| Sl. No. | Item Description |
| 1 | Fabrication Installationand commissioning of ACB Panel , Outdoor type double door, slopping canopy, made of 3.0 mm thich Stainless steel -grade 304 Sheet and angle Iron frame work 50 x50x6mm with, cubical type and all MCCB to be connected to busbar via spider link with copper bus bar of 1000 Amps and with suitable mounting plate, frame and canopy, confirms to following: i). ACB shall comply with standards IS/IEC 60947-1 & 2.ii). ACB shall have an operational voltage of 690V AC, rated insulation voltage of 1000 volts AC, rated for impulse voltage of 12kV. iii). ACB shall be of 4pole . it shall be TP with solid link in neutral. iv). ACBs shall be offered in frame sizes that are optimum for optimum panel dimensions. v). ACB shall omply with the environmental directives like RoHS. Product Environmental Profile shall be furnished to understand the environmental impact. vi). ACB shall have the breaking performance Icu = Ics = Icw (1sec) vii). ACBs shall be colour coded and shall be identifiable for different breaking capacities based on the colour code used. viii). ACBs shall have provision for terminal separator by construction. ix). It shall NOT be possible to rack out the ACB in ON condition and suitable racking handle shutter interlock with padlock arrangement shall be provided to ensure the safety of User and to avoid accidents.x). All air circuit breaker shall be fully tropicalized as standard & suitable for terminating copper bus bars. xi) ACBs shall be provided with terminal adapters for proper cable connections/bus duct connections. Terminal Adaptor orientation for top and bottom side shall be possible to be changed from vertical to horizontal or vice versa on site as per cable/bus duct entry. xii) Air circuit breaker shall be provided with electronic protection unit, with trip units shall have led Matrix/ LCD display with current measurement xiii). The circuit breaker control unit shall measure the true r.m.s value of the current xiv).All trip units provided shall have switchable thermal memory as standard. |
| 2 | xv). The Inbuilt protection release shall have following protections as standard: - a. Long time delay protection against overloads Ir from 0.2 to 1 x In (Step 1A) – OFF b. Long delay protection operation time tr = 40 ms ÷ 30 s c. Short time delay protection against short circuits Isd from 1,5Ir to 10 Ir – OFF d. Short time delay protection operation time (t=k, I2t=k) tsd = 40 ms ÷ 1 s e. Instantaneous protection against very high short circuits li from 2 to 15 In - OFF f. Earth fault current Ig from 0.2 ÷ 1In – OFF g. Time delay on earth fault tripping (t=k, I2t=k) tg from 80 ms ÷ 1s h. Neutral protection IN = 50% - 100% - 150% - 200% - OFF i. Overtemperature protection – an alarm shall be generated for temperature exceeding 75 °C and ACB shall trip for temperatures exceeding 95 °C inside the circuit breaker.xvi). All trip units shall have digital trip counter and shall offer ready summary of the no. of trips on account of individual faults. xvii). The trip unit shall be communication capable and shall be possible to upgrade for connectivity over Modbus without changing the trip unit in future. xviii). The trip unit shall have integral test button on front to test operation and the opening of the poles to verify the healthiness. xix). It shall be possible to monitor the status of the breaker, read information (firmware versions, device version, alarms, measurements, parameters, fault history), view the trip curve characteristics, generate reports based on the data stored and read by the protection unit by way of a manufacturer provided software. The connectivity shall be easily established by way of the micro-USB port. xx). Make: Legrand DMX, Schneider NW, Siemens 3WA The ACB Panel should have following incoming and outgoing connections. |
| 3 | (a) Incomer- ACB 800 A, 4 pole, 65 kA, 415V, Manual Drawout type |
| 4 | (b) Outgoings |
| 5 | (i) MCCB 160 A , adjustable type 4 pole, 36 kA-04 |
| 6 | (ii) MCCB 125 A , adjustable type 4 pole, 25 kA -04 |
| 7 | (iii) MCCB 100 A , adjustable type 4 pole, 25 kA - 02 |
| 8 | (iv) MCCB 63 A , adjustable type 4 pole, 16 kA - 01 |
| 9 | (viii) Digital panel meter for volt/Amp/KWH/H&PF, necessary CT- 01 No |
| 10 | (ix) LED Indicating lamp set - 01 set of three |
| 11 | (x) Timer switch (Auto switching device operating on real time) digital type with min switching time of 1 sec |
