| 1 | SUB-HEAD - I : INTERNAL WIRING |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 3 | Group - C |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 5 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 7 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 8 | 2 X 6 sq. mm + 1 X 4 sq. mm earth wire |
| 9 | 2 x 10 sq.mm + 1 x 6 sq.mm. earth wire |
| 10 | Supply and wiring of submain with 4 number 10 sqmm . FRLSH PVC insulated 1100 V grade multistranded single core copper conductor cable in 32 mm dia heavy duty (2mm thick ) PVC conduit partly concealed in wall and partly laid in slab along with reinforcement befor concreting with two number 6 sq mm FRLSH PVC insulated copper conductorcable as earth contunity wire including colour wash etc. complete in all respects. |
| 11 | Supply and wiring of submain with 4 number 16 sqmm . FRLSH PVC insulated 1100 V grade multistranded single core copper conductor cable in 40 mm dia heavy duty conduit with two number 6 sq mm FRLSH PVC insulated copper conductorcable as earth contunity wire including colour wash etc. complete in all respects. |
| 12 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required |
| 13 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 14 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box forceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5mm thick M.S. sheet with its top surface hacked for proper bonding,top lid shall be screwed into the cast iron/ M.S. sheet box by means of3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 15 | Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 16 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required |
| 17 | Upto 450 mm sweep |
| 18 | Extra for fixing the Louvers/ shutters complete with frame for exhaust fans of all sizes. |
| 19 | Supply of LED 4ft Batten with a nominal system lumen output of 2000 lumens and a minimum system efficacy of 100 lm/W. The luminaire shall have a rated system lifetime of 25,000 burning hours at L70. The luminaire should have a color temperature of 4000K and CRI>80. The luminaire shall meet IP20 rating with THD < 10% and PF > 0.9. The luminaire housing should made of extrusion Al with a PC diffuser. The total power consumption should not exceed 21W (including driver).Including connection with 1.5 sqmm FRLS PVC insulated copper conductor. |
| 20 | Supply of Surface mounting round 6 Watt 10 Watt , LED Down Lighter, suitable for 24Hr Continuous Operation, 660-1100 system lumens, 110lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect. |
| 21 | Supply of Surface mounting round 12 Watt 15 Watt , suitable for 24Hr Continuous Operation, 100lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect |
| 22 | Supply of Surface mounting square 20 Watt , suitable for 24Hr Continuous Operation, 100lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect. |
| 23 | Supplying of LED mirror light luminaire with 10W watt complete with electronic ballast, lamp including connection etc. complete as required, Including connection with 1.5 sqmm FRLS PVC insulated copper conductor. |
| 24 | Supply of LED Flood light 50 Watt , suitable for 24Hr Continuous Operation, 110lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, CCT 3000K, complete in all respect, |
| 25 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 26 | Supplying of 9 Watt Decorative LED Wall Light complete in all respect. |
| 27 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. 1200 mm sweep ceiling fan |
| 28 | Supplying of following size exhaust fan complete with gravity louver and connection with 3 core flexible wire as required. |
| 29 | 300mm EXHAUST FAN |
| 30 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required |
| 31 | 63 A,25KA,FP MCCB |
| 32 | 100 A,30KA,FPMCCB |
| 33 | Supplying and fixing following way ,single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 34 | 12 way, Double Door |
| 35 | Supply and fixing of surface/ flush mounting 6 way V TPN distribution board with additional metal door without MCB complete in all respect, as directed at site by Engineer Incharge. |
| 36 | Supplying and fixing TP/FP sheet steel enclosure on surface/ recess. Suitable for upto 125 A 415 V MCCB complete with connections, testing and commissioning etc. as required. |
| 37 | Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 38 | 40 amps TP MCB |
| 39 | 63 amps TP MCB |
| 40 | 40 amps 4P MCB |
| 41 | 63 amps 4P MCB |
| 42 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 43 | 40 amps |
| 44 | 63 amps |
| 45 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 46 | 40 amps |
| 47 | 63 amps |
| 48 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 49 | Single pole |
| 50 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 51 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 52 | Supplying and fixing DP sheet steel enclosure on surface/ recessalong with 25/32 A 240 V \\"C\\" curve DP MCB complete withconnections, testing and commissioning etc. as required. |
| 53 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. Details of cost for one each |
| 54 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal or coke and salt) as required. |
| 55 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 56 | Laying of one number PVC insulated and PVC sheathed / XLPE power Cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 57 | Above 35 sq.mm. and up to 95 sq.mm. |
| 58 | Above 95 sq.mm. and upto 185 sq.mm. |
| 59 | Above 185 sq.mm. and up to 400 sq.mm. |
| 60 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, rotective covering and refilling the trench etc as required |
| 61 | Above 35 sq.mm. and up to 95 sq.mm. |
| 62 | Above 95 sq.mm. and upto 185 sq.mm. |
| 63 | Above 185 sq.mm. and up to 400 sq.mm. |
| 64 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 65 | Above 35 sq.mm. and up to 95 sq.mm. |
| 66 | Above 95 sq.mm. and upto 185 sq.mm. |
| 67 | Above 185 sq.mm. and up to 400 sq.mm. |
| 68 | Supplying and making cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required. |
| 69 | 4 X 16 sq. mm (28mm) |
| 70 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. |
| 71 | 100mm dia |
| 72 | 150 mm dia |
| 73 | H. T. SYSTEM |
| 74 | Support for 11 KV overheaa line as per technical specification, approvea drawings and scot of work |
| 75 | STP-11M IS 410 SP-55 |
| 76 | Pre-fabricated Hot dip Galvanised steel items liLe V cross arm, top clamp, DC cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, triuisi\\"ormer mounting structure etc made of MS Channels (l00x50x6mm), MS angle (65x65x6mm), MS dats (65x8mm) of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 77 | 11 KV Line Pole Top Bracket (5 No.) - 3.625 Kg. each |
| 78 | 11 KV Line V Cross Arm (8 No.) - 15.94 kg. each |
| 79 | M.S. Channel (X-arm) 100x50x6mm-2200 mm for H-Pole (2 No.) - 17.38 Kg. each |
| 80 | M.S. Angle Iron 50x50x6mm-2400 mm for earthing (1 No.) - 10.8 Kg. each |
| 81 | M.S. Channel 100x50x6mm-1600 mm for earthing (8 No.) - 12.64 Kg. each |
| 82 | M.S. Angle 50x50x6mm-2860 mm for Bracing H-Pole (2 No.) - 12.87 Kg. each |
| 83 | M.S. Angle 50x50x6mm-1400 mm for belting (2 No.) - 6.3 Kg. each |
| 84 | Half Clamp (24 No.) - 1.47 Kg. |
| 85 | Full Clamp (10 No.) - 2.325 Kg. |
| 86 | MS Nuts, Bolts with Washers as per technical specification, approved drawings and scope of work. |
| 87 | GI Nuts, Bolts & Washer off all required sizes - 10 Kg |
| 88 | Hot dip Galvanised Eye Screw Bolt 9\\"x5/8\\" (19 No.) - 0.483 Kg. |
| 89 | Stay Set (Galvanised) with 50x8 mm stay clamp, stay insulator (2 Nos.), anchor plate (200x200x6), nut bolts, 2 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete as per technical specification, approved drawings and scope of work. |
| 90 | Insulator and hardware as per technical specification, approved drawings and scope of work. |
| 91 | 11 KV polymeric Disc insulator 45 KN along with suitable hardware fittings |
| 92 | 11 KV Polymeric Pin Insulators with GI PIN |
