| 1 | Taking out interlocking paver blocks of any description, size, etc and staking it properly at site for carring out cable trenches and connected E/M works and refixing of old stacked interlocking paver blocks at same site after completion of E/M works including all extra handling and removal and disposing off rubbish out of MoD land complete all as specified and directed. |
| 2 | Surfaces dressing n.exc 15cm deep and getting out in loose/soft soil complete all as specified and directed. |
| 3 | Removing excavated material outside MoD land and depositing where directed complete all as specified and directed. |
| 4 | M&L for 25mm sand cushion under paver block or interlocking tiles floor including watering and consolidation complete all as specified and directed. |
| 5 | M&L for PCC (1:4:8) type D-2 (using 40mm graded stone aggregate) as in sub base complete all as specified and directed. |
| 6 | M&L for 60mm thick coloured machine pressed precast concrete interlocking paver block any shape and size conforming to IS 15658-2006 M -40 Grade with grey cement and pigment complete all as specified and directed. |
| 7 | Taking out of old LT UG cable 1100 volts grade complete all as specified and as directed for the following size of cables :- |
| 8 | 400 sqmm 3.5 core |
| 9 | 240 sqmm 3.5 core |
| 10 | 185 sqmm 3.5 core |
| 11 | 95 to 120 sqmm 3.5 core |
| 12 | 50 sqmm 3.5 core |
| 13 | 25 to 35 sqmm 3.5 core |
| 14 | 10 to 16 sqmm 2/4 core |
| 15 | Supply and Laying XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade complete all as specified and as directed for the following size of cables: - |
| 16 | 400 sqmm 3.5 core |
| 17 | 240 sqmm 3.5 core |
| 18 | 185 sqmm 3.5 core |
| 19 | 120 sqmm 3.5 core |
| 20 | 95 sqmm 3.5 core |
| 21 | 50 sqmm 3.5 core |
| 22 | 35 sqmm 3.5 core |
| 23 | 25 sqmm 3.5 core |
| 24 | 16 sqmm 4 core |
| 25 | 10 sqmm 4 core |
| 26 | 10 sqmm 2 core |
| 27 | Supply and Laying XLPE insulated, armoured heavy duty electric cable with copper conductor, 1100 volts grade including cable gland, clamp, pvc conduit etc and including taking down old unsv cable all as specified and as directed for the following size of cables: - |
| 28 | 240 sqmm 3.5 core |
| 29 | 10 sqmm 4 core |
| 30 | 6 sqmm 4 core |
| 31 | 6 sqmm 2 core |
| 32 | 4 sqmm 2 core |
| 33 | 2.5 sqmm 2 core |
| 34 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. area n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soil complete all as specified and as directed. |
| 35 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. in any type of soil complete all as specified and as directed. |
| 36 | Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point in any type of soil complete all as specified and as directed. |
| 37 | M&L for dry river Sand filling in trenches including punning down consolidation in any type of soil complete all as specified and as directed. NOTE; Punned thickness shall be measured for payment purpose. |
| 38 | Supply and laying of DWC Pipe of 40mm dia complete all as specified and as directed |
| 39 | M&L for tubes, 'light grade', galvanised, with all fitting; laid in trenches for cable/ earth lead protection complete all as specified and as directed of the following sizes: - |
| 40 | 100 mm dia nominal bore |
| 41 | 80 mm dia nominal bore |
| 42 | 50 mm dia nominal bore |
| 43 | 40 mm dia nominal bore |
| 44 | M&L for brick protection of cables in trenches with old size sub-class 'B' bricks complete all as specified and as directed. |
| 45 | M&L for cutting of existing bituminous metal road for laying of cables including demolition of road surface, excavation from bottom level of road upto a depth of 0.55 m from road surface and returning filling of excavated earth and making good the road surface with PCC type C2 (1:3:6) with 40 mm graded aggregate upto a depth of 10 cm from road surface and removing of excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point in any type of soil complete all as specified and as directed.[Note: Laying of cable/ protection pipe will be measured and paid under separate item of this schedule] |
| 46 | Cleaning roof top of MES Installations with wire brush including removing of vegetations complete all as specified and as directed. |
| 47 | M&L for bush cutting and cleaning of area in and around of E/M installations complete all as specified and as directed for the following areas: - |
| 48 | Main Receiving Station No 1 |
| 49 | Main Receiving Station No 2 |
| 50 | Sub-Station No 1 |
| 51 | Sub-Station No 2 |
| 52 | Sub-Station No 3 |
| 53 | Sub-Station No 4 |
| 54 | Sub-Station No 5 |
| 55 | Sub-Station No 6 |
| 56 | Sub-Station No 7 |
| 57 | Sub-Station No 9 |
| 58 | Sub-Station No 10 |
| 59 | S&F insulating LT synthetic rubber mat of size 1 m x 2 m x 12 mm thick class A as per IS: 15652 (2006) complete all as specified and directed. |
| 60 | Taking out cable loop after cable ends from panels, cutting/removing heated cable ends with burnt lugs and inserting new lugs after cutting opening of fresh cable end complete including earth work and relaying cable around for cable size 35 to 240 sqmm complete all as specified and as directed. |
| 61 | Expertise and labour only for load balancing of feeder complete after removing all service cables connected to all three phase , checking these for ohmic value, leakage if any and connecting to all the three phases in such a sequence so that is nearly balanced in all the three phase complete all as specified and as directed. |
| 62 | M&L for design fabrication supply installation testing and commissioning of CPRI approved, factory made cubical LT panel board Outdoor type with double door made out of 2.0 mm thick MS sheet, dust, vermin and water proof fixing on wall, having locking arrangement at front duly fitted with 600 amp rated aluminium electroplated copper busbar 4 strip with compression cable glands for entry & exit of cables, powder coated with two coats complete including taking out of old panel, any type & size complete all as specified and as directed comprising of the following : -(i) MCCB 4 pole, 415 V, 400 Amp,36 kA, including spreader terminals - 01 No (ii) Digital voltmeter 3 phase accuracy class 1 with in-built selector switch - 01 Set (iii) Digital ammeter 3 phase, 5 Amp with in-built selector switch and 3 Nos CTs 600/5 Amp - 01 Set(iv) LED indicating lamps RYB with back up protection rewirable fuse (set of three) - 01 set (v) MCCB 4 pole, 415 V, 250 Amp, 36 kA, including spreader terminals - 01 No (vi) MCCB 4 pole, 415 V, 160 Amp, 36 kA, including spreader terminals - 03 Nos (vii) MCB TPN, 4 Pole, 63 Amp, 10 KA including spreader terminals - 03 Nos |
| 63 | S&F Cable Iugs, aluminum tubular complete all as specified and as directed as per following : |
| 64 | 400 sqmm |
| 65 | 240 sqmm |
| 66 | 185 sqmm |
| 67 | 120 sqmm |
| 68 | 95 sqmm |
| 69 | 70 Sqmm |
| 70 | 50 Sq mm |
| 71 | 35 sqmm |
| 72 | 25 sqmm |
| 73 | 16 sqmm |
| 74 | 10 sqmm |
| 75 | S&F Cable Iugs,copper tubular complete all as specified and as directed as per following : |
| 76 | 240 sqmm |
| 77 | 16 sqmm |
| 78 | 10 sqmm |
| 79 | 6 sqmm |
| 80 | 4 sqmm |
| 81 | M&L for Servicing of Air Circuit Breaker AC three phase 415 volt, 50 Hz, 800 Amp to 1600 Amp including taking shut down and racking out the complete assembly, cleaning of all the parts by air blower, applying suitable chemical (CRC), greasing of all moving parts, checking resistance of all the contact points and refixing the same in original position complete all as specified and as directed. |
| 82 | M&L for MCCB 4 pole, 415 V, 100 Amp, 36 kA including taking out of old one complete all as specified and as directed. |
| 83 | M&L for MCCB 4 pole, 415 V, 125 Amp, 36 kA including taking out of old one complete all as specified and as directed. |
| 84 | M&L for MCCB 4 pole, 415 V, 160 Amp, 36 kA including taking out of old one complete all as specified and as directed. |
| 85 | M&L for MCCB 4 pole, 415 V, 250 Amp, 36 kA including taking out of old one complete all as specified and as directed. |
| 86 | M&L for MCCB 4 pole, 415 V, 400 Amp, 36 kA including taking out of old one complete all as specified and as directed. |
| 87 | M&L for MCCB 4 pole, 415 V, 63 Amp, 25 kA including taking out of old one complete all as specified and as directed. |
| 88 | M&L for MCCB Spreader Terminals 2 Pole including taking out of old one complete all as specified and as directed. |
| 89 | M&L for MCCB Spreader Terminals 3 Pole including taking out of old one all as specified and as directed. |
| 90 | M&L for MCCB Spreader Terminals 4 Pole including taking out of old one complete all as specified and as directed. |
| 91 | S&F Cable jointing kit for LT XLPE Cable (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size upto 90 sqmm complete all as specified and as directed. |
| 92 | S&F Cable jointing kit for LT XLPE Cable (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 sqmm to 240 sqmm complete all as specified and as directed. |
| 93 | M&L for Mild steel plates, plain or chequered, 5mm thick or over in thickness in available sizes for use as duct covers as per existing size including taking out of old one complete all as specified and as directed. |
| 94 | M&L for Maintenance of LT distribution panel after taking proper shutdown including cleaning of enclosure with dry cloth and cleaning of contact points with suitable electrical contact cleaning agent and clean dry cloth, checking of tightness of all the contact points, replacement of defective/ burnt out lugs and bolts & nuts and reporting of major defects if any found during maintenence complete all as specified and as directed for the following: - |
| 95 | LT panel with Incoming ACB upto 1600 Amp 1 No and outgoing MCCBs upto 630 Amp 4 pole upto 8 Nos and Changeover if any |
| 96 | LT panel with Incoming MCCB upto 800 Amp 1 No and outgoing MCCBs upto 400 Amp 4 pole upto 8 Nos, all MCBs, Changeover if any |
| 97 | LT feeder pillar box with Incoming MCCB upto 400 Amp 1 No and outgoing MCCBs upto 250 Amp 4 pole upto 8 Nos and all MCBs |
| 98 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 32x6mm galvanised iron strip including taking out of old strip complete all as specified and as directed. |
| 99 | M&L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex head screw including taking out of old one complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 100 | M&L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex head screw including taking out of old one complete all as specified and as directed. Please Enable Macros to View BoQ information |