| 1 | Sub Estimate No.01 Providing 22 KV HT power supply incomer from Anandnagar 220 KV S/S to proposed switching station. |
| 2 | Item No.01 HT Cables (CB-HT) 1.1 Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (strip) cable 22 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT |
| 3 | Item No.02 Cable Enclosures (CB-CE) 2.1 Supplying & laying (including excavation) half round reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 4 | 2.2 Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 5 | Item No.03 Cable Joints & End Termination Kits (HT Cables) (CB-JT/HT) 3.1 Providing and erecting Heat shrinkable outdoor termination kit for 11 kV (UE)/ 22 kV ( E ) XLPE HT cable 3x240 to 400 sq. mm. with necessary material as per specification no. CB-JT/HT |
| 6 | 3.2 Providing and erecting Heat shrinkable straight through joint kit for 11 kV (UE)/22 kV ( E ) XLPE HT cable 3x240 to 300 sq. mm. with necessary material as per specification no. CB-JT/HT |
| 7 | Item No.04 Providing, Laying and Jointing of 315mm dia. (OD) HDPE pipe (PN 6 Class-PE 80 grade: IS 14333) to correct grade and alignment from 3m up to 5m depth including boring, Pilot inclined Dilling from existing ground level up to required depth (invert level) on rig side of proposed gravity sewer line (i.e. entry side) and Final inclined boring from existing ground level up to required depth (invert level) or vice versa on pipe side (i.e. exit side) of proposed gravity sewer line using Horizontal Directional Drilling method in any type of ground including soft soil, mixed ground and soft/hard rock. Length of gravity sewer line between inner faces of two consecutive proposed manholes will be considered for measurement. |
| 8 | Item No.05 Supplying and erecting 22 kV outdoor type gang operated air break, triple pole switch 400 A capacity with 3 post pin type insulator per phase, mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of \\"C\\" class G.I. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp. |
| 9 | Item No.06 C.C. Foundation 6.1 Making Transformer plinth (1.5 x 1.5 x 1.5)m in size with necessary excavation in ground with 150mm thick M-10 PCC at the bottom and top and 250mm thick, burnt brick wall constructed at periphery and remaining hollow portion shall be filled with 40mm hard broken aggregate. External surface duly plastered by 12mm thick including watering etc. complete. |
| 10 | Sub Estimate No.02:-Providing 22/22 KV indoor switching station having 2 incomers and 2 outgoing feeders at Jambhivali. Item No.01 Supply, installing, testing & commissioning of 22/22 KV switching station (2 I/C + 2 O/G) including all equipments /switchgears, control room, Cabling etc. complete as per MSEDCL specifications. |
| 11 | Item No.02 Providing Substation Monitoring System as per MSEDCL specifications at proposed 22/22KV switching station at Jambhivali Phase-IV in Addl. Amernath Indl. Area. |
| 12 | Sub Estimate No.03 Providing 22KV O/H Distribution Network at Jambhivali. Item no.01 Steel Poles (OH-PL) 1.1 Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ |
| 13 | 1.2 Supplying and erecting rolled steel joist (girder) pole 152 x 152 mm (37.1 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ |
| 14 | Item No.02 Accessories 2.1 Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6mm., straining screws, G.l. stay wire 7/10 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete. |
| 15 | Item no.03 C.C. Foundation 3.1 Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles) |
| 16 | Item No.04 Providing ,erecting heavy duty GI steel structure for 22 KV feeder/Transformer DP including fabrication of channel,angle ,strip ,Nut bolts ,wire of different sizes etc complete. |
| 17 | Item no.05 Insulators (OH-INS) 5.1 Supplying and erecting porcelain disc type insulator 70KN with necessary hardware suitable for 22kV line, complete as per specification no. OH-INS/DI |
| 18 | 5.2 Supplying and erecting porcelain pin type insulator with GI pin suitable for 22kV line , complete as per specification no. OH-INS/PN |
| 19 | Item no.06 Conductors (OH-CON) 6.1 Supplying and erecting ACSR conductor of size - 6/1-4.72 mm (Dog) complete. (394.00 kg/km) as per specification No. OH-CON/ACSR |
| 20 | Item no.07 Providing & fixing Danger boards |
| 21 | Item no.08 Plate, Pipe type Earthing (EA-EP) 8.1 Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 22 | Item no.09 Accessories 9.1 Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specification no EA-EP. |
