Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Supply, laying jointing and testing LT UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured IS 7098 marked, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 Sqmm 3 core, laid in trench / laid under floor or fixed naked with wall / on wall / in ducts / in GI pipes etc. with and including MS Clamps, nuts, bolts, washers complete all as specified and directed. Note- Excavation, earth works, sand cushioning, protection bricks / pipe shall be measured and paid seprately. |
| 2 | All as per item No 01 above but LT UG cable of size 10 Sqmm 4 core. |
| 3 | All as per item No 01 above but LT UG cable of size 16 Sqmm 4 core. |
| 4 | All as per item No 01 above but LT UG cable of size 25 Sqmm 3.5 core. |
| 5 | All as per item No 01 above but LT UG cable of size 35 Sqmm 3.5 core. |
| 6 | All as per item No 01 above but LT UG cable of size 50 Sqmm 3.5 core. |
| 7 | All as per item No 01 above but LT UG cable of size 70 Sqmm 3.5 core. |
| 8 | All as per item No 01 above but LT UG cable of size 95 Sqmm 3.5 core. |
| 9 | All as per item No 01 above but LT UG cable of size 120 Sqmm 3.5 core. |
| 10 | All as per item No 01 above but LT UG cable of size 240 Sqmm 3.5 core. |
| 11 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 metre deep in soft / loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom surface to required level all as specified and directed by Engineer-in-Charge. |
| 12 | Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick using excavated soil complete all as specified and as directed. |
| 13 | Removing excavated soil n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed. |
| 14 | M & L for dry Sand cushioning in trenches for protection of cable including watering and consolidation all as specified and directed.Note: Punned thickness (18 cm) shall be consider for measurement purpose |
| 15 | M&L laying well burnt old size bricks, sub class \\"B\\" bricks, straight or curved on plan, laid flat with width equal to length of brick, laid dry over electric cable for protection complete all as specified & directed by Engr-in-Charge. |
| 16 | M&L for 40 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge. |
| 17 | M&L for 50 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge. |
| 18 | M&L for 80 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge. |
| 19 | M&L for PCC 1:2:4 type B1 using 20 mm graded stone agregrate as in coping of electric pole including necessary form work, finishing the exposed surface even & smooth and demolition of old coping complete all as specified and directed. |
| 20 | Supply, fixing, connecting and testing in replacement MCCB 100 Amp 3 pole 25 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 21 | Supply, fixing, connecting and testing in replacement MCCB 125 Amp 3 pole 25 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 22 | Supply, fixing, connecting and testing in replacement MCCB 160 Amp 3 pole 25 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 23 | Supply, fixing, connecting and testing in replacement MCCB 200 Amp 3 pole 36 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 24 | Supply, fixing, connecting and testing in replacement MCCB 250 Amp 3 pole 36 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 25 | Supply, fixing, connecting and testing in replacement MCCB 400 Amp 3 pole 36 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 26 | Supply, fixing, connecting and testing in replacement MCCB 100 Amp 4 pole 25 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 27 | Supply, fixing, connecting and testing in replacement MCCB 125 Amp 4 pole 25 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 28 | Supply, fixing, connecting and testing in replacement MCCB 160 Amp 4 pole 25 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 29 | Supply, fixing, connecting and testing in replacement MCCB 200 Amp 4 pole 36 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 30 | Supply, fixing, connecting and testing in replacement MCCB 250 Amp 4 pole 36 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 31 | Supply, fixing, connecting and testing in replacement MCCB 400 Amp 4 pole 36 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 32 | Supply, fixing, connecting and testing in replacement MCCB 630 Amp 4 pole 36 KA 415 volts 50 Hz adjustable thermal & fixed magnetic release with spreader, MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design, including taking down old existing unserviceable MCCB complete all as directed. |
| 33 | Supply and errection in replacement 07 mitre continuously tapered hot dip galvanised Octagonal cross sectional pole with single dipping method having bottom 130 mm A/F and top 70 mm A/F 3 mm thick confirming to ASTM A 572 Gr with yield 450 mpa cut and folded to form an octagonal section and welded in accordance with AWS for wind loading as per IS 875 part 3 1987.Poles shall be provided with base plate of size 225x225x12 mm which shall be free from any lamination or incursion with no cutting or welding on the pole after hot dip galvanising with single arm 1000 mm long bracket tilted to 150 degree from horizontal toward vertices suitable for mounting on the octagonal pole, of company recommendation and one no TPN Connecton 3 phase 4 wire 100 Amps, and one number MCB SP 6 Amps. A triangular flat MS plat of 6mm thick duly coated with GI shall be welded between cap of the octagonal pole and bracket. Welding work shall be done 250mm on bracket and 150 mm on pole's cap including all RCC work type (1:2:4) type B-1 including 04 Nos foundation nut bolt and plate as per pole manufacturer's drawing and earth work all as per requirement complete all as specified and directed. |
| 34 | M&L for renewal of Earthing complete with galvanised mild steel earth plate electrode 600 x 600 x 6.0 mm thick, buried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipment's at another end, |
| 35 | Item No 34 Contd.........GI earth strip encased in and including 40 mm dia GI 'light grade' pipe from upper end of earth plate upto equipments,20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as described in electric plate of SSR Part I complete.Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. |
| 36 | Supply and fix in replacement bollard light 60 cm long 10 - 12 watt LED Bollard light having epoxy powder coated pressure die cast aluminium housing Light optic /Diffuser - High impact polycarbonate/Optic colour temprature 5700K CRi>70,THD<10% PF >.90 surge protection 4KV inbuilt ,Rated voltage and frequency 240 Volt,50 Hz street furniture with touch if aesthetic innovative design with uniformly lit diffuser at the upper portion acts a beacon of path guidance in a landsscape IP 65 environmental complete with foundation work nut, bolt and washer etc complete all as specified and directed by Engr in Charge. |
| 37 | Supply and fix in replacement 25 Watt LED Post Top lanterns housing made of Die-cast aluminum spigot for mounting LED driver and Integral dome type white coloure plastic body , epoxy powder coated matt black finish after phosphochromate treatment , high quality polycarbonate cover is used over LED moudule to enhance the lumen output & clear acrylic diffuser is used to provide overall glare free light , Powered by electronic integral , isolated poted electronic LED driver in ABS housing with APFC (SMPS based constanct current supply) with lower THD , output short/open circuit protection , Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec-13 , IP 65 , Lumen efficiency not less than 98 lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70% |
| 38 | Supply, installing, testing and commissioning in replacement factory made , tested , CPRI approved powder coated Timer panel board (Dimension of Cubical/enclosure not less than 600 mm x 450 mm x 450 mm), cubical compartmentalized, out door type double door, plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain / SMC insulator. The timer panel shall be dust and vermin proof IP-54 class protection and outer shell made of 3.00 mm CRCA MS sheet, inner shell made of 2.0 mm thick CRCA MS sheet , 40 x 40 x 6 mm thick MS angle iron frame work, the cubical have bottom support of angle iron 50 x 50 x 6mm duly coated with zink metal coating, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size ( but not less than 2.5 Sqmm) and comprising of the following :- |
| 39 | (a) Incoming :-(i) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 16 KA, with thermal magnetic release - 01 Nos(ii) 3 pole power contractor AC 3 rating 40 Amp, 240 Volt AC -01 Nos(iii) Astronomical Digital Timer Switch 240 V AC -01 Nos(iv) Digital VAF+PF meter with RS 485 Cl-1 -01No (v) CTs ratio 100/5 A ,class 1, ISI marked -01 sets of three (vi) Indicating lamp- 01 set of three(vii) Four Pole , Aluminium bus bar 150 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators.(b) Outgoing(i) MCCB 4 pole, 40 Amps, 50 Hz,415 Volts, 16 KA thermal magnetic release - 02 Nos |
| 40 | Note - Platform of panel fixed with PCC 1:4:8 type D-2 with 40 mm graded crushed stone ,15 cm thick in foundation, brick work in CM 1:6 with sub class B old size bricks, rendering 15 mm thick in CM 1:6 on exposed surface and 100 mm thick PCC padding 1:3:6, type C-1 using 20mm graded crushed stone aggregate on Top and grouting bolts etc for panel. The plate form shall be such that it is of a height 45 cm above the nearest road level. All out going feeder shall be connected by cable through suitable size gland plate / glands. All MCCB with adjustable protection for over load and short circuit protection and confirming to IEC60947-II/IS 13947 -II (Latest Version). The MCCBs shall have spreader links and barriers as standard feature of manufacture. |
| 41 | Supply, installation, testing and commissioning in replacement outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 2 mm thick CRCA sheet, powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 2.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase comprising following switch gears controls:- |
| 42 | (a) Incomer (a) MCCB 4 pole, 630 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No (b) Voltmeter with selector switch of range 0-500V - 01 No(c) Ammeter with selector switch of range 0-500Amps - 01 No(d) Indicators lamps - 01 Set of three(e) CT/PTs of suitable range - 01 No(f) TPN Aluminium bus bar with colour code insulation. |
| 43 | (b) Out going(a) MCCB FP 400 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No(b) MCCB FP 250 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(c) MCCB FP 200 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100% - 01 No |
| 44 | Note for MCCB : All incoming & outgoing MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design. |
| 45 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 46 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f) Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 47 | Supply, installation, testing and commissioning in replacement outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 2 mm thick CRCA sheet, powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 2.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase comprising following switch gears controls:- |
| 48 | (a) Incomer (a) MCCB 4 pole, 630 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos (b) Voltmeter with selector switch of range 0-500V - 01 No(c) Ammeter with selector switch of range 0-500Amps - 01 No(d) Indicators lamps - 01 Set of three(e) CT/PTs of suitable range - 01 No(f) TPN Aluminium bus bar with colour code insulated |
| 49 | (b) Out going(a) MCCB FP 250 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 No(c) MCCB FP 125 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100% - 02 No |
| 50 | Note for MCCB : All incoming & outgoing MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design. |
| 51 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 52 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f) Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 53 | Supply, installation, testing and commissioning in replacement outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 2 mm thick CRCA sheet, powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 2.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase comprising following switch gears controls:- |
| 54 | (a) Incomer (a) MCCB 4 pole, 320 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos (b) Voltmeter with selector switch of range 0-500V - 01 No(c) Ammeter with selector switch of range 0-500Amps - 01 No(d) Indicators lamps - 01 Set of three(e) CT/PTs of suitable range - 01 No(f) TPN Aluminium bus bar with colour code insulated |
| 55 | (b) Out going(a) MCCB FP 160Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(b) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(c) MCCB FP 63 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos |
| 56 | Note for MCCB : All incoming & outgoing MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design. |
| 57 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 58 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f) Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 59 | Supply, installation, testing and commissioning in replacement outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 2 mm thick CRCA sheet, powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 2.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase comprising following switch gears controls:- |
| 60 | (a) Incomer (a) MCCB 4 pole, 320 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos(b) Voltmeter with selector switch of range 0-500V - 01 No(c) Ammeter with selector switch of range 0-500Amps - 01 No(d) Indicators lamps - 01 Set of three(e) CT/PTs of suitable range - 01 No(f) TPN Aluminium bus bar with colour code insulated |
| 61 | (b) Out going(a) MCCB FP 200 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No(b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No(c) MCCB FP 125 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos |
| 62 | Note for MCCB : All incoming & outgoing MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design. |
| 63 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 64 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f) Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 65 | Supply, installation, testing and commissioning in replacement outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 2 mm thick CRCA sheet, powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 2.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase comprising following switch gears controls:- |
| 66 | (a) Incomer (a) MCCB 4 pole, 250 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos(b) Voltmeter with selector switch of range 0-500V - 01 No(c) Ammeter with selector switch of range 0-500Amps - 01 No(d) Indicators lamps - 01 Set of three(e) CT/PTs of suitable range - 01 No(f) TPN Aluminium bus bar with colour code insulated |
| 67 | (b) Out going(a) MCCB FP 160 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(b) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No |
| 68 | Note for MCCB : All incoming & outgoing MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design. |
| 69 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 70 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f) Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 71 | Supply, installation, testing and commissioning in replacement outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IEC-61439 (Part - 1 & 2) of 2020 suitable for 415V, 3 phase, 4 wire 50 Hz supply system fabricated from 2 mm thick CRCA sheet, powder coated RAL 7032 shade, dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar of rating 1.5 times of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 2.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase comprising following switch gears controls:- |
| 72 | (a) Incomer (a) MCCB 4 pole, 630 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos(b) Voltmeter with selector switch of range 0-500V - 01 No(c) Ammeter with selector switch of range 0-500Amps - 01 No(d) Indicators lamps - 01 Set of three(e) CT/PTs of suitable range - 01 No (f) TPN Aluminium bus bar with colour code insulated |
| 73 | (b) Out going (a) MCCB FP 250 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(c) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos |
| 74 | Note for MCCB : All incoming & outgoing MCCB shall have either double make double break with Arc Chute per pole or single break independent cassette type design. |
| 75 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 76 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f) Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 77 | M&L for out door type busbar panel board (Dimension of Cubical / enclosure not less than 900 mm x 600 mm x 450 mm) made out of 3.00 mm thick MS sheet and MS angle section 50 x 50 x 6 mm factory made suitable for 3 phase 4 wire 415 Volt, 50 Hz, powder coat painted comprising of the following:- (a) FP, Aluminium bus bar 200 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators.(b) Incoming MCCB 125 Amps 25 KA, ,Ics=100%Icu 415 Volts, 50 Hz, FP with either double make double break with Arc Chute per pole or single break independent cassette type design. – 1 No |
| 78 | Item No 44 Contd........(c) LED Indicator lamp RYB - 01 set of three.(d) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 79 | Material & Labour for preparation of old painted surface of steel tubular pole 9 meter long above coping) and applying two coat of aluminium paint, making of strip of 20 cm width (BLACK and white in alternate band) up to 1400 mm height with one synthetic enamel paint , rewriting pole No by painter with enamel paint, and painting the existing MS clamp with one coat of aluminium paint complete |
| 80 | M&L for preparation of old painted surface of LT panel by scrapping, making good disturbed surfaces by applying putties on uneven surface to make it even and M&L for spray painting to LT panel of any size with two coat of synthetic enamel paint with desired colour complete all as specified and directed. |
| 81 | S&F in repair off load change over switch, 63 Amps, 415 volts, 4 pole side handle type in sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting / jointing materials and dismantling of existing change over switch, complete. |
| 82 | S&F in repair offload change over switch, 200 Amps, 415 volts, 4 pole in sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting / jointing materials and dismantling of existing change over switch, complete. |
| 83 | S&F in repair off load change over switch, 400 Amps, 415 volts, 4 pole side handle type in sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting / jointing materials and dismantling of existing change over switch, complete. |
| 84 | Supply & fix in repair LED RGBW flood lighting luminaire for facade lighting with Die-cast aluminium housing, powder-coated finish, Clear toughened glass of 4 mm thickness, of Total System wattage 45 W with system lumen output 2379 lm with all LEDs on, minimum system lumen efficacy 55 lm/w. Luminaire shall be capable of producing dynamic colour changing light with 16 million colours as the light fixture should be programmable using 8 bit control DMX512 protocol / Ethernet based control. Luminaire should be complete with dedicated Lens made up of UL / VDE approved PC for each LED, offering beam angle of different types such as narrow, medium, wide or elliptical as per the site requirement. Fixture should have Height 276 mm±5% including surface mount base width 183 mm±5% , length 320 mm ±5% with constant locking hinges for simple position control from various angles without special tools. Fixture shall be suitable to operate at an ambient temperature range of -30°C to 50°C .............. |
| 85 | Item no 50 Contd ............... and complete luminaire shall be IP 66 and IK07 rated. LED Life time shall be at least L70B50 @ 70000 burning hours at 50°C. LED should be with ceramic package of make Nichea, Osram, Cree, Limited only. DMX enabler circuit should be inside the Luminaire only. DMX enabler circuit should be inside the Luminaire only. Luminaire shall be complete with integrated BIS IP 66/67 potted driver and capable of operating at line voltage from 90-305 Vac, 50Hz with power factor > 0.9. The product should be BIS approved with R number mentioned on product label. To be supported with Product test reports - LM79, BIS Report and LEDs Test Reports. Luminaire shall be conforming to BIS i.e. IS 10322 (Part 5/Sec 5) and shall be complete with all necessary accessories required for proper working of fixture including weather proof connection cables, water proof connectors etc. as required. |
| 86 | Deployment of manpower & tools / machinery for fault finding in UG cable by disconnecting faulty 1.1 KV LT cables of different sizes from both ends, testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, Re-connections and testing of cables after removal of fault complete all as specified and directed.Note: (a) 1.1 KV LT cable & joints will be measured and paid for separately under respective items of BOQ (b) Contractor or his rep shall come to the site of breakdown within one hour of notification of breakdown along with fault locating machine and manpower. In case the rep or contractor not come to the site of breakdown and start attending breakdown within 1.00 hour a penalty of Rs 1000 per fault per hour will be imposed over contractor and will be deduct from his dues. |
| 87 | S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 / 4 core, 10 to 16 Sqmm XLPE armoured aluminium conductor cable.Note:- Excavation and earth work, extra cable if required will be measured & paid seperatly under respective items of this BOQ. |
| 88 | S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 / 4 core, 25 to 50 Sqmm XLPE armoured aluminium conductor cable.Note:- Excavation and earth work, extra cable if required will be measured & paid seperatly under respective items of this BOQ. |
| 89 | S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 core, 70 to 120 Sqmm XLPE armoured aluminium conductor cable.Note:- Excavation and earth work, extra cable if required will be measured & paid seperatly under respective items of this BOQ. |
| 90 | S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 core, 150 to 185 Sqmm XLPE armoured aluminium conductor cable.Note:- Excavation and earth work, extra cable if required will be measured & paid seperatly under respective items of this BOQ. |
| 91 | S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 core, 240 to 300 Sqmm XLPE armoured aluminium conductor cable.Note:- Excavation and earth work, extra cable if required will be measured & paid seperatly under respective items of this BOQ. |
| 92 | S&F in repair HT Danger notice plate of size 250 mm x 20 mm made of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, including taking down old one complete. |
| 93 | M&L for preparation of old painted surface of HT 4 pole / two pole structure of steel tubular pole 11 metre hight from bottom to top, including all steel cross arms / clamp etc and applying two coat aluminium paint, including painting Red / yellow / blue alternate strip up to 1.5 metre height from top of PCC coping with one coat synthetic enamel paint, and rewriting pole Number with one coat black synthetic enamel paint complete all as specified and directed.Note;- Each pole with cross arm and clamp will be measured as one unit for payment. |
| 94 | Deployment of manpower / tools / machinery for Periodical servicing of air circuit breaker and disconnecting the electrical connection from unserviceable parts and taking out the unserviceable part from the ACB and supply and fix the new part as per existing make / model / capacity incl cleaning and greasing fixed and movement parts etc complete. Note :- (i) All unserviceable spare part will be measured & paid separately under relevant item of this BOQ(ii) Unit rates quoted by tenderers shall deem to include for, bolts, washers, lugs, thimble, wires and petty items required for efficient and smooth functioning of the equipment without any extra cost. |
| 95 | Supply only Shunt release |
| 96 | Supply only Under voltage release |
| 97 | Supply only Earth fault release |
| 98 | Supply only Remote fault indicator |
| 99 | Supply only Microswitch for indication |
| 100 | Supply only lockable trip push bottom |
| 101 | supply only locking ACB in isolating position |
| 102 | Supply only locking ACB in any position |
| 103 | Supply only racking interlock |
| 104 | Supply only door interlock |
| 105 | Supply only machinal operation counter |
| 106 | Supply only Mounting kit for front mounted counter |
| 107 | Supply only spring charge indication microswitch |
| 108 | Supply only racking pad lock assembly |
| 109 | Supply & fix in repair Microprocessor based three phase electronic tamper proof, CT operated, energy meter for LT supply with optical communication port, accuracy class 0.5 voltage 3 x 240 V, 1/5 A conforming to IS: 13779.all as specified and directed by Engr-in-Charge |
| 110 | Supply & fix in repair microprocessor based three phase electronic tamper proof, energy meter of rating 10 to 60 Amp with optical communication port conforming to IS: 13779 all as specified and directed by Engr-in-Charge |
| 111 | Supply & fix in repair Microprocessor based Single phase electronic temper proof energy meter of rating 10 to 60 Amp with optical communication port, conforming to IS: 13779. all as specified and directed by Engr-in-Charge |
| 112 | Supply & fix Mufasa 10 Watts Black Body Outdoor Corded Electric 220 Volts LED Rainproof Wall Lamp Long Distance Straight Beam Spot Light, Aluminium Body (Warm White / White) , 10W LUMINAIRES and powder coated body all as specified as directed by Engr-in-charge. |
| 113 | S&F in replacement whether proof pole mounting junction box, base and door of junction box made out of SMC having outside dimension 333x233x120mm, inside dimension 300x200x105mm , single door front openable provided with hinged cover and locking arrangements with 4 Nos aluminium bas bar 63 Amps, mounted on porcelain insulator including M&L for MCB SP 10-1No, fixed on box in Din rail complete with electrical connection fixed to pole with suitable size FI clamp nut bolts and washer including embossing/painting of danger notice of size not less than 10cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of junction box body Complete all as directed by Engr-in-Charge Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy