| 1 | Material, Laying , connection, testing and commissioning for Automation system for sequencial monitoring and controlling 06 Nos VCBs, RMU for operating of HT 11 KV VCB in Auto mode by electric supply availability, fault current sensing , operating of incomer VCB in Auto mode. The system shall consist the following items complete all as specified and directed by Engr-in-Charge:-1) panel Box with made out of 2mm thick CRCA sheet stand made out of angle iron including programming for automatic ON/OFF operation of VCB and provision of operation in manual mode.2) PLC type 32DI/24DO repairs-1Set3)HMI display7\\" - 1 Nos.4) Communication Module RS 485 serial communication- 1 No.5) Energy meter with RS 485 indicating all Electrical Parametres including PVC flexible copper conductor cable PLC of type - 7 Nos.6) Main Switch 32 A - 1No.7) Control MCB 6A - 21 Nos.8) Relay Module including all accessories - 3 Nos.9) Power Supply Module 24 VDC 5A - 1 No.10) Fan 4\\"- 1 No. |
| 2 | 11) Ventilation Fan Filter 4\\" - 2 Nos.12) Cable tray as per requirement.13) Din Rail - as per requirement14) Control Wire 1.5 Sqmm 2 core as required.15) Power Cable 2.5 Sqmm as required 16) Power Trminals as required.17) Control Terminals as required including internal controll limits.18) Programming of PLC as per site requirement for automatic/ manual mode operation of VCB for ensuring power supply change over based on supply availability all as directed at site.19) Field wiring 1Sq.mm 2 core cable with glands, lugs, connectors, conduit as per requirement of suitable lugs for connection with existing VCB & ACB20) Power Cable of multi core copper conductor with glands, lugs, connectors, conduit as per requirement of suitable lugs for connection with existing VCB & ACB (21) all safety precaution and connection should be as per IE rules. (22) All connection & operational sequention and time lag for switching should be as per user reqmt accordingly CAT II mode of operation (23) Integration of ACBs/VCBsyo suit emergency power feed to MAFI PS-II includng selection and supply with conformity to interlock suitability for normal and CAT-II modes of operation for specific direction of power feeds. |
| 3 | Supply, install, commission and test Ring Main Unit (RMU) HT 11 KV Outdoor Extensible type, cubical 3 Way (2 I/C VCB + 1 O/G VCB) gas (SF6) insulated comprising with incomer - 2 Nos. X VCB and outgoing - 01 NOs X VCB of rating of each 630 Amp 3 phase 50 cycle 12 KV, 20 KA/3 sec ambeint temprature (-5 degree celsius to +55 degree celsius ) . Manual operated SF6 breaker having copper bus bar 600 Amp rating cast resin tank with , LV current transformer compatible with self powered relay & 11 KV resin cast PTs (one set of 3 Nos.) with seprate metering chamber complete make- SIEMENS model 8 DJH ST/ euivalent in makes specified in Appendix \\"B\\" Makes of Particular Specifications.. Each Circuit breaker will have the following- (i) Manually operated SF6 VCB 3 phase 630 A, 12 KV rating circuit breaker having resin cast tank and earthing switch with full making capacity with position ON-OFF - Earth (ii) Manual line disconnector with three position switches ON-OFF -Earth (iii) Anti reflex operating handle (iv) Auxiliary switches 3 No. +3 NC with wiring |
| 4 | (v) Shunt trip coil (230 V AC) for external trip signal (vi) Self powered O/C + E/F relay protection 3 phase definite time over current and short circuit protection with selectable inverse time characteristics and definite time short circuit currrent element ( ANSI 50/51) , definite Make- WIB Woodward AVK SEG/ equivalent (vii) Live cable indicating LEDs energised through capacitive voltage dividers (viii) cable box suitable for cable termination of 1 No , 3 CX 120 Sqmm XLPE cable |
| 5 | Accessories with each RMU includes-(i) Operating handle -01 Nos(ii) Right angled cable boots make- Siemens/equivalent - 03 Sets(iii) Capacitive voltage indicator type HR-ST-Make Hortsmann - 03 Nos separate metering chamber having -(i) 3 phase 3 limb drawout type bus connected epoxy potential transformer ratio 11 kv/root3/110V/root 3 AC accuracy 1.0 burdon 50 VA-01 9ii) Digital type voltmeter -01 Nos.(iii) RYB indicator- SetsNOTE-(i) RMU shall be outdoor plinth mounted (ii) Erection commissioning and civil work (plinth protection) for RMU is deemed to be included with unit rates. The plinth protection details as per the manufacturer instruction after approval of drawing from GE.(i) Cable terminals cable bushing situated not beyond 300 mm or as per OEM tested design from cable cover to allow ease for installation/testing /*replacement purposr) with door arrangement for enhanced safety (IP 54+IP3X) interlocke to prevent access up to 11 KV, 185 Sqmm 3 core alongwith XLPE AL cable termination each set of 03 |
| 6 | (iii) Right angle boots (push on type) each set of 3(iv) 3O/C +1 E/F self powered numerical protection relay with low and high set for overcurrent and earth fault. relay should have facilities to display maximium loaded phase current also. relay shall record minimum 5 fault records with time stamping . Relay shall be communicable with RS 485 port on MODBUS protocol-01 No. /per VCB (v) Relay for OTI/WTI/B - relay protection-01 No.(vi) Associated ring core cast -resin insulated CTs 50/1 Amps 2.5 VA 10 P 10 protection - each set of 3 (vii) Arc proof cable cover having cable entry from bottom , front with interlocking mechanism including earth switch -01 No.(viii) Capacitive voltage indication fixed type system as per IEC 6123 with LED -01 set(ix) ON OFF Earth mechanical indication on the front mimic of the panel - 01 No.(x) Emergency trip push button -01 Nos. |
| 7 | 01 No bus connected fixed- type auxilary transformer with floor mounted compartment of matching height and depth positioned alongside RMU to provide required aux supply for spring charging motor and metering consisting of following accessories.(i) 3 ph ( 11 KV/root 3) ; 230 volt AC 500 VA auxilary transformer -01 No. alongwith trivector meter 2X12 Volt DC battery -01 Set(iii) Battery charger with power pack -01 No. with indication of status of functioning (iv) HRC fuses links for primary side isolation and AC/DC supply availability -01 Set(vi) anti condensation space-heater -01No.(vii) LED lamp for illumination and 3 pin socket with switch-01 No.(viii) Enclosure- powder coated camouflage (ix) Complete RMU must be scada compatible(x) Separat cable entry box must be mounted with RMU system(D) Standard mano meter -01 for each tank operating handle -2 , cable clamping provision (standard) -01 / for every cable entry operation and maintenance manual-01, installation and commissioning manual-01, Foundation as per OEM recommendation (earth work and PCC works) for placing RMU on plinth is deemed to be included in the cost quoted . Height of plinth should not be less than 0.60 mtrs from ground level. Please Enable Macros to View BoQ information |
| 8 | 01 No bus connected fixed- type auxilary transformer with floor mounted compartment of matching height and depth positioned alongside RMU to provide required aux supply for spring charging motor and metering consisting of following accessories.(i) 3 ph ( 11 KV/root 3) ; 230 volt AC 500 VA auxilary transformer -01 No. alongwith trivector meter 2X12 Volt DC battery -01 Set(iii) Battery charger with power pack -01 No. with indication of status of functioning (iv) HRC fuses links for primary side isolation and AC/DC supply availability -01 Set(vi) anti condensation space-heater -01No.(vii) LED lamp for illumination and 3 pin socket with switch-01 No.(viii) Enclosure- powder coated camouflage (ix) Complete RMU must be scada compatible(x) Separat cable entry box must be mounted with RMU system(D) Standard mano meter -01 for each tank operating handle -2 , cable clamping provision (standard) -01 / for every cable entry operation and maintenance manual-01, installation and commissioning manual-01, Foundation as per OEM recommendation (earth work and PCC works) for placing RMU on plinth is deemed to be included in the cost quoted . Height of plinth should not be less than 0.60 mtrs from ground level. Please Enable Macros to View BoQ information |