| 1 | Sch 'A' Part-I (Building Work):-This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as \\"Rs. 0.00\\" under col.5 signifies this fact only. |
| 2 | Construction of block of operator cum LT panel room complete all as shown on drawings and as specified. |
| 3 | Total Amount of Sch 'A' Part - II (Site Clearance and Development Work) |
| 4 | Total Amount of Sch 'A' Part - III (Internal Water Supply Work) |
| 5 | Total Amount of Sch 'A' Part - IV (Internal Electric Supply Work) |
| 6 | Total Amount of Sch 'A' Part - V (Area Drainage) |
| 7 | Total Amount of Sch 'A' Part - VI (Sewage Disposal (Sump Well and Sewer Line) Work) |
| 8 | Total Amount of Sch 'A' Part -VII (Road, Path, Culvert and Hard Standing Work) |
| 9 | Total Amount of Sch 'A' Part -VIII (External Water Supply and Staging for Treated Water Work) |
| 10 | Total Amount of Sch 'A' Part - IX (External Electric Supply Work) |
| 11 | Total Amount of Sch 'A' Part - X (Compound Wall Work) |
| 12 | Sch 'A' Part - XI (Misc Items of work) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as \\"Rs. 0.00\\" under col.5 signifies this fact only. |
| 13 | Designing (Hydraulically . Structurally and aesthetically), Providing constructing hydraulic testing, commissioning of sewage treatment plant (60 KLD Capacity) consisting of coarse bar screening chamber (RCC) with steel screening (Manual), receiving sump RCC, Submersible pumps in receiving sump, stilling chamber in RCC, fine bar screen chamber ( Manual) RCC with steel screen, oil & grease remover (RCC), Grit separator equalization tank (two tank of 50% capacity each), air grid for equalization tank, feed pumps 02 No's, moving bed Bio reactor (s) with plastic media of appropriate density , size and quality to keep very high MLSS greater than 15000mg / litre). Air blowers for MBBR (02 No's), tube settlers assay, sludge pump screw type 02 No's Sludge dewatering centrifugal, sludge holding tank, Air grid for sludge holding, chlorine dozing system chlorine contact tank, foundation for all E/M equipment's, associated typing work with reqd valves, gates, drains, pathways, electrical control panel with inter connecting cable, spare parts for 2 years of operation, etc. complete as turned key job with all involved civil, electrical, digital and mechanical works as per detail specification for civil, electrical and mechanical components with all duties and taxes complete. Also refer important notes below:-) for Tartary treatment it also include filter feed tank of RCC, Filter feed pump, Dual media filter, activated carpon filter, treated water tank in RCC. Treated water can also been used for irrigation, horticulture, fire fighting and MT wash. (Contd..../) |
| 14 | Tertiary treatment includes for one No chlorine contact cumfilter Feed tank in MS FRP construction, as per design specification of OEM with one set of chlorine dozing system comprising of solution tank and dozing pump with necessary connection for dozing solution in chlorine contact tanks 02 No's, filter feed centrifugal mono block pumps complete with motor and all accessories and fitting for feeding tertiary unit, level sensor for chlorine contact cum filter feed tank inter link with pumps for ON/Off operation a spare level in the sump, one pressure gauge for each pump to provide to measure pressure at the outlet one No dual media filter complete with media, frontal pipe valve and pressure gauge to measure the pressure across the filter, one no of activated carpon filter, complete with media, frontal piping, valve and pressure gauge, one No treater water tank in MS FRP construction to receive super natant coming from tertiary treatment, 02 No sludge transfer self priming mono block pump complete with all necessary fittings and accessories incl one pressure gauge for each pump, one no sludge holding tank in MS FRP construction as per design specifically to receive sludge from tube settler, 02 No's sludge transfer self priming monoblock pump complete with motors and all accessories and fittings, level sensor in the sludge holding tank and inter link with pumps for ON-OFF operation as per level in the sump, (Contd..../) |
| 15 | pressure gauge for each pumps , one eno electrical control panel for operation for all electrum mechanical STP, power and control cables of suitable size to inter connect with varies drives late over suitable cable tray and instrumentation with STP panel etc. complete including permission of civil auth for connecting outlet water into natural resources testing, commissioning etc; Note:- (i) Rate shall include for permission for civil auth for the connection of out let etc. testing, commissioning and design complete including all as specified . (ii) Inlet and outlet data shall be taken considering MBBR Tech. However contractor is free to design, testing, commissioning of any approved Technology of E-in-C branch without any extra cost to the department. (iii) The size of pump, tank, channels etc. consider in schedule are indicative for estimation purpose. contractor need to design 60 KLD plant and all component including E/M and B/R of any E-in-C's approved tech of STP and same shall be vetted from IIT/NIT. (iv) The Arch drawing, structural drawings of different designed by the contractor shall be vetted by him from NIT/IIT before approval of concerned section of this HQ. (v) Completion certificate shall be issued only after testing of treater water parameter as per state pollution control Board Norms . (Contd..../) |
| 16 | Raw severage parameterpH 6.5- 8.5COD 350-450BOD 200-300TSS 250-300Total nitrgen -Total phosporus -Fecal Coliform Present Odour Odour presentEffluent parameters to be achieved after tertiary treatment pH 6.5-8.5 COD < 50mg /ltrrBOD < 10mg /ltrTSS < 10mg /ltrTotal nitrgen < 10mg /ltrTotal phosporus - 1 mg/ ltrFecal Coliform - NilOdour - No foul odour |
| 17 | Supply, installation, testing and commissioning of non clog vertical submersible pump set capacity 200 LPM, 12m Head, 3 phase, 415 volts, 1 HP of with chrome steel impeller and cutter, non clog to pass 40mm size particle including with guide rail and lifting chain, suitable size of cables, complete all as specified and directed. |
| 18 | Puddle flange of 500mm long, 300mm dia, sluice valve with 8m telescopic shaft of size 300mm dia, in RCC wall, having clamp support for telescopic rod, having circular handle of dia not less than 300mm, with nut bolts etc. complete all as specified and directed by Engineer in Charge. |
| 19 | Ultra sonic level sensor: supply and fix and connection with Panels automatic level sensor for submersible pump complete all as specified and directed. |
| 20 | 3 layer (inner antimicrobial, outer UV stabilized) ISI marked, IS-15801, PP-R pipe SDR 11 (PN-10) and PP-R plain fittings in trenches/wall/cellings or laying in floors complete of 50mm dia, outer dia including all fittings, for riser, complete all as specified and directed. |
| 21 | 2.5 sqmm, 3 core copper multistaranded flat cable suitable for non clog vertical submersible pump, 1 HP, three phase, 415 Volts complete all as specified and directed. |
| 22 | Excellent quality rigid & sturdy lifting tripod, chain, SWR and block mechanism for lifting of non clog vertical motor pump capacity 1 HP from STP plant complete all as specified and directed. |
| 23 | Water pressure gauge, pressure upto 7kg, suitable for non clog vertical motor pump 1 HP complete all as specified and directed. |
| 24 | Cutting the existing GI pipe line of 50mm dia, screwing and including inserting GI Tee of size 50mm x 50mm x 25mm dia, complete with threading for making new branch connection of 25mm dia, including necessary fittings complete all as directed by Engr-in-Charge. |
| 25 | Cutting bitumen road/concrete path any type including excavation, returning filling, levelling, well ramming in layers, including soiling with stones, WBM 7.5cm thick and laying premix carpet 25mm thick using ready mix patch mate material, including rolling and compaction complete all as specified and directed. |
| 26 | Construction of Valve pit of size (90x90x90)cm (Internal dimensions) using PCC (1:4:8) type D-2, using 40mm graded crushed stone aggregate for foundation, 10cm thick, and 100mm off sets on all sides, 230mm thick brick masonry walls built in cement mortar (1:6), 15mm thick rendering all around the masonry work in cement (1:6), for internal and up to 15cm below GL for external surfaces of walls, 50mm thick PCC (1:2:4) type B-1 using with 20mm graded crushed stone aggregate including necessary form work for grouting including 3.15mm thick, MS top sheet cover double door with locking arrangement welded to MS frame made out of (50x60x6)mm angle iron frame fixed with hold fasts including painting of steel surface with two coats of synthetic enamel paint over a coat of red oxide primer including necessary excavation in any kind of soil, returning filling in and removal of surplus soil to a distance not exceeding 50m complete all as specified and shown on drawing No. CEUZ/TD/1500/2015, sheet No.1/1. |
| 27 | Supply, Fabrication, Installation, Testing & Commissioning IP54 440V AC LT Panel Indoor type, Compartmentalized, Modular, outdoor sheet 3.15mm and indoor sheet 2.0mm thick, CRCA Sheet of appropriate size, front operatable double doors, front & back openable only, dust & vermin proof, cable entry through 2.0mm CRCA gland plates - bottom only, powder coated after 7-tank pre-treatment process - siemens grey shade on body/doors & orange shade on mounting/gland plates + incomer doors, 3phase HR sleeved color coded aluminium main busbar of 200A for phase and 100A for neutral with transparent FRP covers & on SMC/DMC Supports, 50mmx5mm aluminium earth busbar running across the whole length of the LT panel with 2 Nos studs at both the side-ends, lifting arrangement/hooks at the top, wiring with appropriate size of copper industrial cables, black painted base frames - 40mmx40mmx6mm MS angle frame, cable glandes brass chromium plated of different sizes suitable for incoming & outgoing with one spare box connection of all equipment with panel and fitted with following specified items: - (Contd..../) |
| 28 | (a) Incoming MCCB 63 Amps, FP 415 volt 35, KA - 01 No(b) Outgoing MCCB 40 Amps, FP 415 volts, 35 KA -01 No (STP)(c) Outgoing MCCB 16 Amps, TP 415, volt 25 KA – 05 No (03 No for Motor Pump+01 for Compressor+01 Standby)(d) Outgoing MCB 40 Amps, SPN 230, volt 15 KA - 02 No (01 for Bldg+01 for Security light)(e) Digital Volt Meter (0 To 500) with selector switch 01 No(f) Digital Ammeter (0 To 200) with CT, selector switch 01 No(g) Indicating Light Led Type,22.5mm,415V AC- (R, Y, B) 01 No(h) 100A, 3ph, 4wire, 50hz TPN aluminium busbar with heat shrinkable coloured insulated PVC sleeves set of 04(i) Connection with suitable copper cable PVC single core |
| 29 | Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6.0mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size (32x6)mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15cm thick alternate layers of charcoal dust & common slat including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20mm graded crushed stone aggregate) reinforced with TMT steel bars 8mm dia @150mm c/c both ways with suitable handle and angle iron (40x40x5)mm frame, GI medium grade watering pipe 20mm bore and funnel with wire mesh, GI light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed. Note:- On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction. |
| 30 | Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6.0mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size (25x4)mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15cm thick alternate layers of charcoal dust & common slat including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20mm graded crushed stone aggregate) reinforced with TMT steel bars 8mm dia @150mm c/c both ways with suitable handle and angle iron (40x40x5)mm frame, GI medium grade watering pipe 20mm bore and funnel with wire mesh, GI light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed. Note:- On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction. |
| 31 | 7 meter long hot dipped galvanised OCTAGONAL street light pole with one single light bracket for street light. The bottom of pole shall be 130mm dia and top shall be 70mm dia with 3mm thickness, high tensile strength conforming to BS EN 10025, base plate shall be 220mmx220mmx112mm with 4 No of anchor bolt 'J' type 700mm long, 20mm dia with nut washer and bolt shall be inserted to RCC footing, including pole top mounted cap type street light bracket for single street light fitting. The pole shall have internal inbuilt junction box including 3 phase bus bar and one 6 amp MCB, complete including necessary earthwork excavation in any kind of soil, RCC M-25 (Design mix) as in footing including reinforcement as per manufacturer drawing, formwork etc. complete all as directed. |
| 32 | Fire extinguisher life guard ISI ABC of 9 KG complete all as directed. |
| 33 | CABLE TRAY:- Supplying and installation perforated painted with powder coating M.S cable trays with perforation not more than 17.5 % in covenient sections, joined with connectors, suspended from the ceiling with M.S suspenders including bolts & nuts, ivory painting suspender etc.; of size 450mm width X 50mm depth X 2.0mm thickness, 20 metre complete all as specified and directed. |
| 34 | Double walled corrugated (DWC) pipe for cable protection with outer dia 50mm and inner dia 38mm including suitable size of coupler for connection of pipe complete all as specified and directed. |
| 35 | Supply, installing, commissioning & testing of Diesel Engine Driven Generator Set of 15 KVA with AMF panel complete with suitable acoustic enclosures all as per central pollution control board guide lines, 50 cycle pre second with 0.8 power factor, engine and alternator as per latest CPCB IV norms complete. The alternator of rating 15 KVA of Generator set shall be directly coupled with Diesel Engine mounted on common base plate with alternator and all as specified and comprising of the following:-Notes: EngineInline type, 4 cylinder diesel engine of of suitable BHP rating at 1500 RPM as per new CPCB norms IS 10002 direct injection type with turbo charger & water cooled engine electric starting system, arrangement of starting and the engine shall be capable of running 12 hours continuously and with 10% of overloading for one hours in each 12 hours running. The engine recommendations. Engine shall be directly coupled with alternator mounted on common base plate with the following:- (Contd..../) |
| 36 | (a) 1 No, 12 volts, 80 AH batteries with battery charger. The battery charger shall be able to charge the battery at all time whenever electric supply is given to battery charger through control panel.(b) Heavy duty industrial silencer.(c) Fly wheel with coupling bolts.(d) Lub oil filter.(e) Instrument panel comprising of microprocessor based controller for measuring parameters like coolent temperature, Running hours, lubricating oil pressure etc.(f) Engine speed mechanical /easy governor class A, Governing as per BS 5514 (g) Air filter (Dry type)(h) Turbocharger of suitable capacity(i) Gear pump for forced feed lubrication(j) Fuel injection Pump(k) Fuel filter double bowl(l) Radiators(m) Flexible rubber coupling (Contd..../) |
| 37 | (n) Set of fuel pipes of suitable length(o) Base plate(p) Fuel tank capacity as per manufacturer design with all connecting pipe & fabricated MS stand including level gauge.(q) Anti vibrating pads& mounting for the generators set, Engine and alternator(r) Legging of exhaust manifold with asbestos rope to exposed pipes(s) Flexible exhaust pipe with end flanged of suitable size. (Contd..../) |
| 38 | Alternator:- Alternator of rating capacity (rated KVA) & capable to take 10% extra load at every 12 hours interval for one hours, 3 phase, 4 wire, 50 Hz, 415 volts, 0.8 power factors. 1500 RPM self excited self regulated required to be coupled with above engine. The alternators shall be conforming to IS-4722 & IS-4728 as per following specification.(a) Type: Salient poles, single bearing brushes type suitable for direct coupling to engine.(b) Rating: Guaranted to deliver required output at the ambient temp conditions. Suitable for an over load of 10% 1 hour in every 12 hours operations.(c) Voltage Regulation: Provided with fast response thyristors type electronics automatic voltage regulators, which holds output voltage with in desired limits. (+/-1%)(d) Self excited- self regulated(e) Alternator loading: Suitable for taking rated load immediately after machines reaches rated voltage and speed.(f) Vibration: Suitable for direct coupling with engine and mounted on common MS Channel base frame. (Contd..../) |
| 39 | (g) Enclosures: Screen protected drip proof enclosure with IP-23 Degree of protection.(h) Cooling: Liquid cooled type.(j) Control panel shall be provided with suitable PC controller and digital display for measuring of line/phase voltage/currents, frequency etc.AMF Panel ( Standard control panel for DG set shall be made of fabricated sheet cubical type with front hinged cover, with microprocessor based controller with following features:-(a) State of the art compact microprocessor based fully configurable technology.(b) Integration of all engine and alternator parameters.(c) For ease of viewing, high performance graphical LCD and prominent display.(d) Event logging history for easy of maintenance/service.(e) Capability of with standing wide range of operating temp.(f) Individual touch bottons for manual, auto and test mode. (Contd..../) |
| 40 | (g) LED indications for genset status and alarms.(h) Battery conditions monitoring.(j) Statistical cumulative counters like, No of starts, Engine run Hrs, Kwh.(j) Setting provision for different parameters on front panel.(k) Two nos microprocessors based, MCCB 63 Amps, 16 KA breaking capacity, one for main supply and other for DG set supply.(l) Two nos contractors of suitable capacity for main & DG.(m) AI bus bars of 400 Amps capacity provided with termination.(ii) Display Parameters(a) Electrical parameters: Phase voltage, line current, frequency, average voltage, average current, KW, KWH, KVA, KVAR, Power factor, earth fault current.(b) Mechanical Parameters: Lube oil pressure coolant, Temp, Engine speed, Fuel status, Engine run hours, Battery Voltage.(iii) Protection:(a) Electrical protections: Under/over voltage, under/over frequency, phase failure. Phase sequencer reverse, over current, over KW. (Contd..../) |
| 41 | (b) Mechanical protections: Under/over speed, low lube oil pressure, High engine coolant temp, Low fuel level alarm, start/stop fail, charging alternator fail.(c) Cable entry gland plate without cable glands.FoundationDG Set shall be installed on new foundation block as per manufactures recommendations including excavation works PCC etc. for foundations, provision of cable ducts, making good any damage to existing structure, fuel piping from fuel tank to generator set with medium grade GI tubing and cold water piping system (Medium grade GI tubing from nearest water point to radiator of engine with brass tap and stop cocks and fittings complete connecting the existing earthing strips to control panel, DG set and generator. |
| 42 | PVC coated mild steel foot rest complete all as directed. |
| 43 | Rotational moulded polyethylene water storage tanks of 5000 Litres capacity (ISI marked), (cylindrical vertical tanks with closed top) (White in Colour and three layered) hoisted and fixed in position including making necessary arrangements for fixing inlet, outlet and over flow pipe and provision of wash out pipe etc; complete all as specified and directed. |
| 44 | Supply, laying, jointing, testing, commissioning of HDPE Double wall corrugated pipe of dia 150mm for non pressure underground drainage and sewerage with smooth internal & corrugated external surface confirming to IS 16098:Part-2 2013 with spigot or plain end with necessary jointing of DWC HDPE pipes, clean and prepare the pipe ends, then use either a push fit method with a rubber ring and coupler or a specialized jointing jack to connect them (as per manufacturer instruction) complete all as specified and directed. |
| 45 | Supply, laying, jointing, testing, commissioning of HDPE Double wall corrugated pipe of dia 200mm for non pressure underground drainage and sewerage with smooth internal & corrugated external surface confirming to IS 16098:Part-2 2013 with spigot or plain end with necessary jointing of DWC HDPE pipes, clean and prepare the pipe ends, then use either a push fit method with a rubber ring and coupler or a specialized jointing jack to connect them(as per manufacturer instruction) complete all as specified and directed. |
| 46 | Precast concrete manhole circular chamber of size internal dia 900mm, height: 805mm; wall thickness-125mm, clear opening: 560mm dia with RCC cover-concrete grade M-30 (Design mix) using 20mm graded crushed stone aggregate complete all as specified and directed. |
| 47 | Precast reinforced concrete circular riser ring internal dia 900mm, height : 300mm; wall thickness: 125mm; concrete grade M-30 (Design mix) using 20mm graded crushed stone aggregate complete all as specified and directed. |
| 48 | Precast concrete manhole circular chamber of size internal dia 1200mm, height: 1005mm; wall thickness-125mm clear opening : 560mm dia with RCC Cover-Concrete grade M-30 (Design mix) using 20mm graded crushed stone aggregate complete all as specified and directed. |
| 49 | Precast reinforced concrete circular riser ring internal dia 1200mm, height : 600mm; wall thickness: 125mm; concrete grade M-30 (Design mix) using 20mm graded crushed stone aggregate complete all as specified and directed. |
| 50 | Constructing brick masonry circular type drop manhole with drop connection through cast iron; pipe encased with Cement Concrete Block required internal dia at bottom and 0.56m dia at top in cement mortar 1:4, internaly cement plaster 12mm thick with cement mortar 1:3 finished with a floating coat of neat cement, PCC in foundation 1:3:6 type C-2, using 40mm graded crushed stone aggregate, and making necessary channel in cement concrete 1:2:4 type B-I, using 20mm graded crushed stone aggregate, finished with a floating coat of neat cement, all as per standard design and require depth with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg, fixed in cement concrete 1:2:4 type B-I, using 20mm graded crushed stone aggregate, including PVC coated M.S Foot Rest including earthwork complete for following size complete all as specified and directed. |
| 51 | 900mm internal dia at bottom 1.5m depth using 200mm dia cast iron pipe |
| 52 | 1200mm internal dia at bottom 3.0m depth using 250mm dia cast iron pipe |
| 53 | 1500mm internal dia at bottom 4.5m depth using 300mm dia cast iron pipe |
| 54 | Point wiring for One light point/fan point controlled by one switch 5 Amp single pole one-way complete with 1.5 Sqmm (nominal area) PVC insulated, unsheathed and multi strand copper conductor FRLSH cable drawn into and including PVC concealed conduit (heavy duty) and conduit fittings including 1.5 Sqmm PVC insulated unsheathed and multi stranded copper conductor FRLSH cable as earth wire to common earth and connecting to earth dolly including cutting of chases/wall/floor and suitable size of powder coated CRCA mild steel sheet sunken box including 3mm thick laminated sheet top cover for fixing switches, sockets, regulators etc complete all as specified and directed. |
| 55 | All as per Srl Item No. 40.00 here-in-above but for one 3 pin 5 Amp socket on same board |
| 56 | All as per Srl Item No. 40.00 here-in-above but for one 3 pin 5 amp socket on indipendant board all as directed. |
| 57 | All as per Srl Item No. 40.00 here-in-above but with 2.5 sqmm copper conductor for 15 amp socket with 2.5 sqmm earth continuity conductor. |
| 58 | Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below normal ground level connected with galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15 type B1 in pit with angle iron (25x25x3)mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12mm dia MS fabricated handle, test point etc. in and including light grade GI protection pipe 15mm bore up to 7.5m length for drawing in earth lead wire, all as shown in electric plate No. 3 of SSR Part-I complete with necessary earth work in any type of soil, removal of soil to a distance not exc. 50m, testing on completion complete all as specified and directed.Note:- On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction. |
| 59 | Supply, installation, testing and commissioning LED street light fitting 70 watts, rating, separate individual peanut plated lens and aluminium reflector housing made of LM6 pressure die cast aluminium. Optical cover toukghned glass only, impact resistance>IK05 IP protection not less than IP66, protection should be class-I vibration as per IEC 60598, product standard IS 10322/IEC60598, all the component such as driver, surge protector should be of same make. Driver should be moulded type with operating voltage 140V270V, driver frequency 50 Hz power factor >0.9, moulded type weather proof construction with seprate surge protection device 5 KA rating and separate connector block for termination of incomming cable connection complete all as specified and directed. |
| 60 | 7 Watts LED bulb retrofit type (B-22) suitable for decorative light fittings complete all as specified and directed. |
| 61 | Manning & Operation of the STP (of capacity 60 KLD, after completion of STP main work (phase-I). Operating and keeping the capacity in running / operational condition by deploying FGM / technical staff to produce the treated effluent of specified quality including Sundays and holidays including all connected LT cubicle STP panel , electrical & sewage pumps items such as main switch, starter, change over switch, MCCB, voltmeter, ammeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc all as specified and directed by Engr-in-Charge. Notes: Contractor shall deploy one skilled operator (FGM) and two helper per shift for three shifts per day in each month for operation of STP. (Contd.../) Please Enable Macros to View BoQ information |
| 62 | Manning & Operation of the STP (of capacity 60 KLD, after completion of STP main work (phase-I). Operating and keeping the capacity in running / operational condition by deploying FGM / technical staff to produce the treated effluent of specified quality including Sundays and holidays including all connected LT cubicle STP panel , electrical & sewage pumps items such as main switch, starter, change over switch, MCCB, voltmeter, ammeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc all as specified and directed by Engr-in-Charge. Notes: Contractor shall deploy one skilled operator (FGM) and two helper per shift for three shifts per day in each month for operation of STP. (Contd.../) Please Enable Macros to View BoQ information |