| 1 | Dismantling /disconnecting & taking down insulaters of any size & capacity, complete all as specified and as directed. |
| 2 | M&L for Pin type Porcelain, vitreous, white brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50mm height, 100 mm dia for 1100 volts grade, complete all as specified and as directed. |
| 3 | Loop type insulator, vitreous porcelain, white, brown or green large size, with overall dimensions 140mm, clearance of hole 25.5mm, complete all as specified and as directed. |
| 4 | S&F Steel tubular swaged poles complete with MS base plate Continuously welded to pole, finial taper plug, bolts, nuts & screws as specified type 410 SP- 55 (11 metres long ) includind two coat of black bituminous paint internally throughout and externally upto embedded portion and including applying two coats of synthetic enamel paint over a coat of red oxide primer with black and white strip of 30 cm each upto 1.5 m height and two coats of aluminium paint over a coat of red oxide primer externally on remaining exposed surface aftereraction in position incl prepration of surface, complete all as specified and directed.( earth work ,PCC and copping will be measured and paid for separately under respective item) |
| 5 | S&F Steel tubular swaged poles complete with MS base plate Continuously welded to pole, finial taper plug, bolts, nuts & screws as specified type 410 SP- 31 (09 metres long ) includind two coat of black bituminous paint internally throughout and externally upto embedded portion and including applying two coats of synthetic enamel paint over a coat of red oxide primer with black and white strip of 30 cm each upto 1.5 m height and two coats of aluminium paint over a coat of red oxide primer externally on remaining exposed surface aftereraction in position incl prepration of surface, complete all as specified and directed.( earth work ,PCC and copping will be measured and paid for separately under respective item) |
| 6 | M&L for Switch air break, gang operated triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps (12 Insulator) alongwith fuse system, complete all as specified and as directed. |
| 7 | M&L for Lighting arresters expulsion type complete with all fittings transmission class, discharge capacity 65KA , complete all as specified and as directed. |
| 8 | Dismantling old and unsv stay assy complete comprising of stay clamp, stay wire, stay insulator, stay grip, thimble, bow, stay rod 16 mm dia and stay plate etc including breaking of cement concrete, complete all as specified and as directed. |
| 9 | M&L for stay assembly complete with accessories as shown in electrical plate No 1 ( Loop type insulator, stay clamps excavation and concrete measured separately) 20mm dia including dismentling old and unsv stay assy complete comprising of stay clamp, stay wire, stay insulator, stay grip, thimble, bow, stay rod and stay plate etc including breaking of cement concrete, complete all as specified and as directed. |
| 10 | S & F in repair cross arms bracing supports, clamps and back plate fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat of red oxide zinc chrome, one under coat and one finishing coat of aluminum paint, complete all as specified and as directed. |
| 11 | M & L for cement concrete for foundation fillings and mass conctere type D2 1:4:8 using 40 mm graded aggregate, complete all as specified and as directed. |
| 12 | M & L for cement concrete for coping of poles using B1 1:2:4, 20 mm graded aggregate, smooth finishing without using extra cement, complete all as specified and as directed. |
| 13 | M & L for cement concrete for foundation fillings and mass conctere type C2 1:3:6 using 40 mm graded aggregate, complete all as specified and as directed. |
| 14 | Material and labour for earthing complete with galvanised steel earth plate electrode 60cmX60cmX6.0mm thick, buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5mtr below normal ground level connected to GI earth strip of size 32x6 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron complete earth pit of PCC M-10(Nominal mix) using 20mm graded stone aggregate, 50mm thick earth pit cover of RCC M-15 (Nominal mix) using 20mm graded stone aggregate with MS TMT reinforcement bar of 8mm dia @ 150mm centre to centre both ways, MS handle 10mm dia made to shape, GI funnel, wire mesh and 20mm bore GI water pipe light grade and 40mm bore light grade GI pipe for protection of earth strip from plate to main switch board, common salt, charcoal dust including testing on completion complete all as specified and as directed all as shown in electrical plate No. 3 including testing on completion and making good the disturbed surfaces of wall floors etc without claiming extra cost all as directed by Engr-in-Charge. (Note: GI strip & GI pipe beyond 7.5Mtr length from earth electrode shall be measured and paid separately). |
| 15 | M&L PVC spacer suitable for 3 wire HT OH line including taking down of old one, complete all as specified and as directed. |
| 16 | M&L PVC spacer suitable for 4 wire LT OH line including taking down of old one, complete all as specified and as directed. |
| 17 | M&L for digital volt meter Make AE/AGRON, with selector switch including mounting arrangement and connecting with LT panel, complete all as specified and as directed. |
| 18 | M&L for digital Amp meter 100 Amp Make AE/AGRON with set of 3 Nos CTs with CT ratio 100/5 including selector switch and mounting arrangement and connecting with LT panel, complete all as specified and as directed. |
| 19 | Dismantling old and unsv prestressed concrete poles/steel tublar poles of any type including breaking cement concrete, complete all as specified and as directed. |
| 20 | Painting to existing steel tubular LT poles, 9m long including cross arms, channels, angle iron support, bracings, clamps etc. with two coats of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white and black paint alternately on external surface above PCC benching including preparation of old painted surfaces by scraping etc complete and writing pole numbers. of 2 inches bold letters with black paint after painting, complete all as specified and as directed. |
| 21 | Supply and laying GI pipe 80 mm bore light grade with fitting for cable protection at road crossing/under concrete including taking down of old one, complete all as specified and as directed. |
| 22 | Supply and laying GI pipe 50 mm bore light grade with fitting for cable protection at road crossing/under concrete including taking down of old one, complete all as specified and as directed. |
| 23 | Supply and laying GI pipe 40 mm bore light grade with fitting for cable protection at road crossing/under concrete including taking down of old one, complete all as specified and as directed. |
| 24 | S&F MCCB 4 Pole, 415 V, fixed type, 63 Amps with breaking capacity 16 KA, complete all as specified and as directed. |
| 25 | S&F MCCB 4 Pole, 415 V, fixed type, 100 Amps with breaking capacity 16 KA , complete all as specified and as directed. |
| 26 | S&F MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA , complete all as specified and as directed. |
| 27 | S&F MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA, complete all as specified and as directed. |
| 28 | S&F MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA , complete all as specified and as directed. |
| 29 | M&L for XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete all as specified and directed of following sizes :- |
| 30 | (a) 3 ½ core 120 Sqmm |
| 31 | (b) 3 ½ core 95 Sqmm |
| 32 | (c) 3 ½ core 70 sqmm |
| 33 | (d) 3 ½ core 35 Sqmm |
| 34 | (e) 3 ½ core 25 Sqmm |
| 35 | (f) 2 core 16 Sqmm |
| 36 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level, complete all as specified and as directed. |
| 37 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm in hard/dense soil, complete all as specified and as directed. |
| 38 | Removing surplus exacavated material from excavation not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point, complete all as specified and as directed. |
| 39 | Supply and filling dry river sand in trenches including spreading for cushioning of LT UG cablec and punning down, complete all as specified and as directed.Note : Punned down thickness shall be measured and paid |
| 40 | M&L for well burnt as class ‘B’ bricks as mechanical protection to under ground cables laying with length of the bricks equal to the width of the trench, complete all as specified and as directed. |
| 41 | Supply and fixing on load changeover switch Range 400A, 415V, 4P, confirming to IEC 60947-3, IS/IEC 60947-3 Conforms to Staggered terminals, Site convertible fuse version for open execution Flip-able handle above 400A Interchangeable dual shaft position with site convertibility along with SS enclosure version require separate cable gland box, complete all as specified and as directed. |
| 42 | All as per item No.41 here in before but of capacity 200 Amp, complete all as specified and as directed. |
| 43 | All as per item No. 41 here in before but of capacity 100 Amp, complete all as specified and as directed. |
| 44 | All as per item No. 41 here in before but of capacity 63 Amp, complete all as specified and as directed. |
| 45 | S&F Lugs (Thimbles) all as specified and directed by Engr-in-Charge |
| 46 | (a) Suitable for 120 Sqmm XLPE UG Cable |
| 47 | (b) Suitable for 95 Sqmm XLPE UG Cable |
| 48 | (c) Suitable for 70 Sqmm XLPE UG Cable |
| 49 | (d) Suitable for 50 Sqmm XLPE UG Cable |
| 50 | (e) Suitable for 35 Sqmm XLPE UG Cable |
| 51 | (f) Suitable for 25 Sqmm XLPE UG Cable |
| 52 | (g) Suitable for 16 Sqmm XLPE UG Cable |
| 53 | (h) Suitable for 10 Sqmm XLPE UG Cable |
| 54 | Note:- Schedule of credit Rs 37,205.00 will be deducted from total amount quoted while accepting the bid. Details of schedule of credit is given in tender documents. Please Enable Macros to View BoQ information |