Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Dismantling and taking down of old ACSR conductor complete all as specified and directed by Engr-in-Charges. |
| 2 | Supply, laying, testing & commissioing of 120 Sqmm 3.5 core size XLPE insulated, PVC sheathed, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, IS 7098 Part I marked, suitable for LT 1100 Volt system,laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe including jointing & testing complete all as specified and directed by Engr-in-Charges. Note :- Excavation, earth work ,cable protection , sand fillings shall be measured and paid separately under respective items of schedule. |
| 3 | All as per Ser No 2.00 above but size 95 sqmm 3.5 core complete all as specified and directed by Engr-in-Charges. |
| 4 | All as per Ser No 2.00 above but size 70 sqmm 3.5 core complete all as specified and directed by Engr-in-Charges. |
| 5 | All as per Ser No 2.00 above but size 50 sqmm 3.5 core complete all as specified and directed by Engr-in-Charges. |
| 6 | All as per Ser No 2.00 above but size 35 sqmm 3.5 core complete all as specified and directed by Engr-in-Charges. |
| 7 | All as per Ser No 2.00 above but size 25 sqmm 4 core complete all as specified and directed by Engr-in-Charges. |
| 8 | All as per Ser No 2.00 above but size 16 sqmm 4 core complete all as specified and directed by Engr-in-Charges. |
| 9 | All as per Ser No 2.00 above but size 10 sqmm 4 core complete all as specified and directed by Engr-in-Charges. |
| 10 | All as per Ser No 2.00 above but size 10 sqmm 2 core complete all as specified and directed by Engr-in-Charges. |
| 11 | Material and labour plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate as in base of the pole as a foundation or in any situation complete all as specified and directed by Engr-in-Charges. |
| 12 | Material and labour plain cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of the pole by demolition of existing /broken coping with taking out the LT cables and GI pipe Etc and refixing in new coping or in any situation complete all as specified and directed by Engr-in-Charges. |
| 13 | Excavation in trenches in soft/ loose soil n.exc 1.5mtr wide and not exc 1.5mtr in depth and getting out complete all as specified and directed by Engr-in-Charges. Note:- Work will executed in Govt Md Accn/inside Depot Area. necessary excavation may be done manually/JCB as reqd on site and directed by Engr-in -Charge. |
| 14 | All as per item No 13 here in before but exc 1.5 mtr or part there of in depth beyond the first 1.5 mtr depth complete all as specified and directed by Engineer-in-Charge. |
| 15 | M&L for tibba sand locally available sand filling in trenches dry and clean sand unwashed including punning around cable for protection of under ground cable complete all as specified and directed by Engr-in-Charges. |
| 16 | M&L for laying jodhpur stone quarry stone slab cover 25 to 30 cm in width, 60cm long and 40 to 50 mm thick laid in trenches and over sand covered under ground cables complete all as specified and directed by Engr-in-charge. |
| 17 | Returning, filling, in including spreading, leveling , watering and well ramming in layers n.exc 25 cm in soil complete all as specified and directed by Engineer-in-Charge. |
| 18 | Removing excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtrs above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 19 | Supply and laying of GI Pipe light grade 80 mm dia with necessary accessories under the road for cable protections for crossing of culverts/nallah and complete all as specified and directed by Engr-in-Charges. |
| 20 | Supply and fixing of GI Pipe light grade 50 mm dia with necessary accessories/ fittings bracing with pol/wall by FI clamps made with 32x6mm for cable protections/pole for crossing of culverts/nallah and complete all as specified and directed by Engr-in-Charges. |
| 21 | M&L for Cutting the road / hard standings/Interlocking bricks and excavating in trenches not exceding 0.40 mtr wide and not exc 0.80 mtr deep across the road for laying cable/pipe including making good the excavated portion by means of PCC 1:2:4, type B1 using 20mm graded stone aggregate complete and matching with the surroundings complete all as specified and directed by Engr-in-Charges. |
| 22 | Supply and errecting in replacement of Prestressed concrete pole, 9.0 meter long, 102mm x 152mm at top and 102mm x 289mm at bottom, class 10 including painting alternative black & white strips of 30 cm width upto 1.5 mtr above ground level and including dismantling and taking out the damaged/old PCC pole and setting aside within 50 mtr distance and complete all as specified and directed by Engr-in-Charges. |
