| 1 | Supply and Laying in replacement including testing and commissioning LT UG Power cable, XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with multi-stranded aluminium conductor including termination with LT Panel/Feeder Pillar with galvanised or Cadmium plated high tensile nuts, bolts and washers etc including Sheddling /clamping on any type of wall with suitable size of GI Clamps, nuts, bolts & washers etc of size 3.5 Core 240 Sqmm complete all as specified and directed. |
| 2 | All as per item No.01 above but 50 Sqmm 3.5 core |
| 3 | All as per item No.01 above but 35 Sqmm 3.5 core |
| 4 | All as per item No.01 above but 16 Sqmm 4 core |
| 5 | Excavation in trenches, n.exc 1.5m wide and n. exc 1.5 m depth and getting out in hard/dense soil for foundation of pole, stay, laying of cable and pipe etc complete all as specified and as directed. |
| 6 | Excavation in trenches, n.exc 1.5m wide and n. exc 1.5 m depth and getting out in soft/disintegrated rocks for foundation of pole, stay, laying of cable and pipe etc complete all as specified and as directed. |
| 7 | Returning and filling in, including spreading and well ramming in layers n exc 25 cm complete all as specified and as directed. |
| 8 | Removing excavated material a distance n. exc 50 m & depositing where directed at a level n. exc 1.5 m above the starting point complete all as specified and as directed. |
| 9 | Supply and laying 120 x 103 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e.coupler,Tee, elbow clamp for cable protection of size 240 Sqmm 3.5 core complete all as specified and as directed. |
| 10 | Supply and laying 63 x 50 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e.coupler,Tee, elbow clamp for cable protection of size 50 to 35 Sqmm 3.5 core complete all as specified and as directed. |
| 11 | Supply and laying 40 x 32 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e.coupler,Tee, elbow clamp for cable protection of size 16 Sqmm 4 core complete all as specified and as directed. |
| 12 | S & F in replacement including Installation, testing and commissioning of Busbar panel weather proof outdoor type single door, fabricated out of 2 mm thick CRCA sheet with epoxy powder coating of RAL-7035 ( Siemens Gray) shade with matt finish with seven tank pre treatment process. The Panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-54, Gaskets between all adjacent units and beneath all covers shall be provided to render the joints dust proof. All doors and covers shall be provided with cylindrical panel locks and shall be fully gasketed with neoprene rubber and shall be lockable. The panel shall be provided with aluminium bus bars electrolytic grade of 400 Amps current rating including required size of nut bolts for fixing of cables upto 240 Sqmm. The bus bars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding and fix horizontally. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in a dedicated compartment. All joints and connection shall be done with galvanised or cadmium plated high tensile nuts, bolts, washers and AL Lugs etc. The panel shall be provided with 04 Nos 50mmx50mmx5mm thick angle iron supports of not less than each 0.6 mtr height duly painted with anti corrosive black paint including earth work and grouted in PCC 1:3:6 at suitable depth as per site requirement including taking down existing one. The overall size of the Busbar panel shall not be less than 500mmx300mmx700mm (LxWxH) including 4 Nos cable entry holes suitable for cable entry up 3.5C 240 Sqmm at bottom complete all as specified and as directed. |
| 13 | Supply, installation, testing and commissioning in replacement of LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-54, front side double door type with locking arrangement and nut-bolts for back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber. The panel shall be provided with aluminium bus bars, electrolytic grade of 300 Amp Current rating. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and Cable connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including suitable Lugs etc. The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x6mm thick angle iron supports of not less than each 1 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both sided and suitable extended rotary handle for Incoming MCCB complete all as specified and as directed. The overall size of the panel shall not less than 1600mmX400mmX 1200mm (LxDxH). The panel shall be provided for Cable entry from bottom side for 04 No of Cable upto 240 Sqmm 3.5 Core with suitable size of SS Cable Glands including 2 Nos of Earting Terminals one on each side of the Panel with earth strip, complete all as specified and as directed and including following accessories:- |
| 14 | Continued from item No.13......Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-charge.(a) MCCB 4 Pole, 415 Volts, 200 Amp, 36 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu with extended rotary handle (ROH) mechanism including suitable size of spreader links and phase separator on both side. (Incoming) - 01 No. Make : L&T/Legrand. (b) MCCB 4 Pole, 415 Volts, 160 Amp, 36 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu with extended rotary handle (ROH) mechanism including suitable size of spreader links and phase separator on both side. (outgoing) - 01 No. Make : L&T/Legrand(c) MCCB 4 Pole, 415 Volts, 100 Amp, 16 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links and phase separator on both side. (Outgoing) - 0 1 No. Make : L&T/Legrand (d) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links and phase separator on both side. (Outgoing) - 02 No. Make : L&T/Legrand (e) MCB 4 Pole, 415 Volts, 63 Amp, 10 KA Breaking capacity conforms to IEC 60947-2. (Outgoing) - 02 Nos. Make: L & T/ Legrand |
| 15 | S&F GI tubing 'light grade' in replacement of 100 mm dia ISI marked with all fittings laid in trenches and fixed on pole by flat iron clamps, nut, bolt, washer of suitable size complete all as specified and as directed. |
| 16 | S & Fix in replacement of Cable Route Marker made up of Cast Iron of dia 100 mm and thickness 4.65 mm with supporting angle iron of size 20 x 20 x 3 mm and height 1 mtr for stand including priming, painting and wirting of \\"MES LT CABLE\\" with Arrow Direction in suitable size of letter including necessary earthwork and grouted at suitable depth in PCC 1:3:6 Type C2 using 40 mm graded aggregate in mass concrete complete all as specified and as directed. |
| 17 | M&L for road cutting through existing bituminous road as required for laying pipe/cable etc and make good with and including earthwork and necessary excavation, complete material required to match with the existing one or with PCC (1:2:4) type B1 and bitumen complete all as specified and as directed. |
| 18 | S & F in replacement of Manual Change Over LT Panel weather proof outdoor type double door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-54, front side single door type with locking arrangement for front side and nut bolt fitting for back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with spreader links/busbars extension of adequate rating including incoming and outgoing cable connection, thimbles, all joints and connection shall be done with galvanised or cadmium plated high tensile nuts, bolts and washers etc. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured for indicators. The panel shall be provided with RYB LED indicating lamps at both incoming cables. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . The overall size of the Change Over Panel shall not be less than 700mmX600mmX800mm (LxDxH) including One No. of Manual ON Load Change Over Switch of rating 315 Amp, 415Volts, 50 Hz, AC, Four Pole with staggered terminals including both side of spreder links (conforms to IEC 60947-3). The panel shall be provided for Cable entry upto size of 240 Sqmm cable from bottom side for 04 Nos of Cable including 2 Nos of Earthing Terminals one on each side of the Panel with GI earth strip complete all as specified and as directed.Note : Before manufacturing drawing and design of panel shall be approved by Engr-in-charge. Make of Change Over : L&T /C&S |
| 19 | M & L in replacement for earthing complete with galvanized steel earth plate electrode 600 X 600 X 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.50 m deep below normal ground level in any type of soil strata, connected to galvanized iron strip 25 X 4 mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 3 of MES schedule 1991 Part – I connected to Change over switch panel including necessary excavation and earth work, concrete pit & chamber,pit cover made of PCC 1:2:4 type B1 with lifting handle and Earth lead and 20mm Dia GI watering pipe medium grade, Funnel, wiremesh, etc. complete all as specified and as directed. |
| 20 | Supply & Fix in replacement including testing and commissioning of digital automatic timer switch distribution panel board, factory assembled in powder coated steel sheet enclosure, comprising of 4P MCB, 40 Amps & 3 Pole power contactor 40/50 Amps and 230V digital time switch for controlling LED street lights, including earth work for fixing Timer switch distribution panel board and shall be provided 4 Nos 20x20x3mm thick angle iron supports of not less than each 0.6 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth complete all as specified and as directed. Please Enable Macros to View BoQ information |