| 93 | Earthing arrangement as per technical specificatons, approved drawings and scope of work. |
| 94 | Spike Earthing 20mm solid Rod |
| 95 | Providing and fixing 6 SWG dia G.I. wire on surface or in recessfor loop earthing as required. |
| 96 | PG Clamps for 30/50/80/100 mm2 |
| 97 | Barbed Wire |
| 98 | Danger Plate (Enamelled with Clamp) |
| 99 | Phase Indication Plates for each phase set of 3 (On H•Pole & d Pole) |
| 100 | ACSR conauctor, Dog type (100 sq mm) |
| 101 | Transformers |
| 102 | Supply, Installation, testing and commissioning of 250 KVA. 11/0.433 KV, 3 Phase, 50Hz, Dyn 11, Oil type, ( UPPCL approved make) copper wound transformer with Off load tap changing arrangement on HV side in steps of +/- 2.50%, +/- 5% , having cable end boxes on HV side and 500 Amp. bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 2026 (Part 1 to Part 5) & as per specification attached complete in all respects as required at site. |
| 103 | EXTERNAL LIGHT FEEEDER PILLAR |
| 104 | SITC of compartmentalised design, dust tight & vermin proof made out of 14 gauge M.S. sheet, stove powder coated L.T panel complete as required with following incomming & outgoing as per detail below. |
| 105 | INCOMER |
| 106 | 1 Nos. 400 AMP FP MCCB |
| 107 | BUSBARS |
| 108 | 1 Nos. 500 Amp TPN busbars of aluminium alloy as per SLD. |
| 109 | OUTGOING |
| 110 | 100 Amp.MCCB-3Nos. & 63 Amp.MCCB-2Nos. |
| 111 | INSTRUMENTS |
| 112 | 1 Nos. 0 to 500 Volt digital voltmeter with Voltmeter Selector Switch & Protective |
| 113 | 1 Sets breaker 'ON' & 'OFF' indicating lamp |
| 114 | 1 Sets auto trip indicating lamp . |
| 115 | Supply & Stringing of LT AB Cable of 3x120+1x95+1x50sqmm |
| 116 | Supply & Laying of 4C X 25sqmm Al. Unarm. Cable |
| 117 | Supply & Installation of 3Phase Distribution Box |
| 118 | Supply & Installation of C- Type / Holding Clamp |
| 119 | Supply & Installtion of Eye hook Clamp |
| 120 | Supply & Installation of Nut & Bolts with washer |
| 121 | Supply & Installation of Suspension Clamp |
| 122 | Supply & Installation of Dead end Clamp |
| 123 | Supply & Installation of Piercing Connector 120Sqmm |
| 124 | Supply & Installation of Piercing Connector 95Sqmm |
| 125 | Supply & Installation of PG Clamp for ACSR Conductor |
| 126 | Supply and fixing danger board fabricated from 10 gauge M.S. Sheet as per I.E. Rules. |
| 127 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm diaincluding accessories, and providing masonry enclosure withcover plate having locking arrangement and watering pipe etc.with charcoal/ coke and salt as required. |
| 128 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 129 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metrebelow ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nutbolt & spring washer spaced at 50mm) |
| 130 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I.pipe from earth electrode including connection with G.I. nut,bolt, spring, washer excavation and re-filling etc. as required. |
| 131 | Providing and fixing 6 SWG dia G.I. wire on surface or in recessfor loop earthing as required. |
| 132 | Providing, laying and fixing following dia RCC pipe NP2 class(light duty) in ground complete with RCC collars, jointing withcement mortar 1:2 (1 cement : 2 fine sand) including trenching(75 cm deep) and refilling etc as required. |
| 133 | Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 110 to 130 Watt. Confirming to IP 66 Protection complete in all respect. CAT- AAA Pwd 2024 23.17 |
| 134 | Supply & Installation of Single Arm Bracket for fitting of Street Light |
| 135 | 11 KV 8 Panel board 24 V DC operated with 1 no I/C panel |
| 136 | 11 KV 8 Panel Board 24 V DC operated with 1 No O/G Panel |
| 137 | 11 KV 3 Core XLPE Cable 300 mm2 for O/G Feeders |
| 138 | Supply and Fixing of extinguisher , ABC Type 6.00 Kg capacity ( ISI Marked IS 15683 & TAC |
| 139 | Supply Fixing of CO2 Type fire extinguisher 6.5 Kg Capacity ( ISI Marked IS 2878 & TAC |
| 140 | Less 5% as Departmental Chargew Please Enable Macros to View BoQ information |