| 23 | S&F in replacement of LED street light fitting 70 Watt made out of pressure die cast aluminium powder coated housing high impact resistant 4mm thick toughened glass cover and matrix of power LEDs inbuilt electronic driver up to 10 KV surge protection fitted with adjustable pole adapter to enable on site tilt angle setting depending on road geometry CCT 5700-6000 CRI greater than 70, IP 66, PF >0.95,THD < 5%,input power 70 W system with 120 lumens per watt output operating voltage 160-260V complete all as specified and directed by Engr-in-Charges. |
| 24 | Supply and Fixing of pole mounted junction box of inside dimension 240x130x110 made out of FRP body (hot mulded type) with IP-55 protection and locking with screws alongwith 5/6 Amp rating MCB SP-01 No, 4 pole connector suitable to insert the cable size up to 16 Sqmm-01 No,with neutral link and din rail suitable for mounting the MCB/Connector etc complete in side box and duly fixed on steel tubular pole/PCC/RCC pole including cable glands, aluminum lugs/thimbles for incoming and out going cales and complete all as specified and directed by Engr-in-Charges. |
| 25 | Supply & fixing of PVC insulated, sheathed weather proof, copper conductor of size 1.5 sqmm, 3 core complete all as specified and directed by Engr-in-Charges. |
| 26 | Supply & fixing of PVC conduit 20 mm, heavy duty rigid non metallic including of all tee, bends, elbows etc complete all as specified and directed by Engr-in-Charges. |
| 27 | S&F in replacement of 32 mm dia GI pipe bracket (medium grade) bent to shape of length not less than 1.2 mtr including fixing on pole using flat iron 25x3 mm size clamps 2 Nos of suitable size nuts,bolts,washers etc includig paint of two coats of alluminium paint over one coat of red oxide primer suitable for street light fittings complete all as specified and directed by Engr-in-Charges. |
| 28 | M&L of earthing with Galvanised Steel earthplate of size 60x60cmx6mm thick electrode and 32x6mm GI strip as earth lead, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to 32x6mm earth strip by means of nuts, bolts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I, connected to earth test terminal point all as specified or as indicated including testing on completion (Rates inclusive of neccessary excavation in any type of soil, earth work, PCC pit, CI cover, funnel with watering pipe, suitable size of light grade GI Protection pipe for earth strip in ground etc. complete all as specified and directed by Engr-in-Charges. |
| 29 | M&L of GI strip of size 32x6 mm including mounting on PVC/Porcelain insulators on wall and burried in ground depth not less than 60 cm in ground complete all as specified and directed by Engineer-in-Charge. |
| 30 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 600 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 400 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 315 Amp 36 KA thermal adjustable type -01 Nos, MCCB 4P 100 Amp 16 KA thermal adjustable type-02 No, MCB TPN 415 Volt 10 KA 'C' 40 Amp -01 Nos,Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 31 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 200 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 125 Amp 16 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 63 Amp 36 KA thermal adjustable type -01 Nos, MCB TPN 415 Volt 10 KA 'C' 40 Amp -02 Nos,Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 32 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 100 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 63 Amp 16 KA thermal adjustable type OUTGOING :- (i) MCB TPN 415 Volt 10 KA 'C' 40 Amp -02 Nos,Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 33 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 500 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 315 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 200 Amp 36 KA thermal adjustable type -01 Nos, MCCB 4P 160 Amp 36 KA thermal adjustable type-01 No, MCB TPN 415 Volt 10 KA 'C' 40 Amp -02 Nos,Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 34 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 100 Amp 16 KA thermal adjustable type -01 Nos, MCB TPN 415 Volt 10 KA 'C' 40 Amp -04 Nos,Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 35 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 150 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 100 Amp 16 KA thermal adjustable type OUTGOING :- (i) MCB TPN 415 Volt 10 KA 'C' 40 Amp -03 Nos,Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 36 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 63 Amp 16 KA thermal