| 1 | Construction of 11KV line From Receiving Station Pahalgam to Nunwan Pahalgam for connecting newly Installed 2 MVA 11/0.433 KV Distribution Transformer at Nunwan Base Camp for SANJY 2026. |
| 2 | Supply,loading, unloading at site Erection, testing & commissioning of S.T Pole 11mtr Long SP-56 with base plate & cap for HT. Strictly as per REC standards |
| 3 | Supply,loading, unloading at site Erection, testing & commissioning of S.T Pole 9 mtr Long SP-33 with base plate & cap for HT. Strictly as per REC standards |
| 4 | Supply, installation of GI Ch. Iron X arms 75x40x6 sqmm. 8 ft.long . 16 Nos |
| 5 | Supply and Installation of GI Angle Iron for H Frame cross belt including Clamps (50X50X6)mm |
| 6 | Supply,loading , unloading at site ,Laying, stringing, tensioning & binding of ACSR 30mmsq (Weasel) Conductor. |
| 7 | Supplying and fixing of GI Channel “V’ cross-arm (75 x 40x6mm) with GI Angle Pole Top Bracket (50x50x6 mm) including back clamps of 50X8 mm for fixing V-Cross arm and pole top bracket without making holes in the ST pole as per REC standard for single pole [email protected] kg each |
| 8 | Supplying and fixing of pole Earthing Complete by Spike Earthing Rod 20mm 2.5 Mtr long with GI strip (25x3)mm to each LT and HT pole |
| 9 | Painting of poles with one coat of red oxide and two coats of Aluminium paint as per Standards. This also includes numbering of ploes with paint, submission of Pre and Post Execution photographs duly anthenticated by AEE concrened. |
| 10 | Supply and fixing of Danger Plates with Clamps |
| 11 | Supply and fixing of Anti-Climbing Device with clamps and any other item required for complete job |
| 12 | Supply,fixing, testing & commissioning of 11KV Pin Polymer Insulators with GI pins complete. |
| 13 | Providing & fixing of 11 kV polymeric composite disc insulator 12 kV , min failing load 45 kN, lighting impulse 75 kV positive and 80 kV negative, creepage distance 320mm |
| 14 | Providing and Fixing of GI Nuts and Bolts. |
| 15 | Cement bottoming 1:2:4 mix as per REC Standards 0.48cum/pole Please Enable Macros to View BoQ information |