| 1 | Supply, erection and commissioning of 7.5Cs Axial/Mixed flow VT Pump having 40 meter working head along with required bends and delivery pipe (thickness 8mm and length approx 4mtr) complete in all respect as per site requirement and as per approved specification of the deptt. |
| 2 | Supply, erection and commissioning of Solid shaft induction Motor 225HP squirrel cage LT 3 phase 415V for continuous duty, vertical flange mounted, suitable for above mentioned 7.5Cs pump complete in all respect as per site requirement & as per approved specification of deptt. |
| 3 | Supply, erection and commissioning of 1000 Amp Motor Control Center/ LT Panel as per IP-54 with 01no incomer ACB of 1000 Amp and 03no outgoings having 03no MCCB of 630 amp/4pole alongwith an additional plug & socket having MCB of 63 Amp for lighting loads on front of cabinet, indicators, relays, meters, push buttons, bus bars and with 03no fully Automatic ATS Starters (complete in all respect like relays, indicators timer etc) of 03no 250HP capacity with minimum contactor ratings of 550, 400 & 265 amp with designed Capacitor bank of (minimum 160 KVAR capacity with minimum 04 step APFCR), suitable size MCCB, Selector Switch, duty contractors, discharge resistors, digital display instruments & other allied accessories for automatic as well as manual operation of Capacitor Bank suitable for 02no 225HP LT motors as per design of Motor Control Centre with a stand of MS Channel/angle (1 feet height from floor level) with IP-54 protection & as per approved specification of deptt. (as per Annexure-C) at PH No 1. |
| 4 | Supply, errection and commissioning of LT cable Single core - 1000 Sq mm Aluminium Conductor, XLPE insulated, Armored cable from Transformer to Motor Control Centre as per approved specification of the deptt. |
| 5 | Supply, errection and commissioning of LT cable Single core - 630 Sq mm Aluminium Conductor, XLPE insulated, Armored cable from Transformer to Motor Control Centre as per approved specification of the deptt. |
| 6 | Providing and fixing cast iron double flanged swing check type reflux (non return) valve of required diameter/400mm PN-1.6 marked with IS:5312 including nuts and bolts marked with IS:1363, rubber sheet marked with IS:638 etc (Makes- Kirloskar, IVC Nasik Vag). Complete in all respect as per site requirement. |
| 7 | Providing and fixing C.I. sluice valve of required diameter/400mm along with bolts, nuts, rubber insertions etc (Makes- Kirloskar, IVC Nasik Vag). Complete in all respect as per site requirement. |
| 8 | Supply and fixing of delivery head (with 630mm pipe dia, 08mm thickness approx length 08 mtr along width of pump house) connecting all the delivery pipes of 03no 7.5Cs pumps further conecting it with HDPE pipe line of 630mm dia.. |
| 9 | Providing and fixing cast iron double flanged swing check type reflux (non return) valve of required diameter/630mm PN-1.6 marked with IS:5312 including nuts and bolts marked with IS:1363, rubber sheet marked with IS:638 etc (Makes- Kirloskar, IVC Nasik Vag). Complete in all respect as per site requirement. |
| 10 | Providing and fixing C.I. sluice valve of required diameter/630mm along with bolts, nuts, rubber insertions etc(Makes- Kirloskar, IVC Nasik Vag). Complete in all respect as per site requirement. |
| 11 | Providing and fixing CI/MS flange for connecting MS delivery pipe to HDPE pipe line of 630mm OD along with bolts, nuts, rubber insertions etc. Complete in all respect as per site requirement. |
| 12 | Providing and fixing of Lightening Arrester with protection radius of 50mtr along with earthing arrangement as per proper specification for pump house building and transformer as per the site requirement at pump house 1. |
| 13 | Providing and fixing of chemical earthing by digging suitable bore and depth pit for LT Panels complete with copper electrode, copper strip for all panels complete in all respect as per site requirement. |
| 14 | The above rates are inclusive of all kind of taxes including GST and other expences like F.O.R. destination and inclusive of all incidental charges, enroute & at destination. Nothing extra shall be paid separately.Terms & Conditions as mentioned in Bid document in Price Schedule. Please Enable Macros to View BoQ information |