| 12 | Fabrication Installationand commissioning of ACB Panel , Indoor type , made of 2.0 mm thich Stainless steel -grade 304 Sheet and angle Iron frame work 50 x50x6mm with, cubical type and all MCCB to be connected to busbar via spider link with copper bus bar of 800 Amps and with suitable mounting plate, frame and canopy, confirms to following : i). ACB shall comply with standards IS/IEC 60947-1 & 2.ii). ACB shall have an operational voltage of 690V AC, rated insulation voltage of 1000 volts AC, rated for impulse voltage of 12kV.iii). ACB shall be of 4pole . it shall be TP with solid link in neutral.iv). ACBs shall be offered in frame sizes that are optimum for optimum panel dimensions. v). ACB shall comply with the environmental directives like RoHS. Product Environmental Profile shall be furnished to understand the environmental impact. vi). ACB shall have the breaking performance Icu = Ics = Icw (1sec) vii). ACBs shall be colour coded and shall be identifiable for different breaking capacities based on the colour code used. viii). ACBs shall have provision for terminal separator by construction. ix). It shall NOT be possible to rack out the ACB in ON condition and suitable racking handle shutter interlock with padlock arrangement shall be provided to ensure the safety of User and to avoid accidents. x). All air circuit breaker shall be fully tropicalized as standard & suitable for terminating copper bus bars. xi). ACBs shall be provided with terminal adapters for proper cable connections/bus duct connections. Terminal Adaptor orientation for top and bottom side shall be possible to be changed from vertical to horizontal or vice versa on site as per cable/bus duct entry. xii). Air circuit breaker shall be provided with electronic protection unit, with trip units shall have led Matrix/ LCD display with current measurement xiii). The circuit breaker control unit shall measure the true r.m.s value of the current xiv). All trip units provided shall have switchable thermal memory as standard. |
| 13 | xv). The Inbuilt protection release shall have following protections as standard: - a. Long time delay protection against overloads Ir from 0.2 to 1 x In (Step 1A) – OFF b. Long delay protection operation time tr = 40 ms ÷ 30 s c. Short time delay protection against short circuits Isd from 1,5Ir to 10 Ir – OFF d. Short time delay protection operation time (t=k, I2t=k) tsd = 40 ms ÷ 1 s e. Instantaneous protection against very high short circuits li from 2 to 15 In - OFF f. Earth fault current Ig from 0.2 ÷ 1In – OFF g. Time delay on earth fault tripping (t=k, I2t=k) tg from 80 ms ÷ 1s h. Neutral protection IN = 50% - 100% - 150% - 200% - OFFi. Overtemperature protection – an alarm shall be generated for temperature exceeding 75 °C and ACB shall trip for temperatures exceeding 95 °C inside the circuit breaker.xvi). All trip units shall have digital trip counter and shall offer ready summary of the no. of trips on account of individual faults. xvii). The trip unit shall be communication capable and shall be possible to upgrade for connectivity over Modbus without changing the trip unit in future. viii). The trip unit shall have integral test button on front to test operation and the opening of the poles to verify the healthiness. xix). It shall be possible to monitor the status of the breaker, read information (firmware versions, device version, alarms, measurements, parameters, fault history), view the trip curve characteristics, generate reports based on the data stored and read by the protection unit by way of a manufacturer provided software. The connectivity shall be easily established by way of the micro-USB port. xx). Make: Legrand DMX, Schneider NW, Siemens 3WA The ACB Panel should have following incoming and outgoing connections. |
| 14 | (a) Incomer- ACB 630 A, 4 pole, 65 kA, 415V, Manual Drawout type |
| 15 | (b) Outgoings |
| 16 | (i) MCCB 160 A , 4 pole, 36 kA-03 |
| 17 | (ii) MCCB 125 A , 4 pole, 36 kA -02 |
| 18 | (iii) MCCB 100 A , 4 pole, 36 kA - 02 |
| 19 | (iv) MCCB 63 A , 4 pole, 16 kA - 01 |
| 20 | (viii) Digital panel meter for volt/Amp/KWH/H&PF, necessary CT- 01 No |
| 21 | (ix) LED Indicating lamp set - 01 set of three |
| 22 | (x) Timer switch (Auto switching device operating on real time) digital type with min switching time of 1 sec |
| 23 | Fabrication Installationand commissioning of LT Panel , Outdoor type double door, made of 2.0 mm thich Stainless steel grade 304 Sheet and angle Iron frame work of size 50 x50 x 5 mm with 300 mm height , double sloping, cubical type with copper bus bar and with suitable mounting plate, frame and canopy, confirms to latest with following MCCB specifications : (Location - Infront GE(P) Office)i). MCB shall offer protection against overload and short circuitii). MCB shall conform to IS / IEC 60898‐1(2002) with ISI/ CE mark on the product. iii) MCB shall have minimum breaking capacity of 10kAiv). MCB shall conform to Energy limitation class 3 ensuring minimum let through energy making installation safev). MCB shall have no line load bias offering flexibility to uservi). MCB shall offer IP 20 protected terminalsvii). MCB shall have safety shutters on the terminals for additional safetyviii). MCB shall have sliding bottom clamp to enable easy fixation and removal of the product from the bankix). MCB shall have integrated label holder for easy identification of circuitx). MCB shall have pull up terminals avoiding false insertion of the cablesxi). MCB shall have Minimum operating voltage 12 V AC/ DCxii). MCB shall provide facility for padlocking in position both ON/OFF positionxiii). All Multi pole MCBs must have internal integral inbuilt common trip bar to open all poles simultaneouslyxiv). MCB made up of self-extinguishing, heat- and fire-resistant material according to IEC 60898-1 and glow-wire tested at 960°C |
