| 1 | Percentage BoQ BoQ_Ver3.0 Percentage Normal INR Only INR Select, At Par, Excess (+), Less (-) IOCL Tender Inviting Authority :- EXECUTIVE ENGINEER ELECTRICAL DIVISION PWD B&R JALANDHAR Name of Work : Supply, Installation, Testing and Commissioning of 82.5KVA DG set in Agriculture Co-Op. Staff Training Institute, Jalandhar. Contract No: ELECTRICAL WORKS Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Work Name Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Supply , Erection, Testing and Commissioning of Silent (Sound Proof) Diesel Generator Set 82.5 KVA /66KW with Manual Control Panel. It should be air cooled/water cooled naturally aspirated/ turbo charged/ turbo charged after cool (As per manufacturer standard). ENGINE: The Diesel engine developing 101.3 BHP (min.) for giving a power rating as per ISO 8528-Part-1 (With CPCB-IV Norms as amended upto date) in KVA at the load terminals of alternator at 1500 rpm at actual site conditions. The engine shall confirm to IS 10000/ISO 3046/BS: 649/ BS 5514 amended up to date have dynamically balanced Fly wheel, air cleaner (dry/ oil bath type) as per manufacturer standard. A mechanical/ electronic governor of TYPE A1 AND A2 to maintain engine speed at all conditions of load, daily fuel service tank of minimum 8 hours running capacity as per manufacturer standard, Dry exhaust manifold with suitable exhaust residential grade silencer to reduce the noise level suitable self-starter for 12 V/24 V DC, battery charging alternator unit and voltage regulator, Lubrication oil cooler, Lubrication oil filters with replaceable elements. |
| 3 | ENGINE CONTROL PANEL: Engine control panel fitted and having digital display i.e Start/stop key switch/push button, Battery charging indication, Engine Hours indications, Over speed indication, High water temperature indication. Lubricant oil pressure indication,) RPM indication and MCCB (Fixed Thermal and Adjustable Thermal protection) of suitable rating for outgoing supply. ALTERNATOR: The alternator should be designed as per (IS4722 and IEC:34) standard. Rated Power Factor: 0.8 (lag), Rated voltage: 230/415 volt, SPDP (Screen Protected Drip Proof), Degree of protection: IP-23, Ventilation: Self ventilated air cooled Altemator should have 40 degree maximum class H insulation, Automatic voltage regulator unit should be provided as per standard practice of manufacturer. Its voltage dip shall not exceed more than 20% of the rated voltage at any step load or transient load as per ISO 8528 (Part-1). Its efficiency at full load 0.8 power factor, 10% overload one hour in every 12 hrs of continuous use. |
| 4 | ACOUSTIC ENCLOSURE: The enclosure shall be fabricated out the CRCA sheet of thickness not less than 1.6 mm on the outside cover with inside cover having not less than 0.6 mm thick perforated powder coated CRCA sheet. It should be IP54 Suitable for outdoor installation exposed to weather conditions, noise level up to 75 dB (A). All sheet metal parts should be processed through 7-tank pre treatment process and batteries accommodated in the battery rack. The acoustic lining should be made up of high quality insulation material i.e. Rockwool/glass/mineral wool/ PU foam of appropriate thickness & density for sound absorption. The inside of enclosure should be provided with at least one no. 28 W-T5 fluorescent tube light/ LED 10Watt luminaries controlled by a 5A switch for adequate lighting during servicing etc. with 2 year warranty from the date of installation. Complete in all respect as desired by engineer at site:-The Generator set should be installed at site on the suitable size existing plinth of RCC as per specifacation DG set as per satisfaction of the Engineer-in-Charge at site. The model of engine will be decided by the Engineer in Charge. |
| 5 | MANUAL CONTROL PANEL: Manual control panel shall be fabricated out of 1.6 mm sheet steel, totally enclosed, dust, damp and vermin proof wall mounted/ free standing floor mounted type with IP-53 degree of protection & front operated, composite meter for digital display, HRC fuses of suitable rating. MCCB (Fixed Thermal and Adjustable Thermal protection)/ ACB (Over cuurent/ overload, shortcircuit, instantenous, earth fault protection) should be used. Battery charger complete with voltage regulator, Voltmeter and Ammeter for charging the battery from external mains. This will be in addition to the battery charging alternator or dynamo fitted on the engine.All the components in the control panel shall be properly mounted, duly wired and labeled. Suitable terminals are to be provided for panel incoming and outgoing connections. System opeartion facility provided shall afford the following operational requirements. Necessary instruments and accessories such as voltmeter, power factor meter, KW meter, KWH METER, Ammeter, Frequency meter, battery charger complete in all respect as desired at site:-FOUNDATION: Foundation of required size Complete in all respect as desired by the engineer incharge at site. |
| 6 | XLPE INSULATED UN-ARMOURED CABLES (LOOSE): |
| 7 | Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:- |
| 8 | Overall size 95sq.mm (3½ Core) Un-armoured (Loose) |
| 9 | Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 10 | Double Walled Corrugated HDPE Pipe 63/ 51mm (Outer/ Inner dia.) |
| 11 | COPPER EARTHING (Upto 14 metre in Length): |
| 12 | Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 13 | Earthing with 20mm x 3mm Copper Tape (upto 8Metre in Length) |
| 14 | COPPER EARTHING STRIP (As Additional Length): |
| 15 | Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:- |
| 16 | Additional Length 20mm x 3mm thick Copper Tape |
| 17 | ON LOAD CHANGEOVER SWITCH (With Sheet Enclosure): |
| 18 | Supply and erection of On Load Change over Switch with advance neutral UNIT in sheet enclosure on the existing surface. (Confirms to IS 13947 (Part-3). complete with G.I. Bolts, Nuts etc. according to the size of holes in the body of the enclosure & Connections on both sides of switch with suitable size of thimbles as per PWD General Specifications:- |
| 19 | On Load Change Over Switch Four Pole 160amp., 415volts (With Sheet Enclosure) Total in Figures 1676173.0 1676173.0 INR Sixteen Lakh Seventy Six Thousand One Hundred & Seventy Three Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 INR Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |