| 1 | BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER, UDHAMPUR Name of Work: SPECIAL REPAIR/ REPLACEMENT OF THE 11 KV POWER DISTRIBUTION NETWORK AT CP COLONY AND NEARBY AREAS UNDER GE (UTILITIES) UDHAMPUR Contract No: CWE/U(U)-102/2025-26 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Taking out unserviceable PCC poles HT and LT any type and size complete all as specified and directed. |
| 3 | Taking out unserviceable Steel poles HT and LT any type and size complete all as specified and directed. |
| 4 | Taking out unserviceable stay assembly complete any type and size complete all as specified and directed. |
| 5 | Taking out unserviceable insulator any type and size complete all as specified and directed. |
| 6 | Taking out unserviceable Cross arms any type and size complete all as specified and directed. |
| 7 | Taking out unserviceable ACSR conductor HT and LT any type and size all as directed. Note : (i) Unsv materials retrieved from site should be deposited in MES store by the contractor.(ii) Cost of transportation of unserviceable materials from the site to MES store deemed to be included in the quoted rates. |
| 8 | Excavating in trenches, n exc 1.5 m wide and n.exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, and for laying of cable or pipes etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soil, complete all as specified and as directed |
| 9 | Returning, filling in, including spreading, leveling, watering and well ramming in layer not exceeding 25cm thick each complete all as specified and directed. |
| 10 | Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed. |
| 11 | M & L for providing earthing with GI earth plate electrode 600 X 600 X 6mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to GI strip 32 x 6mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR 1996 part 1 ,including necessary excavation and earth work in any strata of soil,comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh , PCC pit with CI cover and frame etc all as specified and directed by Engineer-in-charge. Note:- All the joints shall be made with welding to get proper conductivity. Note:- The Contractor shall fix the Earth Pit Chamber Board of3.15 mm thick mild steel sheet of size min 45 cm X 30 cm fixed with 12 mm thick MS rod two nos up to 90 cm Height by nut/bolts including spray painting with two coats of synthetic Enamel Black Paint complete MS Sheet both side including writing letters min 6 cm height i.e. Earth Pit No. , Location, Earthing test value and date and other letters complete all as specified and directed by Engineer-in-Charge. |
| 12 | Supply and fix cable jointing kit for 11 KV grade cable for Outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed. |
| 13 | Supply, installation, testing & commissioning of 3 Way Outdoor (IP54) 11kV 630Amps 21KA/3 sec. One side Extensible Ring Main Unit Compact switchgear consisting of 3 Nos. Fixed motorized Vacuum Circuit Breaker Module suitable mechanical and electrical interlocking for Two Incoming and One Outgoing Feeder and Copper Busbar in SF6 insulated stainless steel enclosure (2.5mm thick, SS304 grade). The complete RMU must be type tested for Internal arc 21KA for 1 sec with AFLR Classification for Gas tank & Cable Chamber. The Vaccum Interrupter must RMU manufacturer's own make. The complete RMU shall be consisting of followings:-Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along with series trip coil (Modbus RS485 complaint) for each VCB Module.-Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder.-SF6 Gas pressure indicator on the gas tank.-Operating sequence of VCB must be O- 3 mins-CO-3 Mins-CO and suitable for 2000 mechanical operation.-CT shall be minimum 100-50/1A ,2.5VA , 5P20 - 3 Nos. for protection.-CT shall be minimum 100-50/1A ,2.5VA , Class 0.5 - 3 Nos. for Ammeter.-Manometer for each Tank.-Right angle boot to be provided in each module and Foundation suitable for housing / fixing of RMU is included in rate quoted by contractor-2X12V, 26AH Battary with Charger - 1 Set.-Auxiliary VT shall be 11KV/230 ,500VA for AC supply input to Battary Charger. |
| 14 | -The Contractor shall provide and fix identification boards on each way of the RMU (Ring Main Unit) panel, clearly indicating its nature as “INCOMING” or “OUTGOING” and specifying the location or equipment being fed as directed by Engineer-in-Charge.. The identification boards shall be made of powder-coated galvanized iron sheet, securely fixed with screws or rivets, and shall have bold, legible block letters not less than 40 mm in height, painted or engraved in a contrasting color (e.g., black letters on white). The lettering and identification shall conform to the visibility and marking requirements of the Indian Electricity Rules. All boards shall be placed at a visible location on the front of each RMU way for clear identification and ease of maintenance. Channel partner / System Integrator / Authourized Partner/ License partner make RMU shall not be accepted. |
| 15 | Supply, installation, testing & commissioning of 5 Way Outdoor (IP54) 11kV 630Amps 21KA/3 sec. One side Extensible Ring Main Unit Compact switchgear consisting of 5 Nos. Fixed motorized Vacuum Circuit Breaker Module for two Incoming and One Outgoing Feeder and Copper Busbar in SF6 insulated stainless steel enclosure (2.5mm thick, SS304 grade). The complete RMU must be type tested for Internal arc 21KA for 1 sec with AFLR Classification for Gas tank & Cable Chamber. The Vaccum Interrupter must RMU manufacturer's own make. The complete RMU shall be consisting of followings:-Microprocessor based IDMT Relay for Circuit Breakers - Self Powered along with series trip coil (Modbus RS485 complaint) for each VCB Module.-Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder.-SF6 Gas pressure indicator on the gas tank.-Operating sequence of VCB must be O-3 min-CO-3 Mins-CO.and suitable for 2000 mechanical operation.-CT shall be minimum 100-50/1A ,2.5VA , 5P20 - 3 Nos. for protection.-CT shall be minimum 100-50/1A ,2.5VA , Class 0.5 - 3 Nos. for Ammeter.-Manometer for each Tank.-Right angle boot to be provided in each module and Foundation suitable for housing / fixing of RMU is included in rate quoted by contractor-2X12V, 26AH Battary with Charger - 1 Set.-Auxiliary VT shall be 11KV/230 ,500VA for AC supply input to Battary Charger. |
| 16 | -The Contractor shall provide and fix identification boards on each way of the RMU (Ring Main Unit) panel, clearly indicating its nature as “INCOMING” or “OUTGOING” and specifying the location or equipment being fed as directed by Engineer-in-Charge.. The identification boards shall be made of powder-coated galvanized iron sheet, securely fixed with screws or rivets, and shall have bold, legible block letters not less than 40 mm in height, painted or engraved in a contrasting color (e.g., black letters on white). The lettering and identification shall conform to the visibility and marking requirements of the Indian Electricity Rules. All boards shall be placed at a visible location on the front of each RMU way for clear identification and ease of maintenance. Channel partner / System Integrator / Authourized Partner/ License partner make RMU shall not be accepted. |
| 17 | Note for Srl item No 12 to 13:- (i) One no operating handle for manual isolator/ disconnector/ earthing operation and one No manometer shall be provided.(ii) The above swithgear shall confirm to relevant IEC for design, maufacturer, and internal are complince.(iii) PCC foundation for installing the outdoor RMU as per manufacturer drawing 1m above the ground level will be installed at work site with providing sufficient space of working for elect by the contractor.(iv) Testing and commission of RMU will be done through OEM and proper record of calibration and relay setting to be provided to the MES by contractor. (v) Providing of anticat and anticlimbing fencing, vertical post gap minimum 2m and distance from RMU minimum 1m.(vi) The empty space between RMU and fencing will be filled with stone aggregate of 20mm Size and shall be equally distributed with 50mm height from the ground. (vii) Suitable interlocking of mechanical/ electrical type in the RMU breakers has to be provided.(viii) The cost of the above points/ works deem to be including in the rates quoted and nothing extra on the account will be admissible. |
| 18 | Supply, Installation, Testing & Commissioning Factory Made ( CPRI Approved/ Tested Manufacturer) HT Bus Bar Chamber of suitable size completely enclosed with 3.15 mm CRCA Mild Steel Sheet suitable for Bus Bar rating of 100 Amps, 11 KV, 3 phase and 3 Way type, outgoing/incoming from panel enclosure through suitable Insulator Bushing for connecting cable end termination with Metal Sheet Enclosure including Door with locking arrangements, Outdoor type. All cable termination box should be mounted outside the main bus bar panel enclosure made out of 3.15mm CRCA Mild Steel Sheet, Powder coated, Dust and Vermin Proof with Rain Water Protection, Provision of HT 11 KV Post Insulators, 03 No. Fixed Inside with suitable Size Copper Bus-bars for Cable Connections and 11 KV, Danger Notice Board on Both Sides, having all Steel Metal Works including Frame shall be with Anti-corrosive Coating with 07 Tank Process and Finally Epoxy Polyester Powder coating of Siemens Grey RAL-7035 Shade, Panel to be fixed at 450mm above Natural Ground Level on Brick Masonry Platform including Cement Concrete 1:2:4 (20mm graded stone aggregates) 100mm thick around the Area upto 1.50 Metre in all directions from the Panel all as ordered including Provision of Cattle Fencing with Open-able Gate (1.20 Metre to 1.50 Metre in Height) around the Area upto 1.50 Metre, complete all as specified and as directed. |
| 19 | Srl Item No.14Contd/---- Note:- All provision of cable joint with panle main bus bar should be in such a way that main bus bar panel should not be open for any cable connection. |
| 20 | Supply & fix for XLPE insulated, armoured, aluminium conductor cable, 11000 volts grade, heavy duty, cross sectional area 185 sq mm ,3 core, laid in trenches/ducts/through pipe complete all as specified and directed. |
| 21 | S&F Double walled corrugated (DWC) pipe of size 120 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT/LT cable in under ground complete all as specified and directed. |
| 22 | M & L for Danger notice plate of size 25 X 20 CM & 1.6mm thick mild steel sheet vitreous enamelled white with letters figures in english hindi or urdu and conventional skull and bones in signal red colour and fixed with MS clamp bolts and nuts of approved size for HT complete all as specified and directed. |
| 23 | Supply and fixing Route indicator 900X200X200 mm with slant embosed facing including earth work and grouting 600mm below ground level complete all as specified and directed. |
| 24 | Material and labour for Road cutting for laying of HT/LT Cables / Pipes and making good the distrubued surfaces as equal to existing road finishes including refilling the excavated material, compacting , WBM and black top carpeting with biutemen & aggregate complete all as specified and directed. |
| 25 | Supply & fixing or laying Galvanised steel tubing light grade 100 mm dia (ISI marked) for protection of under ground cable on poles / walls under road crossingcomplete all as specified and directed. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |