| 1 | M&L and installation of PACKAGE AIR Cooling Units VC 40T Top Discharge comprising of 23000/40000 CFM/CMH Capacity: (a) 5” inch thick imported high efficiency cellulose pads on 4 sides.(b) Machine with high efficiency axial fan and Three-phase unit (c) Water pump in wet section, distribution water pipe, auto connection of water tank to quick fill water connection with ball valve, drain and overflow connection.(d) Engineering Plastic Body with dust filter (e) Power Consumption of 3 kW. (f) QTY PRICE (in INR) 06 2,20,338 AMOUNT (in INR) 13,22,034 Assembling, Installation, Testing and commissioning (SITC) |
| 2 | M&L and installation of Phase protector for VC 40T Model complete all as spcefied and directed by Engr-in-Charge. |
| 3 | M&L and installation of Canvass Connection - Fire retardant at machine outlet complete all as spcefied and directed by Engr-in-Charge. |
| 4 | Supply, Installation & testing of Galvanised Sheet FABRICATED DUCT as required at site with Connectors, GI Flanges, turning vanes, with proper duct sealing etc with RTV duct Sealant, Complete with supports as per the specifications. Design of duct should be approved by Engineer-in-Charge before commissioning. |
| 5 | 24 Gauge- FABRICATED Duct Sq.mt 150 1292 193800 |
| 6 | 22 Gauge- FABRICATED Duct |
| 7 | Double Louver Air Grills |
| 8 | Thermal Insulation 9 mm for exposed ducting |
| 9 | MS Fabrication Stand |
| 10 | Civil Work |
| 11 | Supply, Laying ,fixing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25.0 sq mm 4 core including cable tray required complete . |
| 12 | Supply, Laying ,fixing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16.0 sq mm 4 core including cable tray required complete . |
| 13 | Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts complete all as specified and directed by Engineer-in-Charge. |
| 14 | Supply and fixing MCCB, 415 volts, 3 pole of capacity 100 Amps, 16 KA, ICS= 100% ICU, class II front face,with thermal- Magnetic release, including spreader terminals, phase barriers, thimbles of suitable size etc, for connection to tap off box enclosure suitable for aluminium bus bar trunking of 400/250 Amps, 3 phase, 4 wire and making electric connections complete all as directed. |
| 15 | Supply and fix of MCB TPN 40 Amps 10 KA \\"C\\" series 415 Volt complete all as specified and directed by Engr-in-charge . |
| 16 | Supply and fix of MCB SP 6 to 32 Amp 10 KA \\"C\\" series 230 Volt complete all as specified and directed by Engr-in-charge. |
| 17 | M&L for Earthing complete with galvanised iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level connecting to GI wire 4 dia mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel and earth wire protected by 15mm dia GI pipe medium grade and connected to distribution board/earthing test point all as shown in electircal plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- (a) The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh,protection pipe, earth wire upto 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II. (b) Contractor must test/ensure Earthing resistance value less tham 5 Ohm and Submit Earth test result to Engr-in-Charge. |
| 18 | Material and labour for PCC 1:4:8 Type D2 (40mm graded stone aggregate) as in base concrete for DG set foundation complete all as specified and directed. |
| 19 | Material and labour for PCC 1:2:4 Type B1 (20mm graded stone aggregate) including necessary form work for DG set foundation complete all as specified and directed. |
| 20 | Supply , testing and commissioning of Tower AC 4/4.5 Ton 3 star rating having room air conditioner, electric driven, 3 Phase working with eco friendly refrigerant R-410A indoor size 1100x258/310mm outdoor size 845x300x595mm complete all as specified and directed. |
| 21 | Supply and fix servo voltage stabilizer for automatic operatins three phase naturally air cooled indoor type & designed for input variation between 300 to 450 V with output voltage stablized at 415 volts and speed of correction 8 volts per second and capacity of 10 KVA suitable for 4 Ton AC complete all as specified and directed. |
| 22 | Cutting and screwing of existing steel tubing for alterations or additions of size 50 mm done in position without taking down and inserting tee branch connection complete all specified and directed by Engineer-in- charge. |
| 23 | M&L for Tubes, 'medium grade' galvanised, with all fittings and fixed complete to walls and ceilings or laid in floors of 40mm bore complete all as specified and derected. |
| 24 | M&L for Tubes, 'medium grade' galvanised, with all fittings and fixed complete to walls and ceilings or laid in floors of 25mm bore complete all as specified and derected. |
| 25 | M&L for Tubes, 'medium grade' galvanised, with all fittings and fixed complete to walls and ceilings or laid in floors of 15mm bore complete all as specified and derected. |
| 26 | Supply and fix of Gun-metal, gate valves, with iron wheel head, screwed both ends for iron pipe ov sizes 40mm and fixed complete all as specified and directed. |
| 27 | Supply and fix of Gun-metal, gate valves, with iron wheel head, screwed both ends for iron pipe ov sizes 25mm and fixed complete all as specified and directed. |
| 28 | Supply and fix of Gun-metal, gate valves, with iron wheel head, screwed both ends for iron pipe ov sizes 15mm and fixed complete all as specified and directed. |
| 29 | S&F of rotational moulded polyethylene cylindrical vertical with closed top water storage tank Triple layered WHITE COLOUR 1000 Ltr capacity with connecting nipple, hoisted and fixed in position on new or existing foundation and making GI tubing inlet or outlet connection, with and incl disconnecting and dismantling the existing un-serviceable PVC/RCC water tank on top of roof/slab of bldgs, complete all as specified and directed. Please Enable Macros to View BoQ information |