| 1 | S & F automatic viscous filter oil type (SAE- 30 oil) with following technical specifications:- (a) Capacity : 120000 CMH (b) Face Velocity : 2.5m/sec(c) IPD: 4.0 mm WG(d) FPD : 10.0 mm WG(e) Efficiency : 90% down to 10 micron(f) Mat Height : 3000mm(g) Overall size : 4300 X 4000mm(h) Make of the motor : Kirloskar 1.0 HP-02 Nos(i) Duty cycle : 30 sec on & 12 mint offMake of the Gearbox : Kirloskar |
| 2 | Notes:- (i) The Rate quoted shall include taking down old viscous filter and depositing it to the AGE E/M MES store Yard (Dolphin Hill)(ii) SAE 30 oil shall be measured and paid separately in relevant items.(iii) The coated rate includes Dismentling of old foundation and S&F new foundation, foundation nut, bolts, washers,excavation, removing of soft soil and PCC, Cement Concrete foundation, filling and mass concrete type B2 (1:2:4) using 20 mm graded aggregate of size (as per site required ) for placing of automatic viscous filter or as per OEM recommendations complete all as specified and directed.(iv) Any other items which are not mentioned in the description of this item or not specified in the tender documents but the same are required for smooth operation of automatic viscous filter oil type shall be provided by the contractor without any extra cost to the Department.)(v) The drawings of the Viscous Filter should be approved by the Accepting Officer before placing order by the contractor.(vi) Contractor shall visit the site and check the dimensions facilitating easy entry / exist and installations, meeting existing conditions conforming to safety codes, before submitting the drawings for approval. |
| 3 | S & F Centrifugal belt type air blower and Motor with following Technical Specifications:- (a) Air Flow (CFM) : 65000(b) Static Pressure (mmWC): 60(c) Working Temp. (Deg.C): 40(d) BHP at Working: 31.1(e) BHP at 20 deg.C: 33.5(f) Total efficiency (%): 81.90%(g) Motor HP/Pole/RPM: 40.0/4/1450(h) Drive Arrangement: Belt driven(i) Fan RPM: 480(j) Impeller Type: Backward Curved(k) Impeller Dia.(mm): ~1430(l) Impeller Balancing As per ISO: 1940,Grade 2.5 |
| 4 | (m) Fan Testing As per IS 4894(n) Vibration Level As per ISO 14694:2003E-BV3(o) Noise Level: 85+4 dB (I/L & O/L Ducted)(p) Impeller (BP/BL/FP): M.S., (10/3/3)(q) Hub : M.S./C.I(r) Shaft : EN-8(s) Casing : M.S., 3mm(t) Fan Pedestal : M.S.(u) Base Frame : M.S. ( as per site required)(v) Anti Vibration Isolators : Polybond(w) Inlet Damper : M.S.(x) Expansion Bellow at Outlet : Silicon(y) Bearing DE & NDE : SKF-22218-EKC3(z) Plummer Block DE & NDE : Masta-SN518(aa) Fan Pulley : Fenner-4 SPB 600(ab) Motor Pulley : Fenner-4 SPB 400(ac) Belt : Fenner-SPB 4 Nos(ad) Belt Guard : M.S. |
| 5 | (ae) Hardware : STD(af) I/L &O/L Matching Flanges : M.S.(ag) Drain Plug and Socket : STD(ah) Inspection Window : M.S.(ai) Shaft Seal : Aluminium plate type(aj) Painting : Epoxy-BlueMotor Details:-(a) Make : Hindustan / Kirloskar / CG(b) Motor HP/Pole/RPM : 40.0/4/1450(c) Motor Specifications : IP55, 415V/3ph/50 Hz, IE-3(d) Motor Specifications : IP55, 415V/3ph/50 Hz, IE-3(e) Motor Mounting : Foot Mounted |
| 6 | Notes:- (i) The Rate qouted shall include taking down old blower, motor and depositing it to the AGE E/M MES store Yard (Dolphin Hill ). (ii) The coated rate includes Dismentling of old foundation and S&F new foundation, foundation nut, bolts, washers,excavation, removing of soft soil and PCC, Cement Concrete foundation, filling and mass concrete type B2 (1:2:4) using 20 mm graded aggregate of size (as per site required ) for placing of Centrifugal belt type air blower and Motor or as per OEM recommendations complete all as specified and directed. (iii) The Rate qouted shall include connected existing duct any required items. (iv) Any other items which are not mentioned in the description of this item or not specified in the tender documents but the same are required for smooth operation of Centrifugal belt type air blower and Motor shall be provided by the contractor without any extra cost to the Department.)(v) The drawings of the blower should be approved by the Accepting Officer before placing order by the contractor.(vi) Contractor shall visit the site and check the dimensions facilitating easy entry / exist and installations, meeting existing conditions conforming to safety codes, before submitting the drawings for approval.(vii) The factory acceptance test shall be carried out by the rep of Accepting Officer prior to dispatch. Contractor shall inform the dates to the GE well in advance for factory inspection. |
| 7 | Supply and filling SAE 30 oil complete all as specified and as directed. [Make shall be Castrol / Servo / HPCL as approved by GE] |