| 24 | (a) Incomer- MCCB 250 A, 4 pole, 50 KA |
| 25 | (b) Outgoings |
| 26 | (i) MCCB 100 A , 4 pole, 35/36 kA - 06 Nos |
| 27 | (vi) Digital panel meter for volt/Amp/KWH/H&PF, necessary CT- 01 No |
| 28 | (vii) LED Indicating lamp set - 01 set of three |
| 29 | Fabrication Installationand commissioning of LT Panel , Outdoor type double door, made of 2.0 mm thich Stainless steel grade 304 Sheet and angle Iron frame work of size 50 x50 x 5 mm with 300 mm height , double sloping, cubical type with copper bus bar and with suitable mounting plate, frame and canopy, confirms to latest with following MCCB specifications : (Location - Infront post office)i). MCB shall offer protection against overload and short circuitii). MCB shall conform to IS / IEC 60898‐1(2002) with ISI/ CE mark on the productiii). MCB shall have minimum breaking capacity of 10kAiv). MCB shall conform to Energy limitation class 3 ensuring minimum let through energy making installation safev). MCB shall have no line load bias offering flexibility to uservi). MCB shall offer IP 20 protected terminalsvii). MCB shall have safety shutters on the terminals for additional safetyviii). MCB shall have sliding bottom clamp to enable easy fixation and removal of the product from the bankix). MCB shall have integrated label holder for easy identification of circuitx). MCB shall have pull up terminals avoiding false insertion of the cablesxi). MCB shall have Minimum operating voltage 12 V AC/ DCxii). MCB shall provide facility for padlocking in position both ON/OFF positionxiii). All Multi pole MCBs must have internal integral inbuilt common trip bar to open all poles simultaneouslyxiv). MCB made up of self-extinguishing, heat- and fire-resistant material according to IEC 60898-1 and glow-wire tested at 960°C |
| 30 | (a) Incomer- MCCB 250 A, 4 pole, 50 KA |
| 31 | (b) Outgoings |
| 32 | (i) MCCB 125 A , 4 pole, 35/36 kA - 02 Nos |
| 33 | (i) MCCB 100 A , 4 pole, 25 kA - 04 Nos |
| 34 | (vi) Digital panel meter for volt/Amp/KWH/H&PF, necessary CT- 01 No |
| 35 | (vii) LED Indicating lamp set - 01 set of three |
| 36 | Fabrication Installationand commissioning of LT Panel , Outdoor type double door, made of 2.0 mm thich Stainless steel grade 304 Sheet and angle Iron frame work of size 50 x50 x 5 mm with 300 mm height , double sloping, cubical type with copper bus bar and with suitable mounting plate, frame and canopy, confirms to latest with following MCCB specifications : (Location - Sports ground)i). MCB shall offer protection against overload and short circuitii). MCB shall conform to IS / IEC 60898‐1(2002) with ISI/ CE mark on the productiii). MCB shall have minimum breaking capacity of 10kAiv). MCB shall conform to Energy limitation class 3 ensuring minimum let through energy making installation safev). MCB shall have no line load bias offering flexibility to uservi). MCB shall offer IP 20 protected terminalsvii). MCB shall have safety shutters on the terminals for additional safetyviii). MCB shall have sliding bottom clamp to enable easy fixation and removal of the product from the bankix). MCB shall have integrated label holder for easy identification of circuitx). MCB shall have pull up terminals avoiding false insertion of the cablesxi). MCB shall have Minimum operating voltage 12 V AC/ DCxii). MCB shall provide facility for padlocking in position both ON/OFF positionxiii). All Multi pole MCBs must have internal integral inbuilt common trip bar to open all poles simultaneouslyxiv). MCB made up of self-extinguishing, heat- and fire-resistant material according to IEC 60898-1 and glow-wire tested at 960°C |
| 37 | (a) Incomer- MCCB 160 A, 4 pole, 36 KA |
| 38 | (b) Outgoings |
| 39 | (i) MCCB 100 A , 4 pole, 25 kA - 01 Nos |
| 40 | (ii) MCCB 63 A , 4 pole, 25 kA - 03 Nos |
| 41 | (iii) MCB 63 A , 2 pole, C curve - 03 Nos |
| 42 | (iv) Digital panel meter for volt/Amp/KWH/H&PF, necessary CT- 01 No |
| 43 | (v) LED Indicating lamp set - 01 set of three |
| 44 | Fabrication Installationand commissioning of LT Panel , Outdoor type double door, made of 2.0 mm thich Stainless steel grade 304 Sheet and angle Iron frame work of size 50 x50 x 5 mm with 300 mm height , double sloping, cubical type with copper bus bar and with suitable mounting plate, frame and canopy, confirms to latest with following MCCB specifications : (Location - Infront SVK)i). MCB shall offer protection against overload and short circuitii). MCB shall conform to IS / IEC 60898‐1(2002) with ISI/ CE mark on the productiii). MCB shall have minimum breaking capacity of 10kA iv) MCB shall conform to Energy limitation class 3 ensuring minimum let through energy making installation safev). MCB shall have no line load bias offering flexibility to uservi). MCB shall offer IP 20 protected terminalsvii). MCB shall have safety shutters on the terminals for additional safetyviii). MCB shall have sliding bottom clamp to enable easy fixation and removal of the product from the bankix). MCB shall have integrated label holder for easy identification of circuitx). MCB shall have pull up terminals avoiding false insertion of the cablesxi). MCB shall have Minimum operating voltage 12 V AC/ DCxii). MCB shall provide facility for padlocking in position both ON/OFF positionxiii). All Multi pole MCBs must have internal integral inbuilt common trip bar to open all poles simultaneouslyxiv). MCB made up of self-extinguishing, heat- and fire-resistant material according to IEC 60898-1 and glow-wire tested at 960°C |
| 45 | (a) Incomer- MCCB 400 A, 4 pole, 50 KA |
| 46 | (b) Outgoings |
| 47 | (i) MCCB 125 A , 4 pole, 35/36 kA - 06 Nos |
| 48 | (ii) MCCB 100 A , 4 pole, 25 kA - 01 Nos |
| 49 | (iii) MCB 63 A , 2 pole, C curve - 01 Nos |
| 50 | (iv) Digital panel meter for volt/Amp/KWH/H&PF, necessary CT- 01 No |
| 51 | (v) LED Indicating lamp set - 01 set of three |
| 52 | M&L for of servicing of LT feeder pillar/ panels by making arrangements of following for one incoming and 08 outgoing upto 300 sqmm cable size panel :(i) Complete cleaning of inside of panel by removing all the incoming and outgoing LT cables and scrubbing the surface to remove any dirt or other sticky items.(ii) Checking the condition of cable terminations and lugs and changing of damaged lugs (35 -300 sqmm )complete by cable cutting and making new termination.(iii) Checking the condition of MCCB, MCB etc and replacement of old burnt MCB/MCCB complete ( Note :New MCB will be paid saparetly under sch of items).(iv) Checking the dondition of front and back doors of the panel and repairing of the door hinges with new by means of making drilled holes in panel and providing new hinges to doors.(v) Consealing all openings of the LT panel by means of applying sealing agent to protect the panel against rodents/snakes entry.(vi) Removal of existing busbar and scrapping existing heat shrinkable sleeves and providing new colour combination heat shrinkable sleeves complete. |
| 53 | M&L for of servicing of LT feeder pillar/ panels by making arrangements of following for one incoming and 10 outgoing upto 400 sqmm cable size panel :(i) Complete cleaning of inside of panel by removing all the incoming and outgoing LT cables and scrubbing the surface to remove any dirt or other sticky items.(ii) Checking the condition of cable terminations and lugs and changing of damaged lugs (35 -300 sqmm )complete by cable cutting and making new termination.(iii) Checking the condition of MCCB, MCB etc and replacement of old burnt MCB/MCCB complete ( Note :New MCB will be paid saparetly under sch of items).(iv) Checking the dondition of front and back doors of the panel and repairing of the door hinges with new by means of making drilled holes in panel and providing new hinges to doors.(v) Consealing all openings of the LT panel by means of applying sealing agent to protect the panel against rodents/snakes entry.(vi) Removal of existing busbar and scrapping existing heat shrinkable sleeves and providing new colour combination heat shrinkable sleeves complete. |
| 54 | M&L for of servicing of LT feeder pillar/ panels by making arrangements of following for one incoming and upto 06 outgoing upto 240 sqmm cable size panel :(i) Complete cleaning of inside of panel by removing all the incoming and outgoing LT cables and scrubbing the surface to remove any dirt or other sticky items.(ii) Checking the condition of cable terminations and lugs and changing of damaged lugs (35 -300 sqmm )complete by cable cutting and making new termination.(iii) Checking the condition of MCCB, MCB etc and replacement of old burnt MCB/MCCB complete ( Note :New MCB will be paid saparetly under sch of items).(iv) Checking the dondition of front and back doors of the panel and repairing of the door hinges with new by means of making drilled holes in panel and providing new hinges to doors.(v) Consealing all openings of the LT panel by means of applying sealing agent to protect the panel against rodents/snakes entry.(vi) Removal of existing busbar and scrapping existing heat shrinkable sleeves and providing new colour combination heat shrinkable sleeves complete. |
| 55 | M&L for of servicing of ACB panels upto 1250 Amp by making arrangements of following for one incoming and upto 06 outgoing upto 240 sqmm cable size panel :(i) Complete cleaning of inside of panel by removing all the incoming and outgoing LT cables and scrubbing the surface to remove any dirt or other sticky items.(ii) Checking the condition of cable terminations and lugs and changing of damaged lugs (35 -300 sqmm )complete by cable cutting and making new termination.(iii) Checking the condition of MCCB, MCB etc and replacement of old burnt MCB/MCCB complete ( Note :New MCB will be paid saparetly under sch of items).(iv) Checking the dondition of front and back doors of the panel and repairing of the door hinges with new by means of making drilled holes in panel and providing new hinges to doors.(v) Consealing all openings of the LT panel by means of applying sealing agent to protect the panel against rodents/snakes entry.(vi) Removal of existing busbar and scrapping existing heat shrinkable sleeves and providing new colour combination heat shrinkable sleeves complete. |
| 56 | M&L for removal of old paint by scrapping the existing panel by means of electromechanical methods complete and compressed air spray painting of existing VCB panel of upto 1200 Amp with epoxy paint with one coat of read oxide (mechanical means) and two coats of epoxy paint smoke gray colour. |
| 57 | M&L for removal of old paint by scrapping the existing panel by means of electromechanical methods complete and compressed air spray painting of existing LT panel of upto 10 outgoing with epoxy paint with one coat of read oxide (mechanical means) and two coats of epoxy paint smoke gray colour. |
| 58 | S & F 4 way connector, bolt type having locking arrangement, weather proof and water proof control space with MCB,SP,6A,230V, B series, 10KA mounted on and including 3mm thick plastic laminated sheet Suitable for LT feeder pillar / street light pole complete all as specified and directed. |
| 59 | Supply and fix analogue time switch(Daily time switch) suitable for outdoor ,power contactor 63 Amps ML-2 type, 3Phase, 415 volts and MCB TPN 63 Amps,10 KA 'C' series, including bus bar of suitable capacity with arrangement of auto/mannual control switch duly prewired and all accessories same shall be enclosed in and including sheet metal enclosure of 3.2 mm thick CRCA sheet of adequate size with powder coated, fixing arrangements on floor including powder coated painting and mounted on 50x50x6mm MS angle iron frame duly painting complete all as specified and directed. |
| 60 | M&L for fixing of new LT TPN connectors inside octagonal including removal od old burnt porcelin/PVC TPN connectors complete including disconnecting and reconnecting of cable with lugs/thimbles all as specified and directed. |
| 61 | Supply and fixing of MCCB 400 Amps 4 Pole, with breaking capacity 36 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 62 | Supply and fixing of MCCB 320/350 Amps 4 Pole, with breaking capacity 36 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 63 | Supply and fixing of MCCB 125 Amps 4 Pole, with breaking capacity 25 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 64 | Supply and fixing of MCCB 100 Amps 4 Pole, with breaking capacity 16 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 65 | Supply and fixing of MCCB 63 Amps 4 Pole, with breaking capacity 16 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 66 | Supply and fixing of MCCB 160 Amps 4 Pole, with breaking capacity 36 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 67 | Supply and fixing of MCCB 200 Amps 4 Pole, with breaking capacity 36 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 68 | Supply and fixing of MCCB 250 Amps 4 Pole, with breaking capacity 36 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 69 | Supply and fixing of MCCB 125 Amps 3 Pole, with breaking capacity 16 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 70 | Supply and fixing of MCCB 100 Amps 3 Pole, with breaking capacity 16 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 71 | Supply and fixing of MCCB 63 Amps 3 Pole, with breaking capacity 16 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 72 | Supply and fixing of MCCB 160 Amps 3 Pole, with breaking capacity 25 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 73 | Supply and fixing of MCCB 200 Amps 3 Pole, with breaking capacity 25 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 74 | Supply and fixing of MCCB 250 Amps 3 Pole, with breaking capacity 36 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 75 | Supply and fixing MCCB SS Enclosure only of MCCB 400 Amps 4 Pole, with breaking capacity 50 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 76 | Supply and fixing MCCB SS Enclosure only of MCCB 320 Amps 4 Pole, with breaking capacity 50 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 77 | Supply and fixing MCCB SS Enclosure only of MCCB 125 Amps 4 Pole, with breaking capacity 25 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 78 | Supply and fixing MCCB SS Enclosure only of MCCB 100 Amps 4 Pole, with breaking capacity 16 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 79 | Supply and fixing MCCB SS Enclosure only of MCCB 63 Amps 4 Pole, with breaking capacity 16 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 80 | Supply and fixing MCCB SS Enclosure only of MCCB 160 Amps 4 Pole, with breaking capacity 25 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 81 | Supply and fixing MCCB SS Enclosure only of MCCB 200 Amps 4 Pole, with breaking capacity 25 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 82 | Supply and fixing MCCB SS Enclosure only of MCCB 250 Amps 4 Pole, with breaking capacity 36 KA, as per site requirement and including removal of old MCCB complete all as specified and directed. |
| 83 | Supply and fixing changeover switch 250 Amps 4 Pole, with SS metal enclosure breaking capacity 36 KA, as per site requirement and including removal of old changeover switch complete all as specified and directed. |
| 84 | Supply and fixing changeover switch 125 Amps 4 Pole, with with SS metal enclosure breaking capacity 36 KA, as per site requirement and including removal of old changeover switch complete all as specified and directed. |
| 85 | Supply and fixing changeover switch 400 Amps 4 Pole, with with SS metal enclosure breaking capacity 36 KA, as per site requirement and including removal of old changeover switch complete all as specified and directed. |
| 86 | Supply and fixing of HRC fuse of capacity 250 Amps complete. |
| 87 | Supply and fixing of HRC fuse of capacity 63 Amps complete. |
| 88 | Supply and fixing of AC contactor ML-2 of capacity 63 Amps complete. |
| 89 | Supply only Aluminum lugs for cable 120 to 400 sqmm, 3.5 core complete all as specified and directed. |
| 90 | Supply only Aluminum lugs for cable 25 to 95 sqmm, 3.5 core complete all as specified and directed. |
| 91 | Supply only Aluminum lugs for cable 6 to 16 sqmm, 4 core complete all as specified and directed. |
| 92 | Supply only Aluminum glands for cable 120 to 400 sqmm, 3.5 core complete all as specified and directed. |
| 93 | Supply only Aluminum glands for cable 25 to 95 sqmm, 3.5 core complete all as specified and directed. |
| 94 | Supply only Aluminum glands for cable 6 to 16 sqmm, 4 core complete all as specified and directed. |
| 95 | Supply only Aluminum ferrules for cable 120 to 400 sqmm, 3.5 core complete all as specified and directed. |
| 96 | Supply only Aluminum ferules for cable 25 to 95 sqmm, 3.5 core complete all as specified and directed. |
| 97 | Supply only Aluminum ferules for cable 6 to 16 sqmm, 4 core complete all as specified and directed. |
| 98 | Supply and fixing of selector switch as make suitable at site complete. |
| 99 | Supply and fixing of rubber packing in LT panel after removal of existing rubber packing complete. |
| 100 | Supply and fixing of lock in LT panels after removal of old broken locks complete. |
| 101 | Taking down unserviceable LT cable from trenches, poles, floor, pipe etc complete all as specified and directed |
| 102 | Supply and laying cable XLPE insulated, armored heavy duty electric cable, galvanized steel strip or wire armored, with aluminum conductor electric power cable(heavy duty) 1100 volts grade with stranded aluminum conductor of size 10 sqmm x 2 core |
| 103 | Supply and laying cable XLPE insulated, armored heavy duty electric cable, galvanized steel strip or wire armored, with aluminum conductor electric power cable(heavy duty) 1100 volts grade with stranded aluminum conductor of size 10 sqmm x 4 core complete all as specified and directed. |
| 104 | Supply and laying cable XLPE insulated, armoured heavy duty electric cable, galvanised steel strip or wire armoured, with aluminium conductor electric power cable(heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sqmm x 4 core complete all as specified and directed. |
| 105 | Supply and laying cable XLPE insulated, armoured heavy duty electric cable, galvanized steel strip or wire armoured, with aluminium conductor electric power cable(heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 sqmm x 3.5 core complete all as specified and directed. |
| 106 | Description all as per item no.58 above but 35 sqmm, 3.5 core |
| 107 | Description all as per item no.58 above but 50 sqmm, 3.5 core |
| 108 | Description all as per item no.58 above but 95 sqmm, 3.5 core |
| 109 | Description all as per item no.58 above but 120 sqmm, 3.5 core |
| 110 | Description all as per item no.58 above but 150 sqmm, 3.5 core |
| 111 | Description all as per item no.58 above but 185 sqmm, 3.5 core |
| 112 | Description all as per item no.58 above but 240 sqmm, 3.5 core |
| 113 | Description all as per item no.58 above but 300 sqmm, 3.5 core |
| 114 | Description all as per item no.58 above but 400 sqmm, 3.5 core |
| 115 | Excavation in trenches n.exc 1.5 m wide and n. exc 1.5 m in depth and getting out in soft/loose soil for removing/laying of cables complete all as specified and as directed. |
| 116 | Returning, filling including spreading , leveling , watering and well ramming in layers n.exc 25 cm complete all as specified and as directed. |
| 117 | Removing excavated material to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed. |
| 118 | Supplying and laying High density polyethylene pipes (HDPE)-DWC 50 mm bore of pressure rating 6 kgf/cm2 laid in trenches for cable protection complete all as specified and directed. |
| 119 | Supplying and laying High density polyethylene pipes (HDPE)-DWC 100 mm bore of pressure rating 6 kgf/cm2 laid in trenches for cable protection complete all as specified and directed. |
| 120 | M&L of GI pipe 80 mm dia light grade with all fittings for cable protection complete all as specified and directed. |
| 121 | M&L of GI pipe 50 mm dia light grade with all fittings for cable protection complete all as specified and directed. |
| 122 | M&L for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation filling & mass concrete complete all as specified and directed. |
| 123 | M&L for PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) as in coping / fountation of poles including use of form work and finishing all exposed faces of concrete as per clause 4.11.66 (a) & (d) of SSR Part-I complete all as specified and directed. |
| 124 | Supplying and laying unreinforced precast concrete cable cover class LV type 1, flat, size 250 x 150 x 40 mm complete all as specified and directed by the Engineer - in - charge. |
| 125 | Supply and fixing in repair of LED street light fitting new generation energy saving and environment friendly long life LED 60 Watt with following specifications: 230 V AC outdoor type,top opening , IK-08, seperate driver compartment, input voltage AC 140V-270V, power factor > 0.95, beam angle 140 x 90 degree , colour temperature 6500 K , rated life 50,000 Hours , Pressure die cast aluminum hosing and heat resistant with tempered PC cover with integrated lens, efficiency 120 lumen/watt ,BIS Certified to LM-79/LM-80 lamp with impact and corrosion resistant including thermal management , over-voltage,short circuit ,open circuit and 6 kV surge protection in multiple optics complete with IP 66 protection including bracket of suitable size with manufacture warrenty complete all as specified and as directed by engineer-in-charge. |
| 126 | Supply and fixing in repair of LED street light fitting new generation energy saving and environment friendly long life LED 70 Watt with following specifications: 230 V AC outdoor type,top opening , IK-10, seperate driver compartment, input voltage AC 140V-270V, power factor > 0.95, beam angle 180 x 90 degree , colour temperature 6500 K , rated life 50,000 Hours , Pressure die cast aluminum hosing and heat resistant with tempered PC cover with integrated lens, efficiency 145 lumen/watt ,BIS Certified to LM-79/LM-80 lamp with impact and corrosion resistant including thermal management , over-voltage,short circuit ,open circuit and 6 kV surge protection in multiple optics complete with IP 66 protection including bracket of suitable size with manufacture warrenty complete all as specified and as directed by engineer-in-charge. |
| 127 | Supply and fixing in repair of LED street light fitting new generation energy saving and environment friendly long life LED 90 Watt with following specifications: 230 V AC outdoor type,top opening , IK-10, seperate driver compartment, input voltage AC 140V-270V, power factor > 0.95, beam angle 180 x 90 degree , colour temperature 6500 K , rated life 50,000 Hours , Pressure die cast aluminum hosing and heat resistant with tempered PC cover with integrated lens, efficiency 145 lumen/watt ,BIS Certified to LM-79/LM-80 lamp with impact and corrosion resistant including thermal management , over-voltage,short circuit ,open circuit and 6 kV surge protection in multiple optics complete with IP 66 protection including bracket of suitable size with manufacture warrenty complete all as specified and as directed by engineer-in-charge. |
| 128 | Supply and fixing in repair of LED flood light fitting new generation energy saving and environment friendly long life LED 210 Watt with following specifications: 230 V AC outdoor type,top opening , IK-10, seperate driver compartment, input voltage AC 140V-270V, power factor > 0.95, beam angle 180 x 90 degree , colour temperature 6500 K , rated life 50,000 Hours , Pressure die cast aluminum hosing and heat resistant with tempered PC cover with integrated lens, efficiency 140 lumen/watt ,BIS Certified to LM-79/LM-80 lamp with impact and corrosion resistant including thermal management , over-voltage,short circuit ,open circuit and 6 kV surge protection in multiple optics complete with IP 66 protection including bracket of suitable size with manufacture warrenty complete all as specified and as directed by engineer-in-charge. |
| 129 | Supply and fixing in repair of LED secuirty light fitting new generation energy saving and environment friendly long life LED 35 Watt with following specifications: 230 V AC outdoor type,top opening , IK-08, seperate driver compartment, input voltage AC 140V-270V, power factor > 0.95, beam angle 140 x 90 degree , colour temperature 6500 K , rated life 50,000 Hours , Pressure die cast aluminum hosing and heat resistant with tempered PC cover with integrated lens, efficiency 120 lumen/watt ,BIS Certified to LM-79/LM-80 lamp with impact and corrosion resistant including thermal management , over-voltage,short circuit ,open circuit and 4 kV surge protection in multiple optics complete with IP 66 protection including bracket of suitable size with manufacture warrenty complete all as specified and as directed by engineer-in-charge. |
| 130 | Supply and drawing through conduit pipe on pole/ wall for making connection to the light fittings 3 Core, Copper cable,PVC insulated and sheathed heavy duty 1100 volt grade multi stranded copper conductor (FRLS) cable 1.5 Sqmm complete all specified and directed |
| 131 | Taking out existing unserviceable FRP terminal box and S&F mounting type weather proof terminal box of size 155 x 155 x100 mm heavy duty (machine mould) consisting of 01 No MCB SP 06 Amps and backlite connector of 32 A for Three phase and neutral (Four terminals) for cable in cable out entire complete. Terminal box to be fixed to wall/ Pole complete all as specified and directed. Make : Sintex/national |
| 132 | Taking out existing unserviceable FRP terminal box and S&F mounting type weather proof terminal box of size 250 x 250 x105 mm heavy duty (machine mould) consisting of 01 No MCB SP 06 Amps and backlite connector of 32 A for Three phase and neutral (Four terminals) for cable in cable out entire complete. Terminal box to be fixed to Pole complete all as specified and directed. Make : Sintex/national |
| 133 | Supply and fix in replacement pipe bracket made out of 40 mm dia GI pipe, medium grade, upto 1.5 mtr long, bent to shape and fixed on existing pole/ wall including necessary clamp/saddle and fixing by screw/bolt complete all as specified and directed. |
| 134 | Supply and fix in replacement pipe bracket made out of 25 mm dia GI pipe, medium grade, upto 1.5 mtr long, bent to shape and fixed on existing pole/ wall including necessary clamp/saddle and fixing by screw/bolt complete all as specified and directed. |
| 135 | Supply and fixing in replacement analog timer switch 3P module, 24 Hrs preprogram complete all as specified and directed |
| 136 | M&L for LT straight through joint heat shrinkable kit suitable for 3 ½ / 4 core of size 10 to 16 sqmm underground cable all as specified and directed. |
| 137 | Description all as per item no.91 above but 25 to 50 sqmm |
| 138 | Description all as per item no.91 above but 70 to 120 sqmm |
| 139 | Description all as per item no.91 above but 150 to 185 sqmm |
| 140 | Description all as per item no.91 above but 240 to 400 sqmm |
| 141 | M&L for finding faults of LT UG XLPE cable of any size and any length upto 70 Sqmm by using computerized / primary current injection method / any other method as directed by the Engr-in-charge and locating fault, cutting and removing the faulty portion of the cable and jointing with suitable cable joint including exaction, refilling and testing after jointing all as required and directed for cable upto 70 sqmm. Note: Joints shall be paid for separately. |
| 142 | Description all as per item no.96 above but 70 to 120 sqmm |
| 143 | Description all as per item no.96 above but 150 to 185 sqmm |
| 144 | Description all as per item no.96 above but 240 to 400 sqmm |
| 145 | M&L Earthing complete with galvanized steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanized earth lead strip 25 x 4 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed |
| 146 | M&L for tree trimming not more than 6 inch thick branch surrounding the street light pole for and area of 03 metre all around the pole or as directed by engineer-in-charge for upto height of 12 meters complete and depositing the branches to a designated place as shown by engineer-in-charge. |
| 147 | Surface dressing n. exc 15 Cm of surrounding area of power house, LT panel and any out door installation in soft/ loose soil (including bush Cutting)complete all as specified and directed |
| 148 | M & L for Structural steel, rolled section such as joist, beam, channel, angle, Tee, in available lengths for structural farm of panel complete all as specified and directed Please Enable Macros to View BoQ information |
| 149 | M & L for Structural steel, rolled section such as joist, beam, channel, angle, Tee, in available lengths for structural farm of panel complete all as specified and directed Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail