming phases.(v) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 volts grade IS 694 marked.(vi) Alarm System for indicating the commercial power failure. |
| 13 | Outgoing : -(i) MCCB having current rating 160 Amp, 4 pole of breaking capacity 25 KA, 415 volts -02 Nos.(ii) MCCB having current rating 100 Amp, 4 pole of breaking capacity 25 KA, 415 volts -02 Nos.(iii) MCCB having current rating 63Amp, 4 pole of breaking capacity 25 KA, 415 volts -02 Nos. |
| 14 | Design, Supply, installation, testing and commissioning of outdoor type LT feeder pillar panel overall depth not less than 450mm depth, MS Channel Base Frame mounted (to be mounted on the 3 side covered brick pedestal of height 450 mm above ground level), suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos Aluminium bus bars of rating 400 Amps insulated, Provision of Spreader link to both incoming and outgoing side of MCCBs for termination of cables; LT panel shall be duly fabricated in an approved fabrication house having modern fabrication and testing facility which includes at least seven (07) tanks pre-treatment facility comprising of de-greasing, rinsing, de-rusting, rinsing, phosphating, rinsing and passivation followed by powder coated painting (thickness not less than 80 Micron) with approved shade of RAL 7032 (SIEMENS GRAY) |
| 15 | Incoming :- (i) MCCB having current rating 200 Amp 4 pole of breaking capacity 25 KA, 415 volts -01 Nos. (ii) Volt meter 0-500 Volts, Square flush pattern,digital type -01 No(iii) Amp meter square flush pattern 0-600 Amps digital type-01 No.(iv) Indicating lamp LED type one set in incoming phases.(v) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 volts grade IS 694 marked. |
| 16 | Outgoing :- (i) MCCB having current rating 100 Amp 4 pole of breaking capacity 25 KA, 415 volts -04 Nos. |
| 17 | Excavation in trenches in any type of soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide for laying of cables, RCC poles/stays and struts etc or /getting out cable cover and stacking for reuse/ credit, trimming sides and forming bottom surface all as specified and directed at site. |
| 18 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and directed. |
| 19 | Removing surplus excavated soil n exc 50 mtr and depositing where directed at a level n exc 1.5 mtr above the starting point complete all as specified and directed. |
| 20 | M&L for dry sand cushioning to underground cables with 8 cm thick before laying of cables and 15 cm thick after laying and stretching of cable complete all as specified and directed.Note:- Only punned thickness i.e. 18 cm shall be measured and paid. |
| 21 | M & L for sub class 'B' brick for covering to under ground cable laid flat transversally width equal to the length of the cable complete all as specified and directed. |
| 22 | Disconnecting and taking down aluminum conductor steel reinforcement (ACSR) of any size from existing over head line complete all as specified and directed. |
| 23 | Disconnecting and taking down cross arms of MS channel or angles sections etc of any size from existing over head line complete all as specified and directed. |
| 24 | Disconnecting and taking down insulators of any size from existing over head line complete all as specified and directed. Please Enable Macros to View BoQ information |