| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surfacel recessed medium class PVC conduit as required. |
| 3 | 2 X 2.5 sq. mm +1 X 2.5 sq. mm earth wire |
| 4 | 2 X4 sq. mm + 1 X4 sq. mm earth wire |
| 5 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | 4 X 16 sq. mm + 2X 6 sq. mm earth wire |
| 7 | Providing and laying of spans of 3 ½ core/2 core XLPE Al. cable Armored of various sizes as mentioned below in place of damaged/burnt out / fresh ones of 1.1KV as per IS 7098/ II/ 85 with latest amendements |
| 8 | 185mmsq 3.5 core |
| 9 | Supplying and making end termination with Aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 10 | 185 sq. mm |
| 11 | 120 sq. mm |
| 12 | Providing and fixing following Panel accessories as per requirement, in a cubical Panel with Bus Bars, Indicators, Ammeter, Voltmeter etc, complete job, as IS Standards: 400 A Manual Four pole, Onload, Front-operated Changeover : 1no.Switch MCCB 250Amp,35KA,FPMCCB, 2 no. |
| 13 | Supply, Installation, Testing & Commissioning, cubicle type compartmentalised board made out of 2mm thick CRCA sheet, totally enclosed, IP 42, floor mounted with channel base frame, dust and vermin proof, indoor, suitable for operation on 415V, 50 Hz AC supply with extensible busbars on both sides including control wiring with 2.5 sqmm size wires/cable, interconnection, duly powder coated painting, earthing, labelling etc. including supply & installation of following switchgears, metering instruments, Bus Bars, Indicator, Meters and accessories as per specifications, Complete jobIncomer MCCB 250A, 35-36kA, 4Pole, icu= ics = icw=100% Outgoing MCCB 200A, 25kA, 4Pole, icu= ics = icw=100% Outgoing MCCB 63A, 16kA, 4Pole, icu= ics = icw=100% Outgoing MCB DP 40A, Outgoing MCB SP 5-32A |
| 14 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 15 | 3 pin 5/6 A socket outlet |
| 16 | 5/6 A switch |
| 17 | 15/16A ,5pin socket outlet (forHeating Point) |
| 18 | 15/16A ,6pin socket Switch (forHeating Point) |
| 19 | Supply & fixing of following sizes of PVC conduit along with accessories in surface / recessed including cutting the wall & making good the same in case of recessed conduit as required, (for conduiting in working stations From junction box in raceway.) 25/32 mm |
| 20 | Supplying and Fixing 25 mm Double Locked PVC Channel 2 mm thick |
| 21 | 4 feet long LED batten 6000/6500k Light with anti-glare diffuser with energy efficient electronic driver CRI greater than 80 with minimum sytem lumens 4000 and maximum wattage24 including connection with multistrand copper conductor 3 core cable etc as required at site with burning hours >= 50000 Hours having system lumens 110 Lm/watt. |
| 22 | Supply of Led fixture 600mmX600mm 36-40W Surface / Recess mounted fixture with HET Plastic diffuser with minimum system lumen efficacy of 100 lm/W with CRCA housing having P.F.>0.95 with THD<10% ,CRI 80.The LED with Useful life of 50000 Hrs at L70. The LEDs used in the luminaire shall have CCT of 3000-6500 K with CRI of minimum 80. The Input voltage range shall be 150V to 270V .Fixture have Surge Protection 2kV .Driver Output voltage shall be less than SELV Limits for safe operation and maintenance. |
| 23 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker IK09 and IP43 suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 24 | Single pole 5-32 A |
| 25 | Double pole 40A |
| 26 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required.(But without MCB/RCCB/Isolator) |
| 27 | 16 way, Double door |
| 28 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 29 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 30 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 31 | Supply installation testing and commissioning of following sizes of plastic body exhaust fans shutter type with Heavy duty motor Rated speed = 1400 RPM . RAte voltage -220 to 240 Volts, 300MM Please Enable Macros to View BoQ information |