| 1 | Servicing of DG Set 62.5 KVA of any Make, checking entire system as per manufacturer's catalogue such as checking all parts for serviceeablility, taking down defective parts such as fuel filter assy, by pass filter assembly, lub oil filter assembly, air cleaner assy, flexible hose pipe, coolent etc and replacing the same with same size, make and capacity of parts, draining out the old used burnt engine oil from the sump cleaning all serviceable filters and oil sump with cleaning solution such as petrol/ diesel and refilling new engine oil upto required level and including testing to DG Set to entire satisfaction of Engr-in Charge. Note:-(i) Spare parts/ Engine oil/ check kit/ filter shall be measured and paid for saperately under respective items of BOQ (ii) Minimum 6 months gap/ 200 hrs of run whichever is earlier shall be considered for next service (iii) Repair Guarantee for replaced parts/servicing of DG Set shall be for six month/200 hrs from the date of service. |
| 2 | All as per item No 1 here-in-before but for DG set 40/50 KVA. |
| 3 | All as per item No 1 here-in-before but for DG set 30/25 KVA. |
| 4 | All as per item No 1 here-in-before but for DG set 20/15 KVA. |
| 5 | Supply only lubricant oil filter suitable for 62.5 KVA DG set |
| 6 | Supply only lubricant oil filter suitable for 40/50 KVA DG set |
| 7 | Supply only lubricant oil filter suitable for 30/25 KVA DG set |
| 8 | Supply only lubricant oil filter suitable for 20/15 KVA DG set |
| 9 | Supply only fuel filter with set of 'O' Ring for 62.5 KVA DG set. |
| 10 | Supply only fuel filter with set of 'O' Ring for 40/50 KVA DG set. |
| 11 | Supply only fuel filter with set of 'O' Ring for 30/25 KVA DG set. |
| 12 | Supply only fuel filter with set of 'O' Ring for 20/15 KVA DG set. |
| 13 | Supply only air filter inner & outer suitable for 62.5 KVA DG set |
| 14 | Supply only air filter inner & outer suitable for 40/50 KVA DG set |
| 15 | Supply only air filter inner & outer suitable for 30/25 KVA DG set |
| 16 | Supply only air filter inner & outer suitable for 20/15 KVA DG set |
| 17 | Supply only Gasket Set suitable for 62.5 KVA DG set |
| 18 | Supply only Gasket Set suitable for 40/50 KVA DG set |
| 19 | Supply only Gasket Setsuitable for 30/25 KVA DG set |
| 20 | Supply only Gasket Set suitable for 20/15 KVA DG set |
| 21 | M&L fof Calliberation of FIP complete after replacement of defective worn out parts for DG Set 62.5 KVA complete all as specified and directed. |
| 22 | bearing bush |
| 23 | plunger spring |
| 24 | delivery valve and spring |
| 25 | banjo bolt and benjo |
| 26 | sealing ring |
| 27 | oil seal |
| 28 | gasket |
| 29 | overflow valve etc. |
| 30 | All as per item No 21 here-in-before but for DG set 40/50 KVA. |
| 31 | All as per item No 21 here-in-before but for DG set 30/25 KVA. |
| 32 | All as per item No 21 here-in-before but for DG set 20/15 KVA. |
| 33 | Supply and changing engine oil 15W/ 40, complete all as specified and directed. |
| 34 | Supply and fixing hose pipe flexible with 2 Nos clamps of same size/ model/ capacity as per existing complete all as specified and as directed. |
| 35 | Supply and changing coolent complete all as specified and as directed. |
| 36 | Supply and changing distilled water in for filling in batteries complete all as specified and as directed. |
| 37 | S&F in replacement automatic voltage regulator suitable for 15 to 62.5 KVA DG set including connections of AVR with panel with and including PVC insulated multistranded copper wires of suitablesize complete all as specified and as directed. |
| 38 | S&F in replacement maintenance free lead acid battery 12 volts 150 AH complete all as specified and as directed. |
| 39 | S&F in replacement maintenance free lead acid battery 12 volts 90 AH complete all as specified and as directed. |
| 40 | S&F in replacement PVC transparent flexible pipe, superior quality, of 10mm dia approximate length 2 RM, tightening the same with two Nos of jublee clips on both ends,complete all as specified and as directed. |
| 41 | M&L for Servicing of self starter after disconnecting the same from DG sets, transporting to workshop, opening the same and replacing the defective parts/ winding including testing after repair/servicing and refixing in orginal position of capacity 15 KVA to 40 KVA complete all as specified and directed. |
| 42 | All as per item No 33 here-in-before but of capacity 50 KVA to 62.5 KVA |
| 43 | S&F in replacement on load change over switch, 63 Amp capacity, 3 phase, 4 pole, 415 volts, 50Hz, side handle operated, with and including MS sheet metal enclosure having advance neutral complete all as specified and as directed. |
| 44 | All as per item No 35 here-in-before but 100 Amp |
| 45 | All as per item No 35 here-in-before but 200 Amp |
| 46 | M&L for servicing/ cleaning of MS diesel tank of DG set 15 KVA to 62.5 KVA by draining out the diesel from tank, cleaning the tank with soap water/ suitable solution and painting the external surface with one coat of synthetic enamel paint of existing colour including repalcement of drain valve, outlet pipe complete all as specified and as directed. |
| 47 | S&F in replacement, indicator lamp assembly (set of three) red, yellow, blue complete all as specified and as directed. |
| 48 | S&F in replacement, battery leads copper conductor single core of length 2 x 1.5m of suitable size for 12volt/ 24volt DC with brass terminal heavy duty complete all as specified and as directed. |
| 49 | S&F in replacement of asbestos rope 20mm dia of good quality for exhaust manifold exhaust pipe complete all as specified and as directed. |
| 50 | M&L for removing the old paint from surface of DG set and alternator upto 62.5 KVA capacity and cleaning the old surface with sand paper and painting complete DG set and panel board including canpoy with synthetic enamel paint (of colour as directed by Engg-in-charge) using spray gun with compressed air and writing the SM No/ MES No, in block letters, with white paint & size of letters n exc 3 cm high complete all as specified and as directed. |
| 51 | S&F in replacement, voltmeter of size 96 x 96mm complete all as specified and as directed. |
| 52 | S&F in replacement, amp meter of size 96 x 96mm complete all as specified and as directed. |
| 53 | M&L for repair/Replacement of battery charger by replacing the worn out and defective items complete all as specified and directed. |
| 54 | S&F in replacement, battery charger with auto cut off indicater suitable for 24 volts DC complete all as specified and as directed. |
| 55 | M&L for disconnecting and dismantling the alternator unit of 15/25/30/40/62.5 KVA DG Set from the base plate of the DG set and transporting to workshop for repair, dismantling the unit, further separating the armature from the startor carefully, cutting and taking out the burnt windings of the alternator carefully, cleaning the slots and , duly applying the insulation and assembling the stampings inserting in position in the startor including applying slot insulation and rewinding of the alternator startor winding with super enameled copper conductor of same gauge and same number of turns as that of existing one including replacement of carbon brushes tapping the windings and bringing out the coil conections for production of 3 phase 415 volt 50 HZ AC supply and preheating the windings and applying insulating varnish and drying the windings in oven and assembling the unit and transporting back to installation and fixing on base plate and coupling with the DG set and testing complete all as specified and directed. |
| 56 | M&L for dismentling/ taking down complete radiator assembly of DG set 62.5 KVA and transporation to market for repair by :-(i) Opening the radiator assembly with brazing/ welding for repair/ services.(ii) Cleaning of all water tube with diluted solution of HCL & cleaning with water preasure & removing the sludge and dust from inside the tank by flushing out.(iii) Repair of fins by soldring/ brazing. (iv) Repair of bottom brass water tank by soldring/ brazing. (v) Repair of radiator hose assembly.(vi) Fixing the complete radiator assembly to its orignal position and testing complete |
| 57 | All as per item No 48 here-in-before but DG set 40/50 KVA. |
| 58 | All as per item No 48 here-in-before but DG set 15/25/30 KVA. |
| 59 | S&F in replacement, water temp gauge circular dial complete all as specified and as directed. |
| 60 | S&F in replacement, fan belt suitable for 62.5 KVA DG set complete all as specified and as directed. |
| 61 | All as per item No 52 here-in-before but suitable for 40/50 KVA DG set complete all as specified and as directed. |
| 62 | All as per item No 52 here-in-before but suitable for 30/25 .5KVA DG set complete all as specified and as directed. |