| 8 | S&L XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured ,electric power cables heavy duty with aluminium conductor, 1100 Volts grade of size 3.5 core 120 Sqmm complete in trenches/ ducts/ on pole etc including taking down existing unserviceable cable complete all as specified and as directed . |
| 9 | Excavation in trenches not exceeding 1.5m wide and not exceeding 10 Sq.m on plan area and not exceeding 1.5m deep in Soft / Loose soil complete all as specified and as directed. |
| 10 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick of excavated soil complete all as specified and as directed. |
| 11 | Removal of surplus excavated material of any type not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point. complete all as specified and as directed |
| 12 | M&L for Sand cushioning/sand covering for underground cable protection/substation yard complete all as specified and as directed[Note: Punned thickness only will be measured and paid.] |
| 13 | Supply and laying sub class 'B' bricks of old size (standard size as per local availability) laid along alignment of cable as protection to cable in trenches complete all as specified and as directed |
| 14 | M&L for GI pipe light grade 80 mm dia for cable protection on road crossings /plinth protection with fixed to the pole wall etc. suitable fittings for cable protection .complete all as specified and as directed |
| 15 | Supply and fix 3 core 4 sqmm PVC copper cable multi stranded drawn through PVC conduit of suitable size medium grade including providing necessary lugs complete incl taking down the existing wire complete all as specified and as directed |
| 16 | Supply and fix 3 core 10 sqmm PVC copper cable multi stranded drawnthrough PVC conduit of suitable size medium grade including providing necessary lugs complete incl taking down the existing wire complete all as specified and as directed. |
| 17 | Supply, fabricate, install, testing and commissioning of LT feeder panel board of suitable size, out door type double door, dust and vermin proof made out of 3.15 mm thick MS sheet mounting on suitable size foundation with 150 mm thick PCC (1:3:6) type C 2 with 100 mm offsets and panel board with front and back opening and locking arrangement compete two coats of finishing powder coated paint of approved shade over one coat of red oxide primer including horizontal copper busbar of suitable size for three phase 4 wire including comprising of the following accessories and fitted in including taking down old panel board with foundation complete all as directed:-(a) Incomming: (i) ACB 4 pole 50 KA,630A thermal magnetic release manual drawout type -01 No(b) Outgoing: (i) MCCB,3P,16KA,100 Amp fixed type-03 Nos,(ii) MCCB,3P,16KA,63 Amp fixed type-03 Nos, (iii) 2HP DOL Starter-03 Nos,(iv) 40HP ASD Starer-03 Nos(iv) Digital panel meter for Amp,Volt,KWH,power factor and other parametre Flush mounting of size 96x96 mm rent,power,energy,THD along with connected CTs-03 Nos(v) Phase Indicator (R, Y & B) -03 Sets (vi) Copper Bus Bar 1000Amp icl PVC sleeves for three phase with neutral supply-01 Set |
| 18 | M & L for Earthing complete with galvanised steel earth plate electrode 60cm×60cm×6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth strip 32×6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion. |
| 19 | Supply,assembly and erection of GI sheet with TDF Flange rectangular/ square duct made out of 'L' shaped hollow profile, duly factory boxed, incl all accessories such as Corner, Cleat, Carriage bolt, Gasket and appropriate sealant on longitudinal joints etc complete of size of 24 Gauge including taking down existing unserviceable GI sheets complete all as specified and as directed.[Note: The rate quoted shall be deemed to be inclusive for necessary civil works such as PCC and connected works for fixing of ducts / channels and making good to disturbed surfaces of wall, floors, etc to match with existing specifications] |
| 20 | M&L for rolled mild steel angles, bars, flats etc., as in supports for stiffening of fencing, wall ties, hold fasts, clamps and similar small articles confirming to Fe 410-W (Gde.E-250), quality-A including suitable size anchor fasteners completely grouted in wall at any height for supporting the Air ducts including applying two coats of synthetic enamel paint over a coat of red oxide primer including dismantling complete all as specified and as directed.[Note: The rate quoted shall be deemed to be inclusive for necessary civil works such as PCC and connected works for fixing of ducts / channels and making good to disturbed surfaces of wall, floors, etc to match with existing specifications] Please Enable Macros to View BoQ information |