| 1 | Supply, installation, testing and commissioning of 11kV Outdoor type Fuse type 4 way Ring Mains Unit consisting of 2Nos. 11kV 630A Load Break Switches only for Incoming & 2 Nos. 11kV 630A Load Break Swithes with suitable 11kV HRC Fuses along with suitable Terminal arrangement ( With 1 Set Spare 11 KV HRC Fuses) to connect atleast 300sqmm 3 Core 11kV HT Cable. The RMU shall be Extendible type suitable for Outdoor Installations & Fabricated out of 2mm thick CRCA Sheet Steel duly painted with PowderCoated Paint, The Bus Bar shall be 630A Auminum & shall duly supported by 12kV Grade Epoxy Inulators suitable to bear teh jerks of Shorth Circuit 25kA for 1 Sec. The job shall be completed in all respect including suitabe Foundation for Installation of RMU Complete with all required meterial and T&P etc. as per direction of E/I. |
| 2 | Supply, installation, testing and commissioning of 11kV Outdoor type Fuse type 5 way Ring Mains Unit consisting of 2Nos. 11kV 630A Load Break Switches only for Incoming & 3 Nos. 11kV 630A Load Break Swithes with suitable 11kV HRC Fuses along with suitable Terminal arrangement ( With 1 Set Spare 11 KV HRC Fuses) to connect atleast 300sqmm 3 Core 11kV HT Cable. The RMU shall be Extendible type suitable for Outdoor Installations & Fabricated out of 2mm thick CRCA Sheet Steel duly painted with PowderCoated Paint, The Bus Bar shall be 630A Auminum & shall duly supported by 12kV Grade Epoxy Inulators suitable to bear teh jerks of Shorth Circuit 25kA for 1 Sec. The job shall be completed in all respect including suitabe Foundation for Installation of RMU Complete with all required meterial and T&P etc. as per direction of E/I. |
| 3 | Supply of aluminum conductor 11 KV(E) XLPE cross linked polythene) over all served cable with flat galvanized steel strip armouring at a depth of 2 to 3 mtr. Below ground level in laid HDPE Pipe on surface the cable run shall be fixed on M.S. clamp etc. of suitable size proper completion work. Make (Polycab/ Gloster/Sterlite/Torrent/L.S. Cable/ Havells) |
| 4 | 300 Sqmm 3 core |
| 5 | S/F and jointing of Indoor11 KV jointing kit (Heat Sink) per XLPE cable including cost of all material Labour and T & P as per proper completion of work as per direction of E/I. Make (Raychem/3M) as per DSR 2022 S.No.10.4.4 |
| 6 | 300 Sqmm3core |
| 7 | Laying of H.T. Cable in Existing RC.C. Multiutility duct of Size 1.00 x 1.20 mt and making suitable size hole by core cutting machine in the duct wall for Cable(Inlet/Outlet) and after the laying of cable, hole must be completely packed with suitable material for avoiding water filling in duct complete with required all material T&P etc. as per Direction of E/I. as per PWD SOR 2024 S.I. No. 20e |
| 8 | Supply and Burring of Safe Earthing Electrode T-39 Zn-Zinc Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 item no. 726 (D) |
| 9 | Supply & Laying of 32mm x 6mm G.I. Strip from earth electrode directly in the ground as required complete in all respect as per PWD SOR 2018 S.No. 717 |
| 10 | S/F of danger board of size 200 x 250 x 1.6 mm of M.S. sheet fixed with clamp of 20 x 3 mm M.S. flate including bolts, nuts and washerduly painted completed with all material, labour and T&P etc. for proper completion of work. |
| 11 | S/F of cable route marker made of 1:2:4 R.C.C. Block size 1000x400x100 mm grouted with 1:3:6 cement stone grit coarse sand 30cm below G.L. with painting numbering & marking etc. complete with all required material T&P etc. complete in all respects as per direction of E/I. (As per drawing atteched) |
| 12 | Construction of plinth for 4 Way RMU Size (3x1.25x0.5Mt) With All Meterial, labour and T & P Required for proper completion of work as per specification drawing and direction of E/I (as per specification attached) |
| 13 | Construction of plinth for 5 Way RMU Size (4x1.25x0.5Mt) With All Meterial, labour and T & P Required for proper completion of work as per specification drawing and direction of E/I (as per specification attached) |
| 14 | Construction of fencing plinth of following sizes in Ist class brick work including plaster and providing flat bricks soling and pointing the same with 1:2 cement and fine sand mortar over 75mm thick cement concreting in the ratio 1:6:12 in open space of the cage as per direction of E/I and drawing. |
| 15 | 4 x 2.25 M For 4 Way R.M.U |
| 16 | Construction of fencing plinth of following sizes in Ist class brick work including plaster and providing flat bricks soling and pointing the same with 1:2 cement and fine sand mortar over 75mm thick cement concreting in the ratio 1:6:12 in open space of the cage as per direction of E/I and drawing. |
| 17 | 5.00 x 2.25 M For 5 Way R.M.U |
| 18 | Supply of fixing of 2.5 Mtr. High cage fabricated with 4.0mm thick chain link /wire mesh of equivalent weight fixed on 50x50x6mm angle iron frame having vertical members spaced at 1.0M to 1.25M. and horizontal members spaced at 1.20M the vetical members shall be grouted in ground and horizontal members in the wall to a depth of 300mm with ends folded. The cage shall have 1000x2000mm size single leaf door with locking arrangement having door frame fabricated with 40x40x5mm angle iron and 4 mm expanded G.I. wire mesh of equivalent weight duly fixed with the cage member. The cage shall have nut bolt arrangement for opening the sides by providing tees 45x20cm of angle iron size 50x50x6mm as per direction of E/I. It shall be painted with red oxide primer and synthetic enamelled paint as per direction of E/I. including all materials, labour and T & P for proper completion of work. As per PWD SOR 2018 S.I No 1142 |
| 19 | Please Enable Macros to View BoQ information |