| 63 | M&L for disconnection of electric connection from DG set control penal, dressing of cable including replacement of burnt out aluminium/copper lugs and fixing with new lugs, nuts bolt complete all as specified and as directed. |
| 64 | S&F in replacement, MCCB, three pole, 250 Amp 415 volts, 50 Hz breaking capacity not less than 35 kA with adjustable thermal and adjustable magnetic protection release with spreader links, Ics = 100% Icu complete all as specified and as directed. |
| 65 | All as per item No 56 here-in-before but four pole, 160 Amp breaking capacity not less than 25 kA complete all as specified and directed. |
| 66 | All as per item No 56 here-in-before but four pole, 125 Amp breaking capacity not less than 25 kA complete all as specified and directed. |
| 67 | Supply and Fixing in replacement of Self Starter of Capacity 24 Volt suitable for Kirloskar /Cummins Dg set complete all as specified and directed. |
| 68 | Supply and Fixing in replacement of Self Starter of Capacity 12 Volt suitable for Kirloskar /Cummins Dg set all as specified and directed. |
| 69 | M&L in repairs to AMF Panel/Control panel of DG Set by replacing following parts and commissioning and testing the panel complete all as specified and directed by Engineer-in-Charge |
| 70 | Relay 12 volt 8 Pin |
| 71 | Relay 24 Volt 8 Pin |
| 72 | On Relay Eloctronic Timer |
| 73 | Line voltage Monitoring Relay 3 Phase 415 Volt |
| 74 | Start/ Stop relay 12 Volt |
| 75 | Start / Stop Relay 24 volt |
| 76 | Energy Starting Relay 12 Volt |
| 77 | Repair/Replacement of start/Stop Switch |
| 78 | Replacement of Engine Control Unit |
| 79 | Replacement of solenoid switch |
| 80 | Repair/Replacement of worn out/defective part of Dynamo kit |
| 81 | Dismentaling &Taking down unserviceable street light fittings LED Fittings/ CFL Fittings,post top lantern,garden light, Pin /Holder type from pole or from Bldgs for repairs including replacement of unserviceable Lamp, holder, integral wiring with appropriate gauge copper conductor and refixing the same after repairs in original position properly using PVC insulation tape or where directed complete including replacement of any spares,cable connections from OH conductors,or from junction boxes to light fitting all as specified and as directed.Note : Spares items such as LED driver and cable etc, will be measured and paid separately under respective items. |
| 82 | S&F LED street light fitting of capacity 60 Watt (Efficacy :120LM/W) made up of pressure die cast aluminium housing with toughened glass cover and high power LED's and secondary lenses with IP66 protection with 10 KV inbuilt surge protector including taking down existing old unserviceable light fittings from the bracket of pole or any other place not more than 8.00 metres height from ground level complete all as specified and directed. |
| 83 | S&F Integral LED street light fitting of capacity 90 Watt (Efficacy :120LM/W) made up of pressure die cast aluminium housing with toughened glass cover and high power LED's and secondary lenses with IP66 protection with 10 KV inbuilt surge protector including taking down existing old unserviceable light fittings from the bracket of pole or any other place not more than 8.00 metres height from ground level complete all as specified and directed. |
| 84 | Supply and fix Integral LED security FLOOD light luminaire 120W LED 230 volts made of pressure die cast aluminium housing with high power LED’s lens & toughned glass IP-66 including GI pipe 50mm ,medium grade ,1.7mtr long mounting bracket and providing fixing clamps ,bolts,nuts of suitable sizecomplete all as specified and as directed. |
| 85 | Supply and fix Integral LED security FLOOD light luminaire 150W LED 230 volts made of pressure die cast aluminium housing with high power LED’s lens & toughned glass IP-66 including GI pipe 50mm ,medium grade ,1.7mtr long mounting bracket and providing fixing clamps ,bolts,nuts of suitable sizecomplete all as specified and as directed. |
| 86 | S&F New generation, IP 65 LED post-top family, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source. Clear Cover offers bright illumination for different applications complete all as specified and directed. |
| 87 | Supply and fixing in replacement path light LED bollard 7W to 10W in cylindrical shape with opal acrylic diffuser and IP 65 & IK-10 protection with silent observer and giving light, diffuser at the upper portion acts a beacon of path guidance in a landscape enironment fixed on PCC block of size 450x450x600 mm with PCC 1:4:8 type D2 40mm graded complete all as specified and directed. |
| 88 | S&F Thermoplastic Cable Junction Boxes IP66/67 \\"weather proof\\" , for outdoor installation with knockouts for cable entry for streetlight with terminals suitable for 10-16 sqmm cable of Size 155 X 210 X 92 mm incl aluninium busbar and MCB SP 6 amps 1 No, for street light, including necessary clamps for fixing with street light pole, and connecting all incoming and outgoing cables with AL lugs of appropiate sizes complete all as specified and directed. |
| 89 | Supply and laying of LT cable in trenches or on poles / walls, XLPE Insulated screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm, 2 core, ISI marked complete all as specified and directed. |
| 90 | Supply & Fixing in replacement of the following spare parts in street lights complete all as specified and directed. :- |
| 91 | LED Driver 60 Watt |
| 92 | LED Driver 90 Watt |
| 93 | Excavation in trenches not exceeding 1.5 metres wide and not exceeding1.5 metres in depth and getting out in any type of soil complete all as specified and directed. |
| 94 | Excavation in trenches n.exc 1.5 metre wide and exc. 1.5m in depth but n.exc 3.0 metre in depths for foundations and getting out in soft/ loose soil complete all as specified and as directed. |
| 95 | Returning, filling in, including spreading , leveling , watering and well ramming in layer not exceeding 25cm each layer complete all as specified and directed. |
| 96 | Removing excavated material not exceeding 50M and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed. |
| 97 | M&L for sand filling in trenches for cable protection provided with layer 8cm deep before laying of cable and 15 cm after laying including spreading and leveling watering and well ramming in layer not exceeding 25mm thick complete all as specified and directed. |
| 98 | Supply and laying in trenches Sub class ‘B’bricks well burnt locally available for covering to cable laid dry flat ,with width of brick perpendicular to the length of cable complete all as specified and as directed. |
| 99 | Material and labour for PCC 1:3:6 Type C-2 (Using 40 mm grade aggregate as in foundation of pole, stay and filling and mass concrete) including providing necessary form work complete all as specified and as directed |
| 100 | Material and labour for PCC 1:2:4 type B1 using 20 mm grade stone aggregate as in copping of electric pole at site including providing necessary form work complete all as specified and as directed. |
| 101 | M&L for of PVC insulated weather proof flat twin core Aluminium cable of size 2.5 Sqmm single core including with PVC conduit of all necessary suitable iron clamp(3 nos), nut and bolts of appropriate size from junction box to street light complete all as specified and directed.. |
| 102 | Supply and fix XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor rating 1100 volts cross sectional area 25 Sq mm 3.5 core laid in trenches or passing through pipes/ducts or fixed to walls/poles incld taking out old unserviceable under ground cable from excavated trenches /pipes (Earth work, segragating cable cover measured separately) complete all as specified and directed. |
| 103 | Supply and fix XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor rating 1100 volts cross sectional area 35 Sq mm 3.5 core laid in trenches or passing through pipes/ducts or fixed to walls/poles incld taking out old unserviceable under ground cable from excavated trenches /pipes (Earth work, segragating cable cover measured separately).complete all as specified. |
| 104 | Supply and fix Pole mounted bracket made out of GI pipe 40 mm dia medium grade of length 1.5 mtr with two clamps made out of 40x6 mm with suitable nuts, bolts and washers incld taking down old unserviceable GI bracket from pole complete all as specified and directed |
| 105 | M&L for GI tubing light grade with all necessary fittings laid in trenches under road crossing fixed on poles, walls under floor for cable protection complete all as specified and directed for 40mm dia complete all as specified and directed. Please Enable Macros to View BoQ information |
| 106 | M&L for GI tubing light grade with all necessary fittings laid in trenches under road crossing fixed on poles, walls under floor for cable protection complete all as specified and directed for 40mm dia complete all as specified and directed. Please Enable Macros to View BoQ information |