| 23 | Item no.10 Accessories 10.1 Supplying and erecting anti climbing devices, fabricated from pole clamps of MS flat 40x5 mm, with drooping spikes 15 cm. in length, welded to it and erected on pole complete. |
| 24 | Sub Estimate no.04 Providing 22/0.433 KV,630 KVA Distribution Transformer Centers along with LT feeder pillars and cables at Jambhivali. Item no.01 Steel Poles (OH-PL) 1.1 Supplying and erecting rolled steel joist (girder) pole 152 x 152 mm (37.1 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ |
| 25 | 1.2 Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ |
| 26 | Item no.02 Accessories 2.1 Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6mm., straining screws, G.l. stay wire 7/10 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete. |
| 27 | 2.2 Supplying and fixing MS base plate 30x30x0.6cm size fixed to the pole base either by welding 12mm dia fixed at position. |
| 28 | Item No.03 C.C. Foundation 3.1 Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles) |
| 29 | Item no.04 Providing ,erecting heavy duty GI steel structure for 22 KV feeder/Transformer DP including fabrication of channel, angle ,strip ,Nut bolts ,wire of different sizes etc complete. |
| 30 | Item No.05 Accessories 5.1 Supplying and erecting 22 kV outdoor type gang operated air break, triple pole switch 200 A capacity with 3 post pin type insulator per phase, mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of \\"C\\" class G.I. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp. |
| 31 | 5.2 Supplying and erecting, 22 kV outdoor type drop out fuse with insulator complete with fuse holders, fuse barrel with metal fitting, fuse element mounted on M.S. channel with working current of 15A capacity complete erected on provided cross arm. |
| 32 | 5.3 Supplying and erecting extra thick alkathene pipe 10 mm dia. erected to enclose bare conductor wires complete.. (use shall be restricted to H.T.) |
| 33 | 5.4 Supplying and erecting anti climbing devices, fabricated from pole clamps of MS flat 40x5 mm, with drooping spikes 15 cm. in length, welded to it and erected on pole complete. |
| 34 | 5.5 Supplying and erecting fencing of section having size at least 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete with provided earthing as per specification no. SS-AS/FSG |
| 35 | 5.6 Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2.45m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminium paint complete. |
| 36 | 5.7 Supplying and erecting double leaf hinged door each 1500 mm in width x 2450 mm in height using B class GI pipe, hinges and angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation and painted complete as per specification no SS-AS/DLD |
| 37 | Item No.06 Insulators (OH-INS) 6.1 Supplying and erecting porcelain disc type insulator 70KN with necessary hardware suitable for 22kV line, complete as per specification no. OH-INS/DI |
| 38 | 6.2 Supplying and erecting porcelain pin type insulator with GI pin suitable for 22kV line , complete as per specification no. OH-INS/PN |
| 39 | 6.3 Supplying and erecting distribution class, 22 kV thyrite type lightening arrester with nut bolts, on provided MS channel as per specification no. OH-INS/LA |
| 40 | Item no.07 Supplying & erecting tension/strain hardware of ACSR conductor etc. complete. |
| 41 | Item no.08 LT Cables (Aluminum) (CB-LT/AL) 8.1 Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 42 | Item no.09 Cable Enclosures (CB-CE) 9.1 Supplying and laying (including excavation of suitable width & depth up to 90 cm) 160 mm outside dia, double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. |
| 43 | Item no.10 Hermetically Sealed transformer (SS-TR-HSL) 10.1 Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 630 kVA, Mineral oil immersed and naturally cooled outdoor type, Copper wound, without gas cushioning, hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45? by thermometer in oil and 50? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%,having 7 number of tap positions with standard accessories complete with test certificate with losses below 1953 Watts at 50% load, 5565 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TR-HSL. |
| 44 | Item no.11 Masonry Work 11.1 Supplying and spreading stone metal 25mm size for 100mm depth above the ground level complete. |
| 45 | Item no.12 Providing & fixing DTC metering with box , single core LT XLPE CABLE ( 300 SQMM .,320 mtr length ) and other allied material for 630 KVA transformer for complete commissioning etc. complete |
