| 1 | Name of Items |
| 2 | PART - A |
| 3 | Supply & Fixing of Street Light Fitting with mandatory driver set having die cast aluminium body and lenses 110 to 130 watt. Confirming to IP 66 protection having company LOGO engraved complete in all respect including labour as per direction of E/I. SI. No. 1424/2018 Cat-AAA. 15400-16500 system lumens High Power LED with Lenses, >1101m/W, PF>0.95 THD<10% at full load, CRI>70, Potted driver set (Not Circuitory) Phase to Phase Protection at 440V & > 300V auto cut and re-start feature, with 5 years warrantee. Make Havells, Philips, Bajaj. |
| 4 | S/B of 600mmx600mmx6mm G.I plate vertically for earthing with it top at least 3 mtr below G.L. complete with 20mm dia G.I. pipe and funnel for watering and 1 earthing lead of 1 No 8 to 10 SWG G.I. wire in 15mm dia G.I. pipe, plate up to switch board 30Cm C.I. frame with hinged cover masonry housing Alternate layers of charchole/coke and solt etc. as per direction of E/I. Complete in all respects. S.I.No-702/18. |
| 5 | S/F of 63 Amp 415 V metal clad TPN rewireable type switch fuse unit on angle iron bracket/Pole complete in all respects as per direction of E/I. SI. No. 316/18. CAT-B. |
| 6 | S/F of 40A TPN of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contractors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc, in case of TPN, complete in all respect as per direction of Engineer-in-charge. SI. No. 807/18 e(ii). |
| 7 | Supply & Fixing of Suspension type clamp made of 'Al' alloy and shall be capable of holding AL alloy messenger wire of compacted dia. The eye hook shall be made of forged or mild steel the clamp shall be provided with black weather resistant plastic coating of at least 1mm thickness to prevent insulation of phase conductor from chafing due to rubbing against the clamp it shall provided sufficient flexibility to allow the movement of clamp at both, straight and angle location its hard ware shall have good finished and all ferrous fitting eye hook bolts nut and washer shall be galvanized with zinc and it also includes all the cost of material T&P etc. required for proper completion of work as per direction of E/I. |
| 8 | Supply & Fixing of Dead end type clamp made of 'Al' alloy and U-bar shall be capable of holding AL alloy messenger wire of compacted dia. The eye hook shall be made of forged or mild steel the clamp shall be provided with black weather resistant plastic coating of at least 1mm thickness to prevent insulation of phase conductor from chafing due to rubbing against the clamp it shall provided sufficient flexibility to allow the movement of clamp at both, straight and angle location its hard ware shall have good finished and all ferrous fitting eye hook bolts nut and washer shall be galvanized with zinc and it also includes all the cost of material T&P etc. required for proper completion of work as per direction of E/I. |
| 9 | S/F of distribution board box for 3 phase ten way connection made of fiber sheet 450x300x200mm size complete with bus bar 25x5mm, neutral bus bar 20x5mm, along with clamps holes etc including the cost of material I T&P etc for proper completion of work. (PSR) |
| 10 | S/L of following size \\"Al\\" conductor P.V.C. insulated armoured served sheathed cable 1100V grade at a depth of 750mm. Below ground level over a cushion of 75mm. Thick sand alround and protected with burnt bricks on side an top on surface the cable run shall be fixed on MS clamp of suitable size, approved make as direction of E/I. complete in all respects. 501/2018. |
| 11 | a. 10 sq.mm 4 core |
| 12 | b. 25 sqmm 3.5 core |
| 13 | Supply & Fixing of following size palm or pin type copper tin plated cable socket (Lug) to the cable lead insulating with tape and making connection complete in all respects as per direction of E/I. S.I. No. 504/2018 |
| 14 | (a) 25 sq.mm. |
| 15 | (b) 95 sq.mm. |
| 16 | Supply & Fixing of piercing connector made of 'Al' alloy suitable of holding main conductor/tap conductor of compacted diameter the connector shall be coverd by the black weather resistant insulation cover made of polyethylene at least 2m thick to avoid short circuit and corrosion including the cost of material including T&P etc. for proper comletion of work as per direction of E/I. PSR. |
| 17 | S/L of Arial bunch cable 1100 V grade XLPE insulated KESCo. approved make confirming to latest relevant specification on steel/PCC supports including binding jumpering sagging and cost of material I T&P etc required for proper completion of work, approved make i.e. Havells, Polycab, Finolex, KEI as per direction of E/I. |
| 18 | (a) (3CX95+1X70+1X16) Sq.mm (Analsed) |
| 19 | (a) ( 1X25+1X16) Sq.mm |
| 20 | I- Cuting of branches ooof trees and shrubs from the road way or with in R.O.W including disposal of wood and leaves to suitable location as per technical specifiicaion Clause 1914. MORD-1900 (15.12). SOR 2023-24 (Civil) |
| 21 | PART - B |
| 22 | S/F of double pole structure with 2 nos S.S. pole 410 SP-61 in 1:3:6 CC foundation 1/6 of pole length below G.L. and plinth 30cm above G.L. 20cm thick around the pole with 1 nos. channel 100mmx50mm 1 Nos. channel 75mmx40mm necessary nuts bolts complete with painting etc. |
| 23 | S/E of 11 K.V. T.P.M.O. switch on pole including handle rod etc. complete in all respects. |
| 24 | S/E of 11 K.V. D.O. fuse set on pole complete in all respect. |
| 25 | S/E of 11 K.V L.A. set of 3 Nos. suitable for mounting on steel support complete in all respect as per direction of E/I. |
| 26 | S/F of 63 KVA 11/0.433 KV conventional 50Hz 3 Phase oil immersed naturally cooled distribution transformer confirming of ISI, UPPCL/Kesco specification complete in all respect make Crompton, Kirlosker, Areva, Kanohar (Meeraut), PME Noida, MEI Mirzapur & univac. |
| 27 | S/B of 600mmx600mmx6mm G.I plate vertically for earthing with it top at least 3 mtr below G.L. complete with 20mm dia G.I. pipe and funnel for watering and 1 earthing lead of 1 No 8 to 10 SWG G.I. wire in 15mm dia G.I. pipe, plate up to switch board 30Cm C.I. frame with hinged cover masonry housing Alternate layers of charchole/coke and solt etc. as per direction of E/I. Complete in all respects. S.I.No-702/18. |
| 28 | S/E of 2.24 mtr. Long cross arm 50mmx50mmx 6mm. Angle iron on pole including clamps, eye bolts with red enamel paint etc. as per direction of E/I. PSR(F.No. 13/23-24) |
| 29 | S/F of 11 KV Disc insulator including gun fitting on cross arm/clamps fixed on pole complete in all respects.(PSR) |
| 30 | S/E of over head line with A.C.S.R. conductor on pole/service bracket including binding etc. complete in all respects. S.I.No-627/18. Racoon/Dog |
| 31 | S/F of M.S. Channel 1.38 meter long on top pillar size 100x50mm as per direction of E/I. (Analysed) |
| 32 | S/B of earth rod 20mm dia 2.5 Mtr. Long including G.I. wire 7/16 SWG to connect earth rod to earth clamp on pole 3.0 mtr. Long steel conduit t carry earth wire along the pole. PSR. |
| 33 | S/L of following size cable \\"Al\\" conductor P.V.C. insulated armoured served sheathed cable 1100V grade at a depth of 750mm. Below ground level over a cushion of 75mm. Thick sand alround and protected with burnt bricks on side an top on surface the cable run shall be fixed on MS clamp of suitable size, approved make i.e. Havels, Polycab, Krishna, Gloster as direction of E/I. complete in all respects. 501/2018. |
| 34 | (a)50 Sq.mm 3½ Core |
| 35 | S/L of following size XLPE 11 K.V. H.T. cable proper completion of work as per direction of E/I (make Finolex, Havells, Gloster, Polycab) |
| 36 | (a) 70 Sq.mm (Analysed) |
| 37 | S/L of following size XLPE cable box with out door jointing kit proper completion of work make Rachem/Mahindra as per direction of E/I. |
| 38 | (a) 70 mm2 3 core (Analysed) |
| 39 | S/L of following size G.I. ''B'' class pipe at a depth of 750mm below ground level as cable carrier as direction of E/I.(PSR) |
| 40 | (a) 150 mm dia |
| 41 | S/L of 25×3mm GI strip from earth electrode complete in all respect. (I.No. 716/18) |
| 42 | S/F of Henley type switch fuse unit complete in all respect as per direction of E/I. (PSR Fl No.-54/22-23) |
| 43 | PART - C (AMC of Street Light work) |
| 44 | Operation & annual maintanence of street light installed for 2 year/365 days per year. Please Enable Macros to View BoQ information |