| 1 | Carrying out routine maintenance and servicing of LT distribution panel board having approximately 15 to 22 nos. of switches as scope of work |
| 2 | Carrying out routine maintenance and servicing of Standalone Small LT distribution panel board/ LT OR HT ATS /Starters/lighting/Isolation transformer as per scope of work |
| 3 | Carrying out routine maintenance and servicing of H.T/M.T.cubicle panels /Transformer& it's /DG & it's Room scope of work |
| 4 | Maintenance & Servicing of DP structure supplying GEB power to ONGC installations scope of work |
| 5 | Carrying out Routine Maintenance & Servicing of 66kv S/S switchyard as per scope of work. |
| 6 | Providing & Erecting of lightening arrestors on the DP structures with necessary hardware and connections to existing earthing strip complete in all respects in place of existing damaged part |
| 7 | Providing & erecting Drop Out Fuse Assembly 3 Phase of 11 KV, 200 A, complete with DO fuse link with necessary hardware, etc. |
| 8 | Providing & erection of new 11 KV, 400 A GOAB switch, 3 phase, complete after dismantling of existing GOAB switch in place of existing damaged part |
| 9 | Providing & Erecting of 100 A DO fuse link for 11 KV DO fuse unit in place of existing damaged part |
| 10 | Providing & Erecting of fuse barrel with metal parts for 11 KV DO fuse units in place of existing damaged part |
| 11 | Providing & Erecting of Top/bottom contact for 11 KV DO fuse unit in place of existing damaged part |
| 12 | Providing & Erecting of female contact for 11 KV GOAB switch in place of existing damaged part |
| 13 | Providing & Erecting of male contact for 11 KV GOAB switch in place of existing damaged part |
| 14 | Providing & Erecting of braided jumper (copper) for 11 KV GOAB switch in place of existing damaged part |
| 15 | Providing & Erecting of lightening arrestor on the 11 KV DP structures with necessary hardware and connections to existing earthing strip complete in all respects with Ratings 9KV, MCOV-7.65KV, NDC-10KA freq-50Hz |
| 16 | Complete job of providing, erecting, fabricating the M.S. structure as per requirement on DP structure frames installed at various ST installations incorporating proper size of M.S. flats supports made out of approx 40x 5 mm of appropriate length for fixing/supporting the insulator., complete with cutting, welding, grinding & finishing duly painted with one coat of red oxide and one coat Aluminum paint with erection on site as per direction of engineer in charge with necessary grouting, cementing, plastering & finishing complete. Job also includes supply & fixing of cylindrical insulators of not less than 40 mm height and 25 mm wide at appropriate distance (approx. 14 insulators for both earthings) on the above welded strips on each DP structure along with all necessary hardware & associated jobs to insulate both the earthing strips of LA from the DP / other metal structure as per CEA regulation 74(2) at various ST Installations. Job involves removal of LA earthing strips from pipes and refixing as per the CEA 74(2). The job shall also includes the removal of earthing strips passing through the pipes and handing over the pipes to EIC. |
| 17 | Painting by cleaning the surface and applying one coat of primer and two coats of Aluminum paint on each DP structures at ST installations |
| 18 | Providing cement concrete for foundation or for concrete filling in 1:2:4 ratio with 20 to 25 mm 5stone metal duly plastered with necessary curing for pole muffing or any other purpose. |
| 19 | Providing burnt brick masonry with 1:6 cement concrete duly plastered including watering stacking joint on exposed faces rocking at joints on exposed faces and watering complete |
| 20 | Providing and spreading the pea gravel at the Electrical Substation sites as per the instruction of E-I-C |
| 21 | Providing and erecting 11 KV D.P 9 mtr high Structure made of 6\\" x 3\\" \\"I\\"-Section Girder 4\\" x 2\\"channels clamps nuts bolts etc Suitable for erection of the followings duly connected with necessary ACSR conductors as per drawing approved by the Engineer- in charge complete with following Height as per IS 7 Mtr above ground (A) 11 KV 200 Amps Drop out fuses with S.R.B.P tubes carries-Three nos (B) 11 KV G.O.D switch complete with insulators operating handle with galvanised pipe Sqbar etc 400 Amp- One Set (C) 11 KV lightening arrestor with clamp- Three Nos (D) 11 KV shackle insulators- Six Nos (E) The above D.P structure should be earthed with 25 mmX 3 mm thick double copper earth strips run separately and connected with separate copper plate earth electrode as per scope of work |
| 22 | Supplying and erecting approved make Analog type voltmeter moving iron with square/ Round Dial flush/pedestal mounting pattern for A.CVoltage 0 to 500 Volt range erected on panel board with all connection wiring etc |
| 23 | Supplying and erecting approved make panel mounting type Digital Voltmeter having 3 digits LED display 0 to 750 AC Volts range erected on existing panel board with all connection wiring etc with manufacturers calibration certificate |
| 24 | Supplying and erecting approved make Analog type moving iron Ammeter direct reading type 0-30A AC current 500 V square / Round dial flush or projection type complete erected with connection and wiring |
| 25 | Supplying and erecting approved make panel mounting type Digital Ammeter having 3 digits LED display external CT operated calibrated for 0 to 1000 Amps suitable to operate on 500 Volt AC erected on existing panel board with all connection wiring etc with manufacturers calibration certificate |
| 26 | Supplying and erecting approved make Analog type moving iron C.T operated Ammeter A C Current suitable slide in scale 0-400 Amp with 3 Nos of Current Transformer erected on panel board with connections |
| 27 | Supplying and erecting Ammeter / Voltmeter selector switch for 3 phase AC Supply 500 V on existing panel board with necessary connections |
| 28 | Replacement of faulty RPM meter of DG/FWP Control Panels with new one |
| 29 | Providing & erecting L.T Current Transformer with bar primary 50/5 to 1000/5 ratio 15 VA burden erected in existing CRCA box duly secured with insulating materials connected to the meter |
| 30 | Supplying and erecting approved make suitable panel indicator lamps of LED type lamp lens cover Bakelite holder complete erected with necessary connections |
| 31 | Supplying & erecting directly operated single phasing preventer complete erected and connected to supply up to 45 Amp Range |
| 32 | Providing and installing \\"Digital multifunction panel mounting meter\\" for LT three phase feeder panel for measurement of voltage current active power reactive power frequency energy etc with feature like a) 3 line 4 digit display b) onsite CT prgramming for CT ratio with secondary as 1/5 Amp c) Size 96MM X 96 MM [Input 3PH 110V L-L Auxilliary 230V L-N AC] Cost of necessary panel fabrication job is included Please Enable Macros to View BoQ information |