| 1 | Taking down carefully existing copper/aluminium point wiring (light, fan, socket or power) complete of any description including fitting such as switches, ceiling roses, pendants, tube light fitting, regulators, sockets, bell push and call bell wooden boards, laminated sheets from sunken boxes, boards, shades light fitting etc and making good the disturbed surfaces of walls, floors, ceiling etc with cement plaster, putty and paint to match with the existing surface complete all as specified and directed. |
| 2 | M&L for Point wiring with 1.5 Sqmm FRLSH insulated, unsheathed, multistranded, 1100 Volts grade copper conductor cable single core conforming to IS:694 along with one run of 1.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of pressed steel terminal box of thickness not less than 18 SWG / with earth dolly of suitable size concealed in wall and covered with 3 mm thick phenolic laminated hylam sheet fixed with brass/GI screws for mounting switches, sockets, fan regulator, etc. complete all as specified and directed for the following points:- |
| 3 | One light / ceiling fan / exhaust fan / call bell point controlled by one switch |
| 4 | One 6A socket point controlled by one switch on independent board |
| 5 | One 6A socket point controlled by one switch on same board |
| 6 | All as per item No. 2.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires. |
| 7 | All as per srl item No 2 here-in-before but with 4 sq mm FRLSH copper wire with 4 Sqmm FRLSH copper earth wire for one 16 Amp socket point controlled by one 16 Amp switch on independent board. |
| 8 | All as per item No. 2.00 here-in-before but with 2.5 Sqmm one 16A socket point controlled by one 16A switch on independent board but just below / above the existing socket points / DBs up to one meter distance in the same vertical plane. |
| 9 | M&L for point wiring for modular fittings complete with 1.5 Sqmm FRLSH insulated, unsheathed, multistranded, 1100 Volts grade copper conductor cable single core conforming to IS:694 along with one run of 1.5 Sqmm FRLSH insulated copper conductor cable green in colour for continuous earthing drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 20mm(OD), concealed in wall/ floor etc including provision of modular cover plates with frames and 1.50 sq mm PVC insulated unsheathed stranded copper conductor (FRLSH) cable for common earth and connecting to earth dolly all as specified and directed by Enrg-in-charge. (Note- rates of chasing/cutting & making goods shall be included in the unit rate) :- |
| 10 | One light / ceiling fan / exhaust fan / call bell point controlled by one switch |
| 11 | One 6A socket point controlled by one switch on independent board |
| 12 | One 6A socket point controlled by one switch on same board |
| 13 | All as per item No. 3.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires. |
| 14 | All as per srl item No. 3 here-in-before but with 4 sq mm FRLSH copper wire with 4 Sqmm FRLSH copper earth wire for one 16 Amp socket point controlled by one 16 Amp switch on independent board. |
| 15 | All as per item No. 3.00 here-in-before but with 2.5 Sqmm one 16A socket point controlled by one 16A switch on independent board but just below / above the existing socket points / DBs up to one meter distance in the same vertical plane. |
| 16 | M&L for point wiring with 1.5 Sqmm PVC insulated FRLSH, unsheathed, copper conductor stranded 1100 volt grade cable in & incl PVC trunking of size not less than 32x12mm ISI marked ivory white with all accessories such as tee, bend, joint cover including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and PVC laminated hylem/Anchor ISI marked top cover 3.0 mm thick for mounting of switches/ sockets/ regulator etc and PVC insulated & unsheathed 1100 volt grade copper conductor, stranded 1.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green. Make - Polycab/Finolex/Havells |
| 17 | One light / ceiling fan / exhaust fan / call bell point controlled by one switch |
| 18 | One 6A socket point controlled by one switch on independent board |
| 19 | One 6A socket point controlled by one switch on same board |
| 20 | All as per item No. 4.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires. |
| 21 | All as per srl item No 4.00 1 here-in-before but with 4 sq mm FRLSH copper wire with 4 Sqmm FRLSH copper earth wire for one 16 Amp socket point controlled by one 16 Amp switch on independent board. |
| 22 | All as per item No. 4.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board but just below / above the existing socket points / DBs up to one meter distance in the same vertical plane. |
| 23 | M&L for point wiring with 1.5 Sqmm PVC insulated FRLSH, unsheathed, copper conductor stranded 1100 volt grade cable in & existing conduit with all accessories such as tee, bend, joint cover including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and PVC laminated hylem/Anchor ISI marked top cover 3.0 mm thick for mounting of switches/ sockets/ regulator etc and PVC insulated & unsheathed 1100 volt grade copper conductor, stranded 1.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green. Make - Polycab/Finolex/Havells |
| 24 | One light / ceiling fan / exhaust fan / call bell point controlled by one switch |
| 25 | One 6A socket point controlled by one switch on independent board |
| 26 | One 6A socket point controlled by one switch on same board |
| 27 | All as per item No. 5.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires. |
| 28 | All as per item No. 5.00 here-in-before but one 16A socket point controlled by one 16A switch on independent board but just below / above the existing socket points / DBs up to one meter distance in the same vertical plane. |
| 29 | Taking down submain wiring of any size any type and in any position metalic/non metallic PVC conduit of wooden batten complete all as specified and directed. |
| 30 | M&L for sub main wiring along with earth wire with FRLSH insulated copper conductor, single core cable drawn through and including medium grade rigid PVC conduit conforming to IS:9537 (Pt-III) and its all accessories/junction boxes/ inspection covers etc of suitable size but not less than 25mm concealed in wall/ floor etc complete all as specified and directed for the following sizes:- (Note: Three runs of copper cable and one run of PVC conduit shall be measured as one unit length) |
| 31 | All as per srl item No 7 here-in-before but 2 runs X 2.5 Sqmm + 1 run X 2.5 Sqmm. Note: Three runs of copper cable and one run of PVC conduit shall be measured as one unit length |
| 32 | 2runs x 4 sqmm(Ph & N) + 1run x 4 sqmm(earth wire) |
| 33 | 2runs x 6 sqmm(Ph & N) + 1run x 6 sqmm(earth wire) |
| 34 | 2runs x 10 sqmm(Ph & N) + 1run x 10 sqmm(earth wire) |
| 35 | M&L for sub main wiring along with earth wire with FRLSH insulated copper conductor, single core cable drawn through in & incl PVC trunking of size not less than 32x12mm ISI marked ivory white and its all accessories complete all as specified and directed for the following sizes:- (Note: Three runs of copper cable and one run of PVC conduit shall be measured as one unit length) |
| 36 | 2runs x 4 sqmm(Ph & N) + 1run x 4 sqmm(earth wire) |
| 37 | 2runs x 6 sqmm(Ph & N) + 1run x 6 sqmm(earth wire) Please Enable Macros to View BoQ information |
| 38 | 2runs x 6 sqmm(Ph & N) + 1run x 6 sqmm(earth wire) Please Enable Macros to View BoQ information |