adjustable type-01, MCB TPN 415 Volt 10 KA 'C' 40 Amp -05 Nos, MCB SPN 230 Volt 10 KA 'C' 40 Amp -01 Nos,Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 37 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 400 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 250 Amp 36 KA thermal adjustable type OUTGOING :- (i)MCCB 4P 200 Amp 36 KA thermal adjustable type-01, MCB TPN 415 Volt 10 KA 'C' 40 Amp -02 Nos, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 38 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i)MCCB 4P 160 Amp 36 KA thermal adjustable type-01, MCB TPN 415 Volt 10 KA 'C' 40 Amp -02 Nos, MCB SPN 230 Volt 10 KA 'C' 40 Amp -01, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) |
| 39 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 400 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 250 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 200 Amp 36 KA thermal adjustable type-01, MCCB 4P 160 Amp 36 KA thermal adjustable type-01, MCB SPN 230 Volt 10 KA 'C' 40 Amp -01, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 40 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 250 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 160 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 100 Amp 16 KA thermal adjustable type-01, MCB TPN 415 Volt 10 KA 'C' 40 Amp -03, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 41 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 100 Amp 16 KA thermal adjustable type-02, MCB TPN 415 Volt 10 KA 'C' 40 Amp -03, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 42 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 150 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 100 Amp 16 KA thermal adjustable type OUTGOING :- (i) MCB TPN 415 Volt 10 KA 'C' 40 Amp -02,MCB SPN 230 Volt 10 KA 'C' 40 Amp -01, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 43 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor typeIP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 500 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 315 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 200 Amp 36 KA thermal adjustable type - 01, MCCB 4P 100 Amp 16 KA thermal adjustable type - 01, MCB TPN 415 Volt 10 KA 'C' 40 Amp -01, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 44 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 150 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 100 Amp 16 KA thermal adjustable type OUTGOING :- (i) MCB TPN 415 Volt 10 KA 'C' 40 Amp -02, MCB SPN 230 Volt 10 KA 'C' 40 Amp -01 Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 45 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 160 Amp 36 KA thermal adjustable type - 01, MCCB 4P 125 Amp 16 KA thermal adjustable type - 01, MCB TPN 415 Volt 10 KA 'C' 40 Amp -02, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 46 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 250 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 160 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 100 Amp 16 KA thermal adjustable type - 01, MCB TPN 415 Volt 10 KA 'C' 40 Amp -04, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 47 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 200 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 125 Amp 16 KA thermal adjustable type OUTGOING :- (i) MCB TPN 415 Volt 10 KA 'C' 40 Amp -04, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 48 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 400 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 250 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 160 Amp 36 KA thermal adjustable type - 01, MCCB 4P 125 Amp 16 KA thermal adjustable type - 01, MCB TPN 415 Volt 10 KA 'C' 40 Amp -02, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 49 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 250 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 160 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 125 Amp 16 KA thermal adjustable type - 01, MCB TPN 415 Volt 10 KA 'C' 40 Amp -02, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 50 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) 4 Nos 300 Amps aluminium bus bar, MCB SPN 230 Volt 10 KA 'C' 40 Amp -01, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 51 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 63 Amp 16 KA thermal adjustable type -01 Nos, MCB TPN 415 Volt 10 KA 'C' 40 Amp -06, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 52 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 1000 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 630 Amp 50 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 315 Amp 36 KA thermal adjustable type -01 Nos, MCCB 4P 250 Amp 36 KA thermal adjustable type -02 Nos, MCCB 4P 200 Amp 36 KA thermal adjustable type -01 Nos, MCCB 4P 125 Amp 16 KA thermal adjustable type -01 Nos, MCB TPN 415 Volt 10 KA 'C' 40 Amp -01, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 53 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 500 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 315 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 200 Amp 36 KA thermal adjustable type -01 Nos, MCCB 4P 125 Amp 16 KA thermal adjustable type -01 Nos, MCB TPN 415 Volt 10 KA 'C' 40 Amp -04, MCB SPN 230 Volt 10 KA 'C' 40 Amp -01,Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 54 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 160 Amp 36 KA thermal adjustable type -01 Nos, MCCB 4P 100 Amp 16 KA thermal adjustable type -01 Nos, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 55 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 150 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 100 Amp 16 KA thermal adjustable type OUTGOING :- (i) MCB SPN 230 Volt 10 KA 'C' 40 Amp -04, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 56 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 400 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 250 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 200 Amp 36 KA thermal adjustable type -01 Nos, MCB TPN 415 Volt 10 KA 'C' 40 Amp -02, MCB SPN 230 Volt 10 KA 'C' 40 Amp -01 Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 57 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 125 Amp 16 KA thermal adjustable type -01 Nos, MCB TPN 415 Volt 10 KA 'C' 40 Amp -04, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 58 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 125 Amp 16 KA thermal adjustable type -02 Nos, MCB TPN 415 Volt 10 KA 'C' 40 Amp -02, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 59 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 400 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 250 Amp 36 KA thermal adjustable type OUTGOING :- (i) 4 Nos 400 Amps aluminium bus bar, MCB SPN 230 Volt 10 KA 'C' 40 Amp -01, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 60 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 400 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 250 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 200 Amp 36 KA thermal adjustable type -01 Nos, MCCB 4P 125 Amp 16 KA thermal adjustable type -01 Nos, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 61 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 300 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 200 Amp 36 KA thermal adjustable type OUTGOING :- (i) MCCB 4P 100 Amp 16 KA thermal adjustable type -01 Nos, MCB TPN 415 Volt 10 KA 'C' 40 Amp -06, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 62 | Supply and installation, testing and commissioning LT feeder pillar box suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC Supply outdoor type IP-65 floor mounting along with factory made type panel weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15 mm thick having Aluminium bus bar of rating 150 A, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. All the covers shall be provided with suitable locking arrangements, mounted on angle iron stand fixed at 75 cm made out of angle size 50 X 50 X 6 mm grouted in PCC 1:3:6, and comprising of the following controls gears INCOMING:- MCCB 4P 100 Amp 16 KA thermal adjustable type OUTGOING :- (i) MCB TPN 415 Volt 10 KA 'C' 40 Amp -04, Digital type volt meter & Amp Meter, LED type Indicating Lamp (03 Nos) complete all as specified and directed by Engr-in-Charges. |
| 63 | Material and labor for edging the machine cut /true dressed jodhpur stone patty of size 30 cm in width, 60 cm long and 50 mm thick, to make edge aroung the LT Panels and complete all as specified and directed by Engr-in-Charges. |
| 64 | Supply and laying the graded coarse aggregate 40mm size for loose filling around the LT Panels surface dressing and cleaning the vegetation before spreading the gravel and complete all as specified and directed by Engr-in-Charges. |
| 65 | Supply and fixing the LT Cable route indicator made by Jodhpur stone well finished and marking of letter \\"DANGER LT Cable MES\\", size 100mmx10mm, 75cm long, 15cm grouted with 1:3:6 PCC foundation below the ground level and 60cm of marker will be elevated on ground. letters of \\"DANGER LT Cable MES\\" will be painted with post office red colour and with black colour background and complete all as specified and directed by Engr-in-Charges. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail