| 1 | M&L in replacement of Power Cables, Aluminum Stranded Conductor 400 sqmm, 3.5 core, XLPE Insulated, Cores laid up, PVC Inner sheathed, Armoured with galvanized wire or galvanized steel strip, overall PVC Sheathed, 1100V Grade as per IS 7098(Part 1) 1988 complete laid in trenches / floors / fixed to poles / walls / drawn through pipes etc including provn of lugs, glands, nuts, bolts & washers etc for connecting in LT feeder pillar box / transformer bushings/LT OH Line and testing on completion all as specified and directed by Engineer-in-Charge.Note: Excavation, earth work and provn of cable covers / protection pipe etc shall be measured and paid separately under relevant items of BOQ. |
| 2 | All as per item No. 1.00 here-in-before but of size 300 sqmm, 3.5 core. |
| 3 | All as per item No. 1.00 here-in-before but of size 240 sqmm, 3.5 core. |
| 4 | All as per item No. 1.00 here-in-before but of size 185 sqmm, 3.5 core. |
| 5 | All as per item No. 1.00 here-in-before but of size 150 sqmm, 3.5 core. |
| 6 | All as per item No. 1.00 here-in-before but of size 120 sqmm, 3.5 core. |
| 7 | All as per item No. 1.00 here-in-before but of size 95 sqmm, 3.5 core. |
| 8 | All as per item No. 1.00 here-in-before but of size 70 sqmm, 3.5 core. |
| 9 | All as per item No. 1.00 here-in-before but of size 50 sqmm, 3.5 core. |
| 10 | All as per item No. 1.00 here-in-before but of size 35 sqmm, 3.5 core. |
| 11 | All as per item No. 1.00 here-in-before but of size 25 sqmm, 4 core. |
| 12 | All as per item No. 1.00 here-in-before but of size 16 sqmm, 4 core. |
| 13 | All as per item No. 1.00 here-in-before but of size 10 sqmm, 4core. |
| 14 | All as per item No. 1.00 here-in-before but of size 10 sqmm, 2 core. |
| 15 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting in soft/loose soil for laying of cables complete all as specified and directed by Engineer-in-Charge. |
| 16 | Supply and spread M-sand in trenches for cushioning of cable complete all as specified and directed by Engineer-in-Charge. (Note: Punned down thickness only shall be measured for the purpose of payment) |
| 17 | Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed by Engineer-in-Charge. |
| 18 | Removing surplus excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 19 | Supply and lay in trenches, un-reinforced precast concrete cable cover, Class LV, Type I, flat, size 250 mm x 150mm x 40mm for cable protection in trenches complete all as specified and directed by Engineer-in-Charge. |
| 20 | Material & Labour for cutting of existing hard standing up to 15 cm depth for laying of pipe lines and making good the disturbed surfaces by providing PCC 1:2:4 type B-1 (using 20mm graded aggregate) after laying of pipes lines and returning filling of soil, complete all as specified and directed. Note:- Excavation and earth work below hard standing will be measured and paid under relevant items. |
| 21 | Supply and fix in replacement of 100mm dia bore tubes, 'light grade' galvanized, with all fitting and fixed complete to walls/ poles or laid in trenches/ floors for cable protection complete all as specified and directed by Engineer-in-Charge. |
| 22 | All as per item No. 21 here-in-before but of size 50mm dia bore. |
| 23 | Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts complete all as specified and directed by Engineer-in-Charge. |
| 24 | M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate as in foundations of pole/ stay assembly complete all as specified and directed by Engineer-in-Charge. |
| 25 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- |
| 26 | Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors.(ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. |
| 27 | (i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.(ii) Incomer :(a) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No(b) Digital Voltmeter with selector switch - 01 Set(c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3(d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3(iii) Outgoing :-(a) MCCB 100 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 05 Nos |
| 28 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed : -Make:- Shalabh India/Osian Switch Gerar/ Uninersal Switch Gear Control |
| 29 | Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors.(ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. |
| 30 | (i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.(ii) Incomer :(a) MCCB 200 Amps, 4 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No(b) Digital Voltmeter with selector switch - 01 Set(c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3(d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3(iii) Outgoing :-(a) MCCB 63 Amps, 4 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release -10 Nos |
| 31 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall be suitable for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- |
| 32 | Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors.(ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. |
| 33 | (i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.(ii) Incomer :(a) MCCB 160 Amps, 4 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No(b) Digital multimeter - 01 Set(c) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3(iii) Outgoing :-(a) MCCB 63 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 8 Nos |
| 34 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1800mm x 1500mm x 800mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- |
| 35 | Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors.(ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. |
| 36 | (i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.(ii) Incomer :(a) MCCB, 400 Amps, 4 Pole, 36 KA (Ics = Icu = Icw for 1 Sec), 415 Volts, 50 Hz, Manual Draw Out (MDO) type with microprocessor based release - 01 No(b) Digital Voltmeter with selector switch - 01 Set(c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3(d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3(iii) Outgoing :-(a) MCCB 200 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 03 Nos(b) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 Nos |
| 37 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1800mm x 1500mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed |
| 38 | Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors.(ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. |
| 39 | (i) Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.(ii) Incomer :(a) MCCB 500 Amps, 4 Pole, 50 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No(b) Digital Voltmeter with selector switch - 01 Set(c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3(d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3(iii) Outgoing :-(a) MCCB 400 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 Nos(b) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos(c) MCCB 100 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 03 Nos |
| 40 | M&L for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 50mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II Please Enable Macros to View BoQ information |