| 46 | Item no.13 L.T.Distribution / Feeder Pillar 8 way, 400 Amps. suitable for 3 phase, 4 wire, 50 HZ, 440 Volts, AC system with Electrolytic grade Aluminum Bus Bar as per enclosed detail Technical specification & Drawing enclosed with M.S. Angle Iron Frame for pedestal only and not for main body, with fuse holders of Electric grade copper Contacts. Silver plated, 315/400 Amps for 1 (one) incoming circuits with solid links and 250 Amps for rest of 8 Nos. of outgoing circuits as per our Drawing enclosed. without fuses. Fuse holder duly tested at CPRI. |
| 47 | Item no.14 L.T.Distribution / Feeder Pillar 4 way, 400 Amps. suitable for 3 phase, 4 wire, 50 HZ, 440 Volts, AC system with Electrolytic grade Aluminum Bus Bar as per enclosed detail Technical specification & Drawing enclosed with M.S. Angle Iron Frame for pedestal only and not for main body, with fuse holders of Electric grade copper Contacts. Silver plated, 315/400 Amps for 1 (one) incoming circuits with solid links and 250 Amps for rest of 4 Nos. of outgoing circuits as per our Drawing enclosed. without fuses. Fuse holder duly tested at CPRI.\\" |
| 48 | Item no.15 Plate, Pipe type Earthing (EA-EP) 15.1 Supplying, installing and testing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.I. cover complete with all accessories of G.I. materials & recording the results as per specification no. EA-EP |
| 49 | 15.2 Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 50 | Item no.16 Accessories 16.1 Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specification no EA-EP. |
| 51 | Item no.17 Providing & fixing Danger boards |
| 52 | Item no.18 Providing Round bottom fire bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook complete. |
| 53 | Item no.19 Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver paint complete. |
| 54 | Sub Estimate No.05 Providing street light poles along the Roads at proposed layout in Jambhivali Phase IV of Additional Ambernath Indl Area. Item no.01 Hot Dipped Galvanized Poles & High-Mast (OH-HM) 1.1 Providing & erecting 7 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL |
| 55 | 1.2 Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/BKT |
| 56 | Item no.02 C.C. Foundation 2.1 Making M-20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 6m to 8m high octagonal/conical GI pole). |
| 57 | Item no.03 Outdoor Fittings (FG-ODF) 3.1 Supplying and erecting integrated LED street light fitting 85-90W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 9300 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs at L70B50 including driver complete with minimum 2 Years warranty as per specification No. FG-ODF/SL. |
| 58 | Item No.04 Bunch of Wires (WG-MA/BW) 4.1 Supplying and erecting PVC insulated PVC round sheathed FR 2.5 sq.mm (50 no. x 0.25mm dia.) 3 core flexible multi stranded copper industrial cable for voltage grade up to 1.1 kV |
| 59 | Item No.05 LT Cables (Aluminum) (CB-LT/AL) 5.1 Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 10 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 60 | 5.2 Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 16 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 61 | 5.3 Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 25 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 62 | Item No.06 Cable Enclosures (CB-CE) 6.1 Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 63 | 6.2 Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. |
| 64 | Item No.07 Mini Feeder Pillar (SW-MFP)/ Street Light Control Panel (SW-STCP) 7.1 Supplying & erecting three phase, 415V, street light control panel upto the max load of 12kW, TPN MCB 63A, powder coated CRCA 14 SWG sheet, outdoor type, having IP54, IK10 protection suitable rating contactor, 24 hrs. astronomical time switch with minimum 5 years battery back up, auto/manual selector switch, ON/OFF push buttons, indicator lamps, control wiring, metering device, etc. for automatic operation with overcurrent, short circuit, earth fault protection on provided iron frame / CC foundation as per specification SW-STCP. |
| 65 | Item No.08 LT - MCBs/ MCB Change Over Switch (SW-MCB) 8.1 Supplying, erecting & marking SPMCB 0.5A to 5A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 66 | Item No.09 Plate, Pipe type Earthing (EA-EP) 9.1 Supplying, installing and testing earthing with galvanised iron earth plate size 60 x 60 x 0.6 cm complete with all accessories of GI materials & recording the results as per specification No. EA-EP |
| 67 | 9.2 Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 68 | Item No.10 Accessories 10.1 Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specification no EA-EP. Please Enable Macros to